6.   INSTALLATION OF WATER DRAINAGE PIPE

(

As for outdoor piping, please refer to installation Manual of outdoor unit.

)

5.   REFRIGERANT PIPING

Outdoor is precharged with refrigerant.

Be sure to see the Fig.1, when connecting and removing piping from unit.

For the size of the flare nut, please refer to Table 1.

Apply refrigerant oil at both inside and outside of lflare nut. Tighten it band tight 3-4 turns then tighten it.

Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).

Check piping joints for gas leakage. Insulate piping as shown in Fig. below.

Cover joint of gas piping and insulator      with seal.

Table 1

(1) Install water drainage pipe

Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethene; size: 25mm; O.D:32mm)

Drain pipe should be short, with  a downward slope at least 1/100 to prevent air bag from happening.

If downward slope can't be made, take other measures to lift it up.

Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

Slope over 1/100

1-1.5m

(Note)

If several water hoses join together, do as per following proceedures.

Specifications of the water hoses shall meet the requirements for the unit running.

The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.

Medium size seal pad  11  (accessory)

R0.4 ~ 0.8

A

90

0.5

45

2

Connect water hoses with a T joint.

5

6

20

Use the self-provided stiff pipe and clamp     with unit. Insert water pipe into water plug until it reaches the

white tape. Tighten the clip until head of the screw is less than 4mm from hose.

Wind the drain hose to the clip using seal pad   9  .

Insulate drain hose in the room.

1

Apply refrigerant oil

Torque spanner

spanner

Piping joing

Flare nut

Clamp  3

Gas pipe

Liquid pipe

Insulator (accessory)

(For liquid pipe)

Insulator (accessory)

(For gas pipe)

(Cover the piping joint

with seal pad.)

Pipe

size

Tighten

torque

A(mm)

Flare shape

9.52 3270~3990N.cm

(333~407kgf.cm)

6180~7540N.cm

(630~770kgf.cm)

15.88

19.05 9720~11860N

.cm

(990~1210kgf.cm)

12.0~12.4

18.6~19.0

22.9~23.3

7

8

7

<

Cautions for the drain water lifting pipe

>

75 below

Self-provided stiff pipe

(accessory)

500 below

Clamp

Tape (White)

Self-provided stiff pipe

300mm below

1~1.5m

280 below

500 below

220

Drain hose

(accessory)

drain water lifting pipe

Suspending bracket

Clamp

(accessory)

Installation height shall be less than 280mm.

There should be a right angle with unit, 300mm from unit.

Over 100

4mm below

(accessory)

(accessory)

Large size seal pad

Clamp

10

6.35 1420~1720N.cm

(144~176kgf.cm)

8.3~8.7

Installation Procedure

Содержание AB094FAAHA

Страница 1: ...al before using the air conditioner No 0010576722A Indoor Unit Operation Installation Manual CASSETTE TYPE AIR CONDITIONER Please keep this manual carefully and safely AB094FAAHA AB124FAAHA AB184FCAHA AB244FCAHA AB424FCAHA AB484FCAHA ...

Страница 2: ...s Cautions Part name of the unit Maintenance Trouble Shooting When Trouble Happens Customer Need to know Installation Procedure 1 5 6 7 9 10 11 12 13 14 15 25 Electrical Wiring Technical Specification 26 28 29 ...

Страница 3: ...hylene and the polyethylene foam pads contain no fluorochloric hydrocarbon Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house Safety Instructions and Warnings Before starting the air conditioner read the information given in the User s Guide carefully The User s Guide contains very important obse...

Страница 4: ...ating the air conditioner s tubes with sharp or pointed items crushing or twisting any tubes or scraping the coatings off the surfaces If the refrigerant spurts out and gets into eyes it may result in serious eye injuries Do not obstruct or cover the ventilation grille of the air conditioner Do not put fingers or any other things into the inlet outlet and swing louver Do not allow children to play...

Страница 5: ...ase to continue using the conditioner will damage the conditioner and may cause electrical shock or fire hazard When need maintenance and repairment call dealer to handle it Incorrect mainten ance and repairment may cause water leak electrical shock and fire hazard switch off Please let the dealer be responsible for installing the conditioner Incorrect installation may cause water leak elec trical...

Страница 6: ...rmitted to placed on or stand on outdoor unit The falling of goods and people may cause acci dents Pets and plants should not be blowed directly in the air flow Otherwise will suffer damage Don t operate the air con ditioner with damp hands Otherwise will be shocked Only use correctly typed fuse May not use wire or any other materials replacing fuse other wise may cause faults or fire accidents Do...

