background image

4. The wiring method should be in line with
the local wiring standard.

5. The power cable and connecting cable are
self-provided.The requirement of the
connecting cable:

All the cables shall have got the local
authentication certificate.

6. The breaker of the air conditioner should
be all-pole switch; and the distance between
its two contacts should be no less than 3mm.
Such means for disconnection must be
incorporation in the fixed wiring.

7. The waste battery shall be disposed
properly.

8. The indoor unit installation height is at
least 2m.

9. The appliance is not intended for ase
young children or infirm persons without
super vision.

10. Young children should be supervised to
ensure that they do not play with the
applience.

2

    All electrical repairs must be carried out
by qualified electricians. Inadequate repairs
may result in a major source of danger for
the user of the air conditioner.

  Do not damage any parts of the air
conditioner that carry refrigerant by
piercing or perforating the air conditioner's
tubes with sharp or pointed items, crushing
or twisting any tubes, or scraping the
coatings off the surfaces. If the refrigerant
spurts out and gets into eyes, it may result
in serious eye injuries.

   Do not obstruct or cover the ventilation
grille of the air conditioner. Do not put
fingers or any other things into the
inlet/outlet and swing louver.

   Do not allow children to play with the air
conditioner. In no case should children be
allowed to sit on the outdoor unit.

Specifications

The refrigerating circuit is leak-proof.

1. Applicable ambient temperature range:

The machine is adaptive in following
situation

2. If the supply cord is damaged, it must be
replaced by the manufacturer or its service
agent  or a similar qualified person.

3. If the fuse on PC board is broken, please
change it with the type of T 3.15A /250VAC

Cooling

Heating

Indoor

outdoor

Rated    Maximum   Minimum
  27              32               18
  19              23               14
  35              43               10
  24              26                 6
  20              27               15
 14.5             --                 --
   7               24                -7
   6               18                 --

DB  C
WB  C
DB  C
WB  C

Indoor

outdoor

DB  C
WB  C

DB  C
WB  C

Cautions

Model

AS072XVERA
AS092XVERA
AS122XVERA
AS182XVERA

Connecting cable

H05RN-F 3G 2.5mm

2

(For power)

H05RN-F 2X1.5mm

2

(For signal,

must use sheilded wires)

Содержание AS072XVERA

Страница 1: ...LTI SPLIT SERIES ROOM AIR CONDITIONER OPERATION INSTALLATION MANUAL Please read this manual carefully before using this air conditioner Please keep this manual safely for future use AS072XVERA AS092XVERA AS122XVERA AS182XVERA No 0010576789 B ...

Страница 2: ...ecautions Parts and Functions Operation Notes for safety Operation and Maintenance Trouble shooting Customer Need to know Instructions to installation When trouble happens Failure code 1 2 3 5 6 7 8 18 19 20 21 22 23 24 29 30 31 ...

Страница 3: ...paper disposal service The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house Safety Instructions and Warnings Before starting the air conditioner read the information given in the User s Guide c...

Страница 4: ... perforating the air conditioner s tubes with sharp or pointed items crushing or twisting any tubes or scraping the coatings off the surfaces If the refrigerant spurts out and gets into eyes it may result in serious eye injuries Do not obstruct or cover the ventilation grille of the air conditioner Do not put fingers or any other things into the inlet outlet and swing louver Do not allow children ...

Страница 5: ...ainten ance and repairment may cause water leak electrical shock and fire hazard switch off Please let the dealer be responsible for installing the conditioner Incorrect installation may cause water leak elec trical shock and fire hazard Don t put fingers or any other things into the inlet outlet and swing louver while the condi tioner is in operation Because the highspeed fan is very dangerous an...

Страница 6: ...ted to placed on or stand on outdoor unit The falling of goods and people may cause acci dents Pets and plants should not be blowed directly in the air flow Otherwise will suffer damage Don t operate the air conditioner with damp hands Otherwise will be shocked Only use correctly typed fuse May not use wire or any other materials replacing fuse otherwise may cause faults or fire accidents Don t pl...

Страница 7: ...rating noise Air conditioner should be located in well vented and easily accessible place Air conditioner should not be located in the following places a Places with machine oils or other oil vapours b Seaside with high salt content in the air c Near to hot spring with high content of sulfide gases d Area with frequent fluctuation of voltage e g factory etc e In vehicles or ships f Kitchen with he...

