Haier HSU-09H03/K(F) Скачать руководство пользователя страница 4

Outdoor unit

1.Connection of pipes

2.Attaching Drain-Elbow

To bend a pipe, give the roundness as large as possible not to crush the pipe

Connecting the pipe of gas side first makes working easier.

The max vertical distance between the indoor unit and the outdoor unit is 5 m.

 If the drain-elbow is used, please attach it as

 figure. (Note: Only for heat pump unit.)

Half union

Flare nut

Spanner

Torque wrench

4

Outdoor unit

Forced fastening without careful centering

may damage the threads and cause a

leakage of gas.

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

3.Purging Method:

Push the air out of the indoor unit and piping as followes:

Tighten the caps on the valves with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 20g  refrigerant shall be added per

 exceeding meter. Charge according to the following list.

Piping length

Additional amount

5m

7m

No need

40g

10m

100g

for     09k  12k

Max. Length: for 9k    A=7m

Max.Elevation:B=5m

for 12k  A=10m

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

B

A

C

Outdoor unit

Indoor unit

Oil trap

A

B

CAUTION

In case more than 5 metres

oil trap

should be installed every 5~7m.

C

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Gas side  9.52mm(3/8")

Fastening torque

18N.m

40N.m

Gas side  12.7mm(1/2")

55N.m