Страница 7: ...th high salt content in the air c Near to hot spring with high content of sulfide gases d Area with frequent fluctuation of voltage e g factory etc e In vehicles or ships f Kitchen with heavy oil vapour or humidity g Near to the machine emitting electric magnetic waves h Places with acid alkali vapuor TV radio acoustic appliances etc are at least 1 m far away to the indoor unit outdoor unit power ...

Страница 8: ...Refrigerant pipe Cable line Earthing line Air filter Outlet Suction grill located in the suction grill In cooling operation to discharge the water from inside the room Discharge unit built in located in the outlet Anti bacteria filter Air intake Air Outlet ...

Страница 9: ...s catched with two pothooks Drag the knob of the grill back lift the filter and take down Air filter Maintenance Clean air filter NOTE 1 Open inlet grill Press the elliptical PUSH knob the inlet grill will automatically drop the inlet grill is catched with two pothooks When having to clean don t dismantle air filter otherwise may cause faults In the environment where there is too much dust air fil...

Страница 10: ...ilutant polishing powder or liquid inseticide Dismantle and install swing plate 1 Fix the swing plate at the bottom 2 Dismantle the swing plate CAUTION Use water to clean the plate and don t heavily scrub otherwise the fine hair may fall off Unscrew the screw at both ends of the swing plate Dismantle and install swing plate 3 Install swing plate Lightly rotate swing plate to insert the ridge at bo...

Страница 11: ...an the air filter indoor unit and outdoor unit and cover the unit with dustcoat Pre season Care See that there is no obstacles blocking the air inlet and air outlet of both indoor and outdoor unit to avoid reduce the working efficiency Be sure to install the air filter ensure that the air filter is not dirty Otherwise may result in machine damages or cause malfunciton due to dust inside the unit T...

Страница 12: ...aint tobacco absorbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the suddenly cooled indoor air is blown out Automatically switch into FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it sometimes auto matically switched ...

Страница 13: ...ning for a while after unit autom atically stops Water or vapor generated from the outdoor unit during heating This happens when the frost accumulated on the outdoor unit is removed during defrosting operation Defrosting operation Please check the following things about your air conditioner before making a service call Unit fails to start Is the power supply switch on Power supply switch is not in...

Страница 14: ...rces in the room Sunlight direct into the room Too crowed in the room Cooled air blown out when heating When the air conditioner does not operate properly after you have checked the above mentioned items or when following phenomenon is observed stop the operation of the air conditioner and contact your sales dealer 1 The fuse or breaker often shuts down 2 Water drops off during cooling or drying o...

Страница 15: ...er and Operation indicator malfunction code When the unit running Timer indicator flash stand for indoor unit malfunction When the operation indicator flashing stand for outdoor unit malfunction Operation indicator flashing times can t determinant outdoor unit malfunction You must check the outdoor unit control board LED1 flashing times or outdoor unit malfunction display code to sure outdoor unit...

Страница 16: ...e After installation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature Too cool or hot is not good for your health Furthermore it will result in excessive consumption of electric power Optimal temper ature Effectively use timer Using TIMER mode...

Страница 17: ...following sheet can be used as required The following parts mentioned in this manual are the installation accessories we prepared Symbol Parts Name Adhesive tape Pipe clamp Connecting hose Drainage hose Non hydroscopic heat insulating material Gypsum powder Following in the list are the accessories supplied with the unit which can be used as required 1 2 3 4 5 6 7 1 2 4 No Accessory parts Qty Remo...

Страница 18: ...ofessional people don t install unit by yourself Incorrect installation will cause water leakage electric shock or fire Install unit as per the Manual Incorrect installation will cause water leakage electric shock or fire accident Be sure to use specified accessaries and parts Otherwise water leakage electric shock fire accident or unit falling down may happen Unit should be placed on a place stro...

Страница 19: ... on ceiling Enough space for maintenance Indoor and outdoor unit piping length is within limit Refer to Installation Manual for outdoor unit Indoor and outdoor unit power cable inter unit cable are at least 1 m away fromT V radio This is helpful to avoid picture disturbance and noise Even if 1 m is kept noise can still appear if radio wave is strong Don t discard any accessories until completed 1 ...

