INSTALLATION

PAGE 6

ENGLISH

Hazard of Explosion! Never use an open flame to detect gas 
leaks. Explosive conditions may occur. Use a leak test solution 

or other approved methods for leak testing. Failure to follow 
recommended safe leak test procedures could result In death 

or serious injury or equipment or property damage. 

Use only dry nitrogen with a pressure regulator for 

pressurizing unit. Do not use acetylene, oxygen or 
compressed air or mixtures containing them for pressure 
testing. Do not use mixtures of a hydrogen containing 
refrigerant and air above atmospheric pressure for pressure 
testing as they may become flammable and could result in 
an explosion. Refrigerant, when used as a trace gas should 
only be mixed with dry nitrogen for pressurizing units. Failure 

to follow these recommendations could result in death or 

serious injury or equipment or property damage.

5.1

 Step - 5.1

 

Using a tank of nitrogen with attached regulator, charge the 
system with 500 PSIG of dry nitrogen. Use adapter AD-87 

(field supplied) to connect to the valve. Check for leaks at the 
flare fittings using soap bubbles or other detection methods. 

If a leak is detected, repair and recheck. If no leaks are 
detected, proceed to evacuate the system.    

Step 5.1

Step 5.3

Step 5.2

Step 5.4A

Step 5.5A

Step 5.6

Step 5.4B

Step 5.5B

Illustration 5

Leak Test

System Evacuation

Step 5 - Leak Test and Evacuation 

5.2

 Step - 5.2

 

Attach a manifold gauge, micron gauge, and vacuum pump 

to the suction line port using adapter AD-87 (field supplied).  

(Illustration 5)

Evacuate the system to 350 microns.
Close the vacuum pump valve and check the micron 
gauge. If the gauge rises above 500 microns in 60 seconds, 
evacuation is incomplete or there is a leak in the system. If 
the gauge does not rise above 500 microns in 60 seconds, 
evacuation is complete.

5.3

 Step - 5.3

 

Remove the adapter and hose connection from the suction 

line port, and replace the cap.

5.4

 Step - 5.4A & 5.4B

 

Remove the cap from the liquid line valve. Using the hex 

wrench, open the valve, then replace and tighten the cap. 

5.5

 Step - 5.5A & 5.5B

 

Remove the cap from the suction line valve. Using the hex 

wrench, open the valve, then replace and tighten the cap.

5.6

 Step - 5.6

 

Wrap the lineset, drain line, and wiring starting at the bottom 
of the bundle with an overlap type wrap, concluding at the 

Содержание HSU12VHGDB-G

Страница 1: ...VHG DB G Installation Manual Step 1 Preparation 2 Step 2 Installation of the Indoor Unit 3 Step 3 Installation of the Outdoor Unit 4 Step 4 Interconnecting the Indoor and Outdoor Units 5 Step 5 Leak Test and Evacuation 6 Step 6 Charging 7 Section 7 Explaining Operation to the End User 8 8 Section 9 Seacoast Application 8 Table of Contents 0010586614 ...

Страница 2: ...r if there is a concern about a dangerous level of refrigerant concentration in the case of refrigerant leakage add extra ventilation 5 Avoid installing the outdoor unit where corrosive gases such as sulfur oxides am monia and sulfurous gas are produced If unavoidable consult with an installation specialist about using a corrosion proof or anti rust additive to protect the unit coils Choose a plac...

Страница 3: ...where the piping hole is to be drilled 2 6 Step 2 6 Drill the piping hole using a hole saw of the correct diameter Angle the drill with a downward pitch to the outside wall so that the outside hole will be lower than the inside hole giving the hole the proper angle for condensate drainage 2 7 Step 2 7 Install the piping hole cover flange at the hole opening on the inside wall NOTE The cover flange...

Страница 4: ...eat Pump models only 3 1 Step 3 1 If attaching the supplied drain elbow to the outdoor unit do so prior to attaching the refrigerant lines and wiring Extension piping to attach to this fitting is field supplied Step 3 2 Step 3 1 Mounting the Indoor Unit Onto the Wall Plate Electrical Connections for the Indoor Unit 2 11 Step 2 11A 2 11B To make the electrical connections for the indoor unit two co...

Страница 5: ...ng the Indoor and Outdoor Units Piping The standard lineset length is 25ft If the installation length is 12K 18K and 5 oz ft for the 24K model Illustration 4 outdoor unit valves chart 4 1 Step 4 1 Refrigerant piping connections for the mini split system are use caution to prevent dirt or debris from entering the tubing Remember to place the nut on the pipe before creating the 4 2 Step 4 2 To join ...

Страница 6: ...k for leaks at the flare fittings using soap bubbles or other detection methods If a leak is detected repair and recheck If no leaks are detected proceed to evacuate the system Step 5 1 Step 5 3 Step 5 2 Step 5 4A Step 5 5A Step 5 6 Step 5 4B Step 5 5B Illustration 5 Leak Test System Evacuation Step 5 Leak Test and Evacuation 5 2 Step 5 2 Attach a manifold gauge micron gauge and vacuum pump to the...

Страница 7: ...efrigerant charge of the product 2 the additional refrigerant amount charged in the field and 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product The filled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refriger...

Страница 8: ...ING INSTRUCTIONS carefully Section 7 Explaining Operation to the End User Section 8 System Specifications Section 9 Seacoast Application The outdoor unit should be installed at least mile away from the salt water including seacoasts and inland waterways If the unit installed from mile to 5 miles away from the salt water including seacoasts and inland waterways please follow the installation instru...

Страница 9: ... This page intentionally left blank ...

Страница 10: ... com Haier America Wayne NJ 07470 2015 Haier America Trading LLC Model HSU09VHG DB W HSU09VHG DB G HSU12VHG DB W HSU12VHG DB G HSU18VHH DB W HSU18VHH DB G HSU24VHG DB W HSU24VHG DB G Issued Date Update July 2016 ...

Отзывы: