background image

Page 15 of 21

507919-01

Issue 1946

Delay Mode

The  defrost  system  has  a  field-selectable  function  to 

reduce occasional sounds that may occur while the unit is 

cycling in and out of the defrost mode. When a jumper is 

installed on the DELAY pins, the compressor will be cycled 

off for 30 seconds going in and out of the defrost mode. 

Units are shipped with jumper installed on DELAY pins.

NOTE: 

The 30 second compressor delay feature (known 

as the quiet shift) 

must

 be deactivated during any unit 

performance testing. The feature is deactivated by 

removing the jumper located on the compressor delay pins 

on the control board mounted inside the unit control box. 

This feature is optional for the homeowner, but may impact 

testing performance.

Defrost Operation

The defrost control system has three basic operational 

modes: normal, calibration, and defrost.

•  Normal Mode—

The demand defrost system monitors 

the O line, to determine the system operating mode 

(heat/cool), outdoor ambient temperature, coil 

temperature (outdoor coil) and compressor run time to 

determine when a defrost cycle is required.

•  Calibration Mode—

The board is considered 

uncalibrated when power is applied to the board, 

after cool mode operation, or if the coil temperature 

exceeds the termination temperature when it is in heat 

mode.
Calibration of the board occurs after a defrost cycle 

to ensure that there is no ice on the coil. During 

calibration, the temperature of both the coil and 

the ambient sensor are measured to establish the 

temperature  differential  which  is  required  to  allow  a 

defrost cycle.

•  Defrost Mode—

The following paragraphs provide a 

detailed description of the defrost system operation.

Defrost Cycles

The control board initiates a defrost cycle based on either 

frost detection or time.

•  Frost Detection

—If the compressor runs longer than 

30  minutes  and  the  actual  difference  between  the 

clear coil and frosted coil temperatures exceeds the 

maximum difference allowed by the control, a defrost 

cycle will be initiated.

IMPORTANT

 - 

The control board will allow a greater 

accumulation of frost and will initiate fewer defrost 

cycles than a time/ temperature defrost system.

•  Time

—If 6 hours of heating mode compressor run 

time has elapsed since the last defrost cycle while the 

coil temperature remains below 35°F (2°C), the control 

board will initiate a defrost cycle.

Actuation

When the reversing valve is de-energized, the Y1 circuit is 

energized, and the coil temperature is below 35°F (2°C), 

the board logs the compressor run time. If the board is not 

calibrated, a defrost cycle will be initiated after 30 minutes 

of heating mode compressor run time. The control will 

attempt to self-calibrate after this (and all other) defrost 

cycle(s).

Calibration success depends on stable system 

temperatures during the 20-minute calibration period. If 

the board fails to calibrate, another defrost cycle will be 

initiated after 45 minutes of heating mode compressor 

run time. Once the control board is calibrated, it initiates 

a  demand  defrost  cycle  when  the  difference  between 

the clear coil and frosted coil temperatures exceeds the 

maximum  difference  allowed  by  the  control  OR  after  6 

hours of heating mode compressor run time has been 

logged since the last defrost cycle.

NOTE: 

If ambient or coil fault is detected, the board will not 

execute the “TEST” mode.

Termination

The defrost cycle ends when the coil temperature exceeds 

the termination temperature or after 14 minutes of defrost 

operation. If the defrost is terminated by the 14-minute 

timer, another defrost cycle will be initiated after 30 minutes 

of run time.

Control Board Diagnostics and Test Mode

Control Board Diagnostics

See control board diagnostic LED table (Table 6) to 

determine control board operational conditions and to 

diagnose cause and solution to problems. 

Test Mode

When Y1 is energized and 24V power is being applied 

to the board, a test cycle can be initiated by placing the 

termination temperature jumper across the “Test” pins for 

2 to 5 seconds. If the jumper remains across the “Test” pins 

longer than 5 seconds, the control will ignore the test pins 

and revert to normal operation. The jumper will initiate one 

cycle per test.

Enter the “TEST” mode by placing a shunt (jumper) across 

the “TEST” pins on the board after power-up. (The “TEST” 

pins are ignored and the test function is locked out if the 

shunt is applied on the “TEST” pins before power-up). Board 

timings are reduced, the low pressure switch is ignored 

and the board will clear any active lockout condition.

Each test pin shorting will result in one test event.

 

For each “TEST” the shunt (jumper) must be removed for 

at  least  1  second  and  reapplied.  Refer  to  flow  chart  for 

“TEST” operation.

NOTE: 

The Y1 input must be active (ON) and the “O” room 

thermostat terminal into board must be inactive.