Страница 20: ...ings refrigerant water drainage wirings inter unit cable to indoor unit before installation Cut a hole in ceiling may be a frame should be used to ensure a smooth surface and to prevent vibration Contact your real estate dealer AB184FCAHAAB244FCAHA 950 Ornament panel 890 Ceiling opening 840 Indoor unit 680 Distance between suspending bolts Distance between suspending bolts 950 Ornament panel 890 C...

Страница 21: ...unit and on the paper pattern Mount paper pattern onto unit using 3 screws Fix the corner of the drain pan at piping outlet 1 Install unit temporarily Put suspending bracket on the suspending bolt Be sure to use nut and washer at both ends of the bracket In the case of ceiling already exists Screws at the piping outlet is fixed at the corner of drain pan Center of ceiling hole Paper pattern 5 Pape...

Страница 22: ...or the unit running The slope of water drain hose 1 shall be within 75mm don t apply too much force on it Medium size seal pad 11 accessory R0 4 0 8 A 90 0 5 4 5 2 Connect water hoses with a T joint 5 6 20 Use the self provided stiff pipe and clamp with unit Insert water pipe into water plug until it reaches the white tape Tighten the clip until head of the screw is less than 4mm from hose Wind th...

Страница 23: ... wire of the deflector motor into the sealing c Screw all 4 hex head screws under the rings about 15mm to lift the board d Turn and adjust the decorated board in the direction of arrow as shown in Fig 4 until it covers the hole of the ceiling e Fasten the screw to keep the thickness of the sealing between the decorated board and the unit body within 5 8mm as shown in Fig 2 f Mount the wiring of th...

Страница 24: ...te tightening of screws might cause the faults as shown in Fig 3 Tighten the screws properly If there is still a gap between the decorated board and the ceiling after tightening the screws please readjust the height of the body of the indoor unit Fig 4 If the indoor unit keeps the horizontal level and the drainpipe can t be influenced adjust the height of the body of the indoor unit from the holes...

Страница 25: ... 1 100 can t be in the S shape or abnormal sound can be caused The lateral length of the drainpipe should be kept with 20m Under the condition of long pipes supports can be provided every 1 52m as to avoid unevenness The central piping should be connected according the following drawing Take care not to apply external force on the connection of the drainpipes 1 5m 2m VP30 heat insulating material ...

Страница 26: ...run to make sure that there is leakage at the connection The confirmation of drainage should be also performed during the installation in the winter season Fill water from the outlet or the specified position and confirm the drainage Fill 600cc water with a hose from the outlet or the specified location on the machine Add the water slowly Don t add water to the motor of the drainage pump After mou...

Страница 27: ...e from the stop valve of outdoor units with vacuum pump Refrigerant sealed in indoor machine is not allowed to use for vacuumization Open All Valves Open all the valves of outdoor units NB oil balancing stop valve must be shut up completely when connected one main unit Checkup for Air Leakage Check if there is any leakage at the connecting part and bonnet with hydrophone or soapsuds Connecting 1 C...

Страница 28: ...r electric leakage should be provided or electric shock may occur The wiring of the mains line is of Y type The power plug L should be connected to the live wire and plug N connected to null wire while should be connected to the ground wire For the type with auxiliary electrically heating function the live wire and the null wire should not be misconnected or the surface of electrical heating body ...

Страница 29: ...r failure suddenly occurs while the air conditioner is working it will resume the previous working state when the power is supplied again The setting method of auto restart function of wired remote control model or wired control remote control model press the sleep button of the wired control or remote control 10 times within 5 seconds and after the buzzer rings 4 times the air conditioner will en...

Страница 30: ...s same with cooling compensation setting number In heating mode setting temp 16 degree high fan speed press swing 7 times in 5 seconds the running lamp will flash the flashing times is same with heating compensation setting number Concerning MRV Auto Restart function for H MRV models Haier Auto Restart function when the unit power drops down suddenly the unit microprocessor will store the previous...

Страница 31: ...A184FCAHA 3600W 3900W 20kg 1PH 220V 60Hz 450m3 h AB124FAAHA 2800W 3200W 400m3 h 20kg 1PH 220V 60Hz AB094FAAHA Noise Indoor Units Net Weight Indoor Units Air Volume Indoor Units Net Dimensions mm Panel Dimensions mm Cooling Capacity Model Power Supply 3600W 3900W 35kg 1PH 220V 60Hz 1920m3 h AB484FCAHA 2800W 3200W 1580m3 h 35kg 1PH 220V 60Hz AB424FCAHA Noise Indoor Units Net Weight Indoor Units Air ...

Отзывы: