ERROR CODES AND TROUBLESHOOTING
PAGE 30
ENGLISH
Check This First
Outdoor Unit
Models:
1U24TL2HFA
1U3036TL2HFA
ASH124TRDFA
ASH3036TRDFA
Line voltage available at:
1. TERMINAL STRIP - 1(N) & 2 (L)
2. AC-L & AC-N at the PCB - CN2 & CN1
3. AC-L OUT & AC-N OUT at the PCB - CN8 & CN9
4. AC-L & AC-N at the IPM - CN1 & CN2 (24K/30K/36K)
310+ VDC available at:
1. P & N at the IPM - CN8 & CN9 (24K/30K/36K)
2. P & N at the PCB - CN24 & CN26
Module power 5-G-15 VDC available at:
1. CN23 at the PCB
2. CN11 at the IPM
Module COM 5-G-15 VDC available at:
1. CN22 AT THE PCB
2. CN10 AT THE IPM
• 1 (N) and 3 (C): 0-80
VAC fluctuating
• 2 (L) and 3 (C):
0-140 VAC
fluctuating
Wiring Diagram Reference
ENGLISH
Outdoor Board Diagram
12K-18K
OUTDOOR UNIT WIRING DIAGRAM
0011509127A
OUTDOOR UNIT WIRING DIAGRAM
COMPRESSOR
●
●
B
Y/G
1
2
3(
C)
N
L
BL
BR
BR
BR
BL
Y/G
Y/G
0011520512
Electrical Shock Hazard
Capacitor retains charge a er
voltage at capacitor has dissipated
(<10V DC) with hand held voltmeter
before servicing. LED2 light
between CN24 and CN26 should be
Riesgo de Descarga Eléctrica
El capacitorre enecargaunavez
voltaje del capacitor se haya disipado (<10V
DC) apoyando la mano sobre el vol metro
antes de realizar el servicio técnico. La luz
LED2 que se encuentra entre CN24 y CN26
deberá estar apagada.
Risque de choc électrique
Le condensateur conserve sa charge après la
coupure de l’alimenta on électrique. Avant
de procéder à une répara
courant au condensateur s’est dissipé
(<10 VCC) à l’aide d’un voltmètre manuel. Le
voyant LED2 entre CN24 et CN26 doit être
éteint.
Conditions Needed for Basic Operation
3-minutes of time delay from the call for heating or cooling
Error Codes and Troubleshooting