Содержание 4HP16

Страница 1: ...ed thoroughly after cleaning In coastal areas the coil should be cleaned with potable water several times per year to avoid corrosive buildup salt NOTICE This manual must be left with the homeowner for future reference This is a safety alert symbol and should never be ignored When you see this symbol on labels or in manuals be alert to the potential for personal injury or death Installation and se...

Страница 2: ...nstalled on a solid foundation This foundation should extend a minimum of 2 inches beyond the sides of the outdoor section To reduce the possibility of noise transmission the foundation slab General Read this entire instruction manual as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Fa...

Страница 3: ...48 Between units 24 Against wall 6 Maximum soffit overhang is 36 NOTE At least one side should be unobstructed by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and top of unit On a solid level foundation or pad unit must be level to within 1 4 in ft per com...

Страница 4: ... 8 042 3 8 3 8 7 8 7 8 048 3 8 3 8 7 8 7 8 060 3 8 3 8 7 8 1 1 8 Field supplied 7 8 x 1 1 8 connector required on both ends of vapor tubing Table 3 Recommended Liquid Vapor Tube Diameters in Be extra careful with sharp bends Tubing can kink very easily and if this occurs the entire tube length will have to be replaced Extra care at this time will eliminate future service problems It is recommended...

Страница 5: ... UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid line valve C Refrigerant gauge set center port to inlet on the recovery machine with an empty recovery tank connected to the gauge set D Connect recovery tank to recovery machine per machine instruction...

Страница 6: ...oil Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refriger...

Страница 7: ...round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVICE PORT CAP CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION 3 VAPOR LINE SERVICE VALVE COPPER TUBE STUB REFRIGER...

Страница 8: ...VES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set int...

Страница 9: ... of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After the line set has been connected to the indoor and outdoor units check the line set connections and indoor unit for leaks Use the following procedure to test...

Страница 10: ...uid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Reinstall service valve cores by removing manifold hose from service valve Quickly install cores with core tool while maintaining a positive system pressure Replace stem caps and finger tighten them t...

Страница 11: ... breaker may result in property damage Size wiring and circuit breaker s per Product Specifications and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostaticdischargecanaffectelectroniccomponents Take care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic discharge...

Страница 12: ...example of control wiring connections when using a standard thermostat Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is located in the bottom of the control panel Connect conduit to the control panel using a proper conduit fitting ROUTING HIGH VOLTAGE GROUND AND CONTROL WIRING WIRE RUN LENGTH AWG INSULATIO...

Страница 13: ...ure auto reset trip at 25 psig reset at 40 5 Add refrigerant if subcooling is lower than table Recover refrigerant if subcooling is high 6 If ambient temp is lower than 60 F check charge in heating mode or weigh refrigerant according to name plate data Heating Mode Check charge in heating mode if ambient temp is below 60 F Indoor temp must be between 65 and 75 F Follow steps 1 to 6 above and compa...

Страница 14: ...ult code Heating and cooling operation will be allowed in this fault condition NOTE The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing Coil sensor location is important for proper defrost operation Ambient Sensor The ambient sensor considers outdoor temperatures below 35 F 37 C or above 120 F 48 C as a fault If the ambient sensor is detected as b...

Страница 15: ... F 2 C the control board will initiate a defrost cycle Actuation When the reversing valve is de energized the Y1 circuit is energized and the coil temperature is below 35 F 2 C the board logs the compressor run time If the board is not calibrated a defrost cycle will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all othe...

Страница 16: ...not perform demand or time temperature defrost operation System will still heat or cool ON ON Fault Demand Defrost Control Failure Indicates that demand defrost control has internal component failure Cycle 24VAC power to control board If code does not clear replace control board OFF SLOW Flash Fault Low Pressure Fault Restricted air flow over indoor or outdoor coil Improper refrigerant charge in s...

Страница 17: ...r is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second off cycle is NOT functional when TEST pins on P1 are jumpered P6 TST PS DF C R O Y1 Y2 Factory Test Connectors No field use DS1 RED LED Diagnostic LED Control board LEDs may be OFF ON or FLASHING to indicate ...

Страница 18: ...bent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY WARNING Painted Surfaces For maximum protection of the unit s finish a good grade of automobile wax should be applied every year In geographical areas where water has a high concentration o...

Страница 19: ...the defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restoring power to your heat pump system Set the room thermostat selector to the Emergency Heat setting to obtain temporary heat for a minimum of 6 hours This will allow system refrigerant pressures and tem...

Страница 20: ...507919 01 Page 20 of 21 Issue 1946 Figure 7 Wiring Diagram 018 030 Models Y2 IS NOT USED WITH SINGLE STAGE UNITS 5 5 ...

Страница 21: ...Page 21 of 21 507919 01 Issue 1946 Figure 8 Wiring Diagram 036 060 Models 5 Y2 IS NOT USED WITH SINGLE STAGE UNITS 5 ...

Отзывы: