system or the refrigerating system .There is general no trouble indicating instrument mounted on the 

domestic refrigerator ,locations and natures of troubles should be determined according to their 

respective features ,therefore ,experience in servicing is very important to troubleshooting .Service 

technicians with rich experience can correctly locate them and take reasonable remedy    measures 

based on their comprehensive analysis of trouble characteristics as well as operating conditions for 

various kinds of refrigerators .   

Three Essentials for Checkup   

1) Look   

 a) Check the tubing of refrigerating system for cracks and various welding points for leaks ;if 

leakage occurs ,an oil stain can be seen definitely .     

b) Check the suction and exhaust pressure values (high pressure and low pressure) of compressor 

to see whether they are normal .     

c) Check the conditions of frost attached to its evaporator and gas return tube .It is abnormal if frost 

has formed on part of the evaporator or there is no frost attached to it .     

d) Pay attention to the speed of temperature drop inside freezer compartment .It is abnormal if the 

speed of temperature drop is obviously slower than the corresponding normal speed .     

e) Check the environment to see whether it is suitable for placing a refrigerator .   

f) Check refrigerator door seal ,case ,table surface and heat insulation layer .     

g) Look at the main control board to ascertain if various indication states are normal.   

   

2) Listen   

a) Listen to the noises produced when the compressor is running Hums from a fully enclosed 

aggregate unit is the sound caused by overload indicating that the motor cannot be started 

normally ,meanwhile ,a clattering sound can be heard from inside the start relay ,which is produced 

because the start contacts cannot be released normally .A whistling sound is caused by the high 

pressure gas flowing out of the crack of the pressure tube inside the compressor ,and clucks are the 

sound of striking after the suspended spring inside the compressor has broken .   

During the normal operation of compressor ,a slight and uniform hum sound due to undulation of 

electric current can be heard generally ,this is a normal phenomenon .However ,if it sounds like 

“tong ,tong …”,i.e., an impact sound inside the compressor ,this means that a large quantity of wet 

vapour of  refrigerant or refrigerating oil has come into the compressor cylinder ;if it sounds like 

“dang ,dang…”,    a striking sound of metal parts inside the compressor ,this means that some moving 

parts have loosened (note to differentiate this   

sound from those formed during starting or stopping the compressor).       

b) Listen to the sound caused by the flowing of gas in the evaporator Open the refrigerator door 

while the compressor is in operation ,incline your ear and listen attentively the gas flow sound inside 

the evaporator .If it sounds like gentle whistling accompanied by a sound similar to water flowing ,this 

is the sound produced by the normal circulation of refrigerant within the evaporator .In case only the 

gas flowing sound can be heard and there is no water flowing sound ,this indicates that the refrigerant 

has already percolated .If neither the flowing sound nor the gas sounds from the evaporator can be 

heard ,this means that the filter or capillary has been clogged .   

   

3)Touch and Feel   

a) Feel the compressor when running ,its temperature should be generally less than 90

 in the 

Содержание HRN 186

Страница 1: ...NG SERVICE Refrigerator SERVICE MANUAL Features 1 Mechanical temperature control 2 Front positioned adjustable thermostat 3 100 HFC free and FCKW free 4 External condenser and adjustable feet 5 Reversible door with magnetic seal 6 stylish interior light MODEL HRN 186 Haier Group ...

Страница 2: ...ENTS CONTENTS 1 SAFETY PRECAUTIONS 2 SPECIFICATIONS 4 PARTS IDENTIFICATIONS 6 SYSTEM FLOW PRINCIPLE 7 CIRCUIT DIAGRAM 8 MAINTENANCE SERVICE AND TROUBLE SHOOTING 9 ANALYSIS OF TROUBLES AND TROUBLESHOOTING 13 ...

Страница 3: ...sor or an abnormal sound from the compressor in operation In this condition an automatic voltage regulator over 750W should be added 11 Take care not to damage the supply line Don t yank at the line pull the plug out gently from the receptacle Don t press the line under the cabinet or step on it Take care not to roll on or damage the supply line when moves the machine from the wall 12 Don t use th...

Страница 4: ...it at a damp place else the insulation of the refrigerator may be impaired 21 Any disassembly or alternation to the refrigerator is strictly forbidden Damage to the refrigeration pipeline is prohibited Service to the refrigerator must be carried out by professionals 22 Don t put bottles of bear and other drinks into the refrigerator else the bottles may be cracked with cold 23 Pull out the plug of...

Страница 5: ...osting H manual A automatic Fridge Freez H Defrost water outlet Air circulating ventilator Yes Kind of coolant R134a R600a R600a Foaming components C P 3 Technical data Voltage frequency V Hz 220 240 V 50 Input power mains fuse minimum W A 110 0 5 Temperature range from to Fridge Freez C 0 10 4 Aesthetics Colours see L Top cover White Cabinet White Door Frame White Fascia panel Handle White Inside...

Страница 6: ...ble thermostat Yes Fast freeze switch Interior light W YES Adjustable feet front rear n front Castors front rear 6 Product dimensions Unit dimensions H W D cm 84 5 54 7 57 Depth with open door cm 108 Net weight kg 39 0 7 Packing dimensions loadability Packing dimensions H W D cm 88 5x 57 8 x59 8 Gross weight kg 42 0 8 Recycling symbols Carton weight in g kg 2 5 9 Service Users instruction language...

Страница 7: ...PARTS IDENTIFICATIONS 1 top cover 2 drawers 3 adjusted feet 4 condensor 5 compressor ...