Страница 8: ...Parts and Functions 6 Front panel Air inlet grille Louver Display board INDOOR UNIT FRONT VIEW INDOOR UNIT BACK VIEW Signal receiver Mounting plate Heat preservation pipe Connecting pipes Drainage pipes ...

Страница 9: ...the electric power of the battery is insufficient Timer ON OFF display Fan speed and air sending direction display Swing direction display Room temperature display Sterilize display This function is optional Humidifying display Clock display Temperature display Used to display the set temperature Lock state display Sleep state display Electric Heating display 2 SWING 29 STERILIZE Fresh Air state d...

Страница 10: ...ype fluorescent lamp or change over type fluorescent lamp or wireless telephone is installed in the room the receiver is apt to be disturbed in receiving the signal so the distance to the indoor unit should be shorter 2R 03 dry batteries MINUT ES Confirmation indicator In disorderation reload the batteries or load the new batteries after 5 mins Note The waster batteries should be disposed properly...

Страница 11: ...ed displayed on LCD When fan speed is AUTO it is changed automatically according to the indoor temperature Note During Auto run operation temp setting will be shown in LCD display unit will select heating cooling or fan operation according to the room temp STERILIZE HEALTH AIRFLOW FRESH CODE AUTO COOL DRY FAN HEAT Select Auto run appears and auto run starts LOW MID HIGH AUTO 2 5 5 1 3 Select temp ...

Страница 12: ... increase or decrease quickly Press ON OFF button Unit stops running and when entry this mode for the next time it will show the previous setting Unit runs at the speed displayed on LCD When fan speed is AUTO it is changed automatically according to the indoor temperature 5 3 2 1 Select cooling operation Shows Cooling operation starts Press FAN button For each press fan speed changes as follows 4 ...

Страница 13: ...n speed changes as follows Press ON OFF button Unit stops running and when entering this mode for the next time it will show the previous setting Unit runs at the speed displayed on LCD In DRY mode when room temp becomes 2 C lower than temp setting unit will run intermittently at LOW speed regardless of FAN setting 3 2 1 4 5 Ultra low air flow Temp setting 2 C Temp setting On reaching 2 C lower th...

Страница 14: ...the next time it will show the previous setting 4 1 2 3 Press FAN button For each press fan speed changes as follows Note In this mode temp can t be selected temp setting will not be shown in LCD display In Fan operation mode AUTO fan speed is not available Operation cycles are as follows LOW MID HIGH Unit runs at the speed displayed on LCD LOW MID HIGH ON OFF TEMP HEALTH FAN MODE SLEEP SWING CLOC...

Страница 15: ... function is invalid Every time the button is pressed temp setting increases 1 C Every time the button is pressed temp setting decreases 1 C If the button is kept pressed setting will increase or decrease quickly Press ON OFF button 5 Unit stops running and when entering this mode for the next time it will show the previous setting In heat mode warm air will blow out after a short period of time d...

Страница 16: ...FAN MODE SLEEP SWING CLOCK TIMER SET LOCK LIGHT RESET Horizontal louvers Side from side Fixed position Press the SWING again to fix the horizontal louvers at your desired position Swing Press SWING the horizontal louvers move from up to down Fixed position Press the SWING again to fix the vertical louvers at your desired position Swing Press SWING the vertical louvers move from side to side 2 STER...

Страница 17: ... after 3 hours running under the above temperature and the conditioner will be closed down after running for 3 hours The temperature is lower than the set temperature so as to avoid uneasiness in sleeping 3 In automatic running The conditioner will run under automatically selected working mode of sleeping 4 In Fan running The Sleep function is invalid About 6 hours The Sleep running starts The Sle...

Страница 18: ...ll change quickly Every time the button is pressed time decreases 10 min If button is kept pressed time will change quickly Time will be shown on LCD It can be adjusted within 24 hours 4 Confirming your setting After setting correct time press SET button to confirm or stops flashing Time displayed Unit starts or stops at x hour x min TIMER ON or TIMER OFF Timer mode indicator on indoor unit lights...

Страница 19: ...rnoon 4 Time confirming for TIMER ON After time setting press TIMER button to confirm stops blinking while starts blinking To cancel TIMER mode Just press TIMER button several times until TIMER mode disappears ON Remote controller ON ON OFF OFF TIMER ON TIMER OFF TIMER ON OFF AM 12 00 PM 12 00 PM 12 00 AM 12 00 BLANK OFF 5 Time setting for TIMER OFF Follow the same procedure in Time setting for TI...

Страница 20: ... does not work the unit will automatically turn off negative ion generation device Health operation After the start of Health operation the negative ion generator will generate large amount of negative ion which can effectively balance the amount of positive negative ion in the air and has the bacteria killing and accelerating the dust deposition of the room to make the room air fresh and healthy ...

Страница 21: ...ioner where the flammable gas is easily leaked Do not spray any paint or insecticide on the air conditioner Insecticide Paint Never pour water on the indoor unit Keep the inlet and outlet of the didoor unit unblocked When the louver is being swung never touch the outlet or put anything into the air grille Operate the unit with the remote controller The instructions with this warning mark must be c...

Страница 22: ...ir flow speed Hi Removal of the restriction of emergency or test operation Press the emergency operation switch once more or manipulate through the remote controller the Pi sound the emergency or test operation is stopped When the remote controller is manipulated it gets the system back to the normal operation mode Disconnect power supply before clean the unit Don t touch it with wet hand Don t wa...

Страница 23: ...e paint tobacco absorbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the suddenly cooled indoor air is blown out Automatically switch into FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it sometimes auto matically switch...

Страница 24: ...after unit autom atically stops Water or vapor generated from the outdoor unit during heating This happens when the frost accumulated on the outdoor unit is removed during defrosting operation Defrosting operation Please check the following things about your air conditioner before making a service call Unit fails to start Is the power supply switch on Power supply switch is not in ON position Is c...

Страница 25: ...r installation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature Too cool or hot is not good for your health Furthermore it will result in excessive consumption of electric power Effectively use timer Using TIMER mode you can make the room temp...

Страница 26: ...conducted to the terminal connection part through properly securing it Improper connection or securing can result in heat generation or fire Take care that wiring does not rise upward and accurately install the lid service panel Its improper installation can also result in heat generation or fire When setting up or moving the location of the air conditioner do not mix air etc or anything other tha...

Страница 27: ...drainage is easy and the outdoor unit can be easily connected Install the indoor unit where its cold air and hot air can be easily sent to all the comers of the room Install the indoor unit where the power socket is near and there is sufficient space around the indoor unit Install the indoor unit where there is no T V set radio set and wireless applian ce underneath and the sunlight lamp is over o...

Страница 28: ... with refrigerant oil and connect pipes Cover the connection part with heat insulation materials closely and make sure fixing with adhesive tape Correct Not Correct cracks on expanded mouth burr incomplete too long Tilting 6 When the mounting plate is first fixed 1 Carry out based on the neighboring pillars or lintels a proper leveling for the plate to be fixed against the wall then temporarily fa...

Страница 29: ...c cable and then pull out the connected to the heat insulation of connecting part specially Hang surely the unit body onto the upper notches of the mounting plate Move the body from side to verify its secure fixing In order to fix the body onto the mounting plate hold up the body aslant from the underside and then put it down perpendicularly Indoor unit C Indoor unit B Indoor unit A To the outdoor...

Страница 30: ... the address is ì1î and the LCD display board shows ì1î Press button ìSLEEPî two times the address is ì2î and the LCD display board shows ì2î Press button ìSLEEPî three times the address is ì3î and the LCD display board shows ì3î Press button ìSLEEPî four times the address is ì4î and the LCD display board shows ì4î H Use the remote controller to turn off the unit At this time the controller should...

Страница 31: ...er it will exit the address checking precedure The person who has completed this installation shall be requested to conduct a test operation for check Is the temperature adjuster working normally Does the location for installation conform to requirements Winding up with Protective Plastic Tape The connection pipes drain pipe and the connection wires shall be wound up with PVC tape Notes The connec...

Страница 32: ...rces in the room Sunlight direct into the room Too crowed in the room Cooled air blown out when heating When the air conditioner does not operate properly after you have checked the above mentioned items or when following phenomenon is observed stop the operation of the air conditioner and contact your sales dealer 1 The fuse or breaker often shuts down 2 Water drops off during cooling or drying o...

Страница 33: ...or at wrong position or short circuit Faulty temperature sensor Tm 4 Sensor disconnected or broken or at wrong position or short circuit Faulty EEPROM on indoor unit PCB 5 Faulty indoor unit PCB Abnormal communication between indoor and outdoor unit 6 Wrong connection or the wires be disconnected or wrong address setting of indoor units or faulty PCB or faulty power supply Indoor unit address repe...

Страница 34: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com ...

Отзывы: