– 17 –
All-Electric
Heat OFF
All-Electric
Heat OFF
Fan Boost
Mode OFF
Fan Boost
Mode ON
Heat Boost
OFF
Heat Boost
ON
Nomenclature Example
AZ95E09DACK2
Engineering Revision
Mode 7 Fan Boost Mode
This setting is used when the unit is installed with
more restrictive duct work where additional
airflow
is needed. This increases the fan speed to ensure
proper circulation.
Press
MODE
until a
7
appears in the first digit of the
display. Press the
-
pad for
OFF
“
“ or the
+
pad
for
ON
“
”. This is shown in the second digit of the
display. Press
AUX
to lock in selection and exit
AUX
mode.
The default setting for Mode 7 is
OFF
.
Mode 8 All-Electric Heat (AZ95H Only)
This electric heat option functions only on the AZ95H
model. When this option is
ON
" ", heat pump
operation is locked out, causing the unit to provide
only electric resistance heat.
To set
All-Electric Heat
option, press
MODE
until
an
8
appears in the first digit of the display. Press
the
-
pad for
OFF
“ “ or the
+
pad for ON “
”. This
is shown in the second digit of the display.
The default setting for Mode 8 is
OFF
.
Mode 9 Heat Boost (AZ95H Only)
When
Heat Boost is ON
, supplementary electric
heat is added to the heat pump operation to help
maintain a consistent, comfortable room temperature.
To set Heat Boost, press
MODE
until a
9
appears
in the first digit of the display. Press the
-
pad for
OFF
“
” or the
+
pad for
ON
“
”. This is shown in
the second digit of the display. Press
AUX
to lock in
selection and exit
AUX
mode.
The default setting for Mode 9 is
OFF
.
Mode P Engineering Revision Setup
This setting is used to configure the unit when the
circuit board is replaced.
The first time the unit is powered after a service
board is installed, the unit will automatically enter this
mode. The UI will read
P1
. Press the
+
pad until the
number matches the engineering revision as shown.
The engineering revision is the last number in the
model number. Press
AUX
to save and exit.
The engineering revision may be adjusted after the
first power cycle using
AUX
. Press
MODE
until
P
appears in the first digit, and follow the steps
described above.
П
П
П
П
П
П
П