Страница 8: ...f Refrigerating Principle 2 Brief Description of System Flow Chart 3 6 series is a direct cooling single system refrigerator which has a freezer compartment When the refrigerator is just powered on the refrigerant flows in the sequence 1 2 3 4 5 ...

Страница 9: ...CIRCUIT DIAGRAM CIRCUIT DIAGRAM ...

Страница 10: ...MAINTENANCE SERVICE AND TROUBLE SHOOTING ...

Страница 11: ... distinctly at night 3 The compressor consists of an electric motor and a compressing apparatus During its normal operation the motor s stator core and windings will rise to a temperature in the range of 100 110 and the temperature of the piston and cylinder of the compressing mechanism can also reach as above 100 due to the heat produced when compressing refrigerant Most of the heat radiates to t...

Страница 12: ...indicating that the motor cannot be started normally meanwhile a clattering sound can be heard from inside the start relay which is produced because the start contacts cannot be released normally A whistling sound is caused by the high pressure gas flowing out of the crack of the pressure tube inside the compressor and clucks are the sound of striking after the suspended spring inside the compress...

Страница 13: ...t meshes of its screen has been clogged resulting in an obstructed flowing of refrigerant thus causing a drop in temperature due to throttling d Feel the temperature of exhaust gas from the refrigerating system the exhaust gas should be very hot and this is the normal working state For those refrigerator with enclosed type of compressor refrigerating system no frost or dew drop will from on the ga...

Страница 14: ... m ain control board is norm al W hether each contact of m ain control board is norm al T ighten each contact and test m achine again Y Trouble of lighting and display system A djust the grade according to fact C om pressor is open circuit or short circuit Inner trouble of com pressor If it is infinite or 0 then the starter is out of w ork H eat protector is out of w ork C apacitance is out of w o...

Страница 15: ...tion to those parts that are liable to leak check main connection points for oil seepage and tubing for cracks If there is no severer leak point charge the system with nitrogen and detect leak points with the commonly adopted method repair them evacuate charge the system with refrigerant and then turn on the refrigerator to make a test run 2 Too much refrigerant charged into the system ANALYSIS OF...

Страница 16: ...igh and low pressures with pressure gauges to see whether they are Normal If an abnormal sound comes from the compressor or the temperature of its Causing is too high Cut the discharge port open and operate the compressor feel it if There is pressure at the discharge port with your finger For a normal compressor its Discharge port is difficult to be blocked with your finger if you just apply a lit...

Страница 17: ... replacing the dry filter with a new one or clearing it thoroughly recharge the system with refrigerant and seal the charging port B No Refrigerating The phenomenon that the compressor runs normally but no frost or only a little frost appears on the evaporator and the refrigerator temperature does not drop down is called no refrigerating There are many causes for this trouble and it is relatively ...

Страница 18: ... charge the system with the filtered refrigerant However the commonly adopted method is to connect a filter with moisture absorbers such as silica gel anhydrous calcium chloride to the refrigerating system so as to filter out the moisture from the system then replace the filter evacuate it again and finally charge the system with refrigerant b Clogged with dirt in capillary ANALYSIS OF TROUBLE The...

Страница 19: ...es stop the compressor at once and if technique is available open the cylinder cover and check up the valve block repair it or replace it with a new one C Sudden stop of Compressor during Its Running The cause of sudden stop of a compressor during its running is mostly that the gas suction pressure and or discharge pressure exceed their respective prescribed ranges thus making a pressure operated ...

Страница 20: ...rmally If this cannot be achieved and the stoppage still occurs repeatedly it is most likely that the mechanical parts or contacts are out of order disassemble the thermostat make a thorough checkup and repair it b Overload of electric motor ANALYSIS OF TROUBLE Probably too many things have been put into the refrigerator and hence the thermal load exceeds its refrigerating capacity or in case the ...

Страница 21: ... value it will be difficult to start the motor and a hum sound can be heard from it REMEDY Measure the voltage with a voltmeter if it is really too low give directions to the user for buying a stabilizer so as to step up the voltage thus normal operation can be achieved 3 Check the thermal relay to see whether its contacts are closed ANALYSIS OF TROUBLE Three suspended spring inside the compressor...

Страница 22: ...l these will cause poor contact in electricity REMEDY Dismantle it to repair or replace it with a new one c Poor electric contactor in thermostat ANALYSIS OF TROUBLE Burnout of contactor and leakage of temperature sensing agent may occur generally REMEDY Replace the old with a new one d Check the terminals for loose connection and electric circuits for other abnormal phenomena 5 Mechanical faults ...

Страница 23: ...t reach its rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in the temperature sensor is also hotter therefore the thermostat is unable to cut off the power supply to the compressor and stop it REMEDY If it has been found that the refrigerant in the system is insufficient in quantit...

Страница 24: ...arts with your hand Test the refrigerator with a test pencil it will light up intensively measure the resistance between the power cord plug and the case body with an avometer the reading will be zero 0 in the worst case the fuse will be blown Check the 3 prong outlet to see whether the live wire and the null line are inversely connected this makes the ground protection lead out from the power cor...

Страница 25: ...zer poor cooling Display section for freezer appear F4 enclosed bar of freezer gap or broken Maintain technics of sensor Repair the Enclosed bar Check and adjust the circuitry Open the switch of equalize low temperature Conduct user to use it properly Maintain technics of sensor Repair the Enclosed bar Y N Y N Y N Y Y N N Y Y Y Y Y N Y Y N N Y If it抯mechanical refrigerator change the tache of disp...

Страница 26: ......

Отзывы: