Haier DW-86L288 Скачать руководство пользователя страница 13

14

Notes:

A flashing alarm light cannot be cancelled unless the root cause for the alarm is eliminated.
The buzzing alarm can be temporarily silenced for 30 minutes by pressing the alarm silence
button. However, if the problem is not fixed, the buzzer alarm will resume after 30 minutes.
The freezer is equipped with a rechargeable battery controlled by a power switch. Before
operating the freezer, this switch must be turned on.

Once the unit is plugged into the

specified voltage, the unit operates to charge the battery. When there is a power outage, the
battery sustains the temperature display. If the battery voltage is less than a threshold, the
temperature display turns off.

While the battery is still capable of providing power to the

display, the temperature display can be turned off by unplugging the power cord and turning
off the battery control switch.
The freezer is also designed to auto-adjust the inner temperature set point at high ambient.
When the ambient temperature is warmer than 32

and the set point temperature is set to be

lower than -82

, the set point temperature will automatically default to -82

. If the ambient

temperature is equal to or cooler than 32

, the set point will resume to the intended inner set

point. This feature extends the life expectancy of the freezer.

Buzzer alarm resumption after cancellation

Remote alarm terminals

When the unit is in the alarm mode, you may press the

to stop the buzzing of

the alarm. However, the remote alarm cannot be cancelled. If the alarm condition still persists
after 30 minutes, the buzzer alarm resumes automatically.

Silence

key

Remote alarm terminals are located in the machine compartment in the back of the unit. The
alarm signal is delivered via the terminals. The terminals are rated for 24 VDC at 1 A. The power
for remote alarm system must be connected with the wire or battery with UL certificate.

Under normal operating conditions, the terminals with wires are open. When the unit is in the
alarm mode, the two terminals with wires are in the closed mode. The following schematic is a
wiring diagram.

Terminal output

Remote alarm terminal with brown wire

Remote alarm terminal with blue wire

Connect with remote
alarm terminal with brown
wire

Connect with remote alarm
terminal with blue wire

DC power source

Alarm device

Display and Alarms

11

The procedure to change the freezer temperature is as follows.

1.In order to change the setting of the freezer, the freezer's control must be unlocked
first. The temperature display flashes when the up or down arrow is pushed. Push the
up or down arrow again to change the display to security code mode then enter the
initial value 06. Push the

key for 5 seconds. The locking sign turns off. This

means the unit is in unlocked mode. Push the

SET

key again to select the mode for

the temperature set point value, high temperature alarm value and low temperature
alarm value. The matching indicator lights up as each function is chosen.

SET

2.Freezer temperature set point: Push the

SET

key. Once the Inner Temp.indicator

is on, the temperature set point area flashes. To change the temperature set point,
push the

or

key intermittently to increase or decrease the temperature

setting by 1

. After the adjustment is done, do not make any further changes for 10

seconds. The temperature display stops flashing. The unit enters the locked mode.
The temperature range is -10

to -86

.

3.Setting of high temperature alarm:Push the

SET

key to turn on the High Temp.

Alarm light. The temperature display flashes. To change the high temperature alarm of
the unit, push the

or

key intermittently to increase or decrease the

temperature setting by 1

. After the adjustment is complete, do not make any further

changes for 10 seconds. The temperature display stops flashing. The unit enters the
locked mode.

When the freezer temperature is warmer than the high temperature

alarm set point, the unit's alarm sounds, and the high temperature alert light flashes.
High temperature alarm set point can only be set to a value of at least 5

warmer than

the set point temperature of the unit. The high temperature alarm value cannot be set
to exceed the maximum limit.

4.Setting of low temperature alarm: Push the

SET

key to turn on the Low Temp.

Alarm light.To change the high temperature alarm of the unit,push the

or

key intermittently to increase or decrease the temperature setting by 1

. After the

adjustment is complete, do not make any further changes for 10 seconds.

The

temperature display stops flashing.

The unit enters the locked mode.

The low

ULT FREEZER

Alarms

SET

Silence

V

-80

Run

Voltage Regulator

Temperature Adjustment and Setting

Содержание DW-86L288

Страница 1: ... for future reference Haier Medical and Laboratory Co Ltd This product is suitable for ultra low temperature storage of products in applications such as clinical pharmaceutical scientific research and epidemic institutions User Manual For Haier DW 86L288 388 628 386 626 Ultra Low Temperature Storage Freezer DW 86W420 ...

Страница 2: ...on Information 7 Installation 8 Initial Loading 9 Temperature Adjustment and Setting 11 Display and Alarms 13 Routine Maintenance 15 Troubleshooting Guide 16 Recycle Rechargeable Battery 17 Specifications 18 Schematic Diagrams Refrigeration and Wiring Diagram 19 Optional Accessories 20 Technical Service 24 The actual design color and door pattern of the unit you received may vary as a result of co...

Страница 3: ...tions They include compressor delay protection low voltage booster and high voltage protection The refrigeration system for the unit features a balanced cascade technology powered by low temperature rated speciality compressor Innovative and integrated design of the door lock and handle provide convenient application Advanced LED display on the freezer can display the cabinet temperature set point...

Страница 4: ...Racks Storage box CO and LN2 backup cooling system 2 For installation and instructions for operation please refer to the user s manual shipped with the system Warning Any equipment using CO can displace oxygen in the surrounding area Please verify that there is sufficient ventilation around the workplace If there is limited ventilation alternative means to ensure a safer environment must be employ...

Страница 5: ...perate this product Customers are advised to follow instructions provided to avoid potential damage to product and injury to operators Note Use this product only in the way described in the product literature and this manual Before using it verify that this product is suitable for its intended use Do not modify system components or use unauthorized parts as this will void the product warranty This...

Страница 6: ...t the equipment should be located in a safe zone Improper usage of the equipment with this type of materials may hurt the environment or operator s health Installation and maintanence of your Haier ULT should be carried out only after reading this manual Equipment Instrument Services can install and validate your unit please call local Haier sales and service center 4 Proper Usage Optional Accesso...

Страница 7: ...this time if the LED stops flashing the supplementary power supply is normal If the LED continues to flashes it means that the power supply is under capacity requirement It is necessary to replace the battery The LED green light is off when there is sufficient power to the recorder 9V battery Button Hand Dateline Screw fixing Recorder Figure 5 The Temperature Recorder Button 5 If there is leakage ...

Страница 8: ...ts The cold temperature of the products and the interior wall may cause the skin to burn During any repair operation gloves should be worn to avoid injury by sharp edges or corners The air filter for the condenser should be cleaned regularly Freezer temperature could be compromised If a unit is out of service for a long period of time make sure the power cord is unplugged Deteriorated insulation o...

Страница 9: ...load is being introduced The temperature display indicates the temperature where the temperature sensor is mounted inside the unit chamber Temperature uniformity within the chamber may vary from the sensor location due to loading patterns or insufficient temperature stabilization time An access port is installed in the back wall of the unit which can be used as the through hole for the thermocoupl...

Страница 10: ...y to avoid damage to property 2 There should be at least 30 centimeters space all around the unit for good ventilation for heat removal 3 The location for installation should be flat and firm 4 There should be good ventilation and no direct sunlight 5 The freezer unit cannot share the same power socket with another piece of equipment The power plug should be securely connected with the power socke...

Страница 11: ... legs Rotate the leveling legs clockwise to extend them out to anchor to the floor to ensure the unit does not move while in usage 3 Grounding Warning A socket with proper grounding must be used for the equipment If the socket is not grounded an upgrade of the power socket to include grounding must be done by a qualified technician Do not use gas lines water mains telephone lines or lightening rod...

Страница 12: ...an the unit Then use a dry cloth to wipe off the left over detergent solution Non diluted detergent can harm plastic surfaces Please follow the instructions on how to mix a detergent solution Do not pour water directly onto the exterior and interior of the unit Water can damage the electrical insulation causing malfunction Compressors and other mechanical parts are hermetically sealed They do not ...

Страница 13: ...wn wire Connect with remote alarm terminal with blue wire DC power source Alarm device Display and Alarms 11 The procedure to change the freezer temperature is as follows 1 In order to change the setting of the freezer the freezer s control must be unlocked first The temperature display flashes when the up or down arrow is pushed Push the up or down arrow again to change the display to security co...

Страница 14: ...re set point temperature and current voltage The display shows the following indicator lights Locked indicator When the light is on it means all set values are in the locked mode This is to prevent erroneous operations Network indicator The indicator suggests that the network is in working mode Run indicator When the light is on it means the compressors are in working mode Regulator indicator The ...