(7)  Installation work for air outlet ducts

Calculate the draft and external static pressure and select the length, shape and blowout.

   Blowout duct

2-spot, 3-spot and 4-spot with     200 type duct are the standard specifications. Determine the
number of spots based on following table.

Note  (1) Shield the central blowout hole for 2-spot.
          (2) Shield the blowout hole around the center for 3-spot.

Limit the difference in length between spots at less than 2:1.
Reduce the length of duct as much as possible.
Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)

Use a band. etc. to connect the main unit and the blowout duct flange.
Conduct the duct installation work before finishing the ceiling.

(8)  Connection of suction, exhaust ducts

(a) Duct connection position

i) Fresh air inlet

Inlet can be selected from the side or rear faces depending on the working conditions.
Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted.
 (Side inlet cannot be used.)

ii) Exhaust (Make sure to use also the suction.)

Use the side exhaust port.

Good example

Bad example

Bad example

Ceiling surface

Heat

insulation

Suction panel
(Silent panel)

Air conditioner main unit

B  Special blowout
     (Option)

A  Blowout duct
     (Optional or marketed item)

C

Hole for check

special inlet (option)
(with air filter)

inlet duct

 (optional or

 marketat item)

Exhaust hole

State seeing from top of unit

Side fresh air inlet

Rear fresh air inlet

Fig.1

Fig.2

Installation Manual For Indoor Unit

Содержание AD182AMEAA

Страница 1: ...ITIONER AD182AMEAA AD242AMEAA AD282AMEAA AD362AMEAA AD422AMEAA AD482AMEAA AD522AMEAA AD182AMERA AD242AMERA AD282AMERA AD362AMERA AD422AMERA AD522AMERA Please read this operation manual before using th...

Страница 2: ...nction 7 8 Care and Maintenance 9 For Preparation of Heating Hot Keep 10 Is The Unit Installed Correctly 11 Installation Manual For Indoor Unit 12 18 Safety Precautions 3 5 Parts and Functions 6 Cauti...

Страница 3: ...an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed w...

Страница 4: ...ident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be ar...

Страница 5: ...is operated at the vicinity of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system sim...

Страница 6: ...hould be H05RN F 4G 0 75mm2 All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that the grouding wire is...

Страница 7: ...Parts and Functions 6 Air outlet Air inlet Duct Air outlet Air inlet Duct For series 182 242 282 For series 362 422 482 522...

Страница 8: ...at the air inlet or outlet Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal At HEATIN...

Страница 9: ...e FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode E...

Страница 10: ...no obstacles blocking the air inlet and air outlet of both indoor and outdoor units Make sure that the air filter is not dirty Cut in the power supply switch 12 hours before starting run Post Season C...

Страница 11: ...ver to ordinary heating operation WARMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mecha...

Страница 12: ...as generates Hot spring area etc The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machin...

Страница 13: ...hen strength is insufficient injury can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes et...

Страница 14: ...of your client user a Places where chilled or heated air circulates freely When the installation height exceeds 3m warmed air stays close to the ceiling In such cases suggest your client users to ins...

Страница 15: ...allation Manual For Indoor Unit For series 362 422 482 522 For series 182 242 282 3 Avoid installation and use at those places listed below a Places exposed to oil splashes or steam e g kitchens and m...

Страница 16: ...drain pipe to unit pay suffcient attention not to apply excess force to the piping on the unit side Also fix the piping at a point as close as possible to the unit For drain pipe use hard PVC general...

Страница 17: ...for the needed height is higher than 500 mm the back flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan Therefore make the h...

Страница 18: ...duct flange Conduct the duct installation work before finishing the ceiling 8 Connection of suction exhaust ducts a Duct connection position i Fresh air inlet Inlet can be selected from the side or re...

Страница 19: ...nit so that the power for the outdoor unit is supplied by terminals Item Model Phase Switch breaker A Circuit breaker Overcurrent protector rated capacity A Power source wire size minimum mm2 30 20 2...

Страница 20: ...sly Sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously CT check abnormal 3 times in 30m High pressure switch acts 3 tim...

Страница 21: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...

Отзывы: