When the outdoor environment temperature is higher than 50
,AC current protection value
decreases by 20AD
Antifreezing protection of the indoor heat exchanger
When refrigerating/heating, prevent freezing.
Tpg_indoor
is the minimum value of the effective indoor unit (start it and it is in accord with the
running state).
When Tpg_indoor
ice_temp_1
, the frequency of the compressor decreases at the speed of
1HZ/1second.
When Tpg_indoor
ice_temp_2
, the frequency of the compressor decreases at the speed of
1HZ/10seconds.
When Tpg_indoor begins to rise again, and ice_temp_2
=Tpg_indoor
= ice_temp_3
, the
frequency of thecompressor doesn’t change.
When ice_temp_3 Tpg_indoor ice3
, the frequency of the compressor increases at
the speed of 1HZ/10seconds.
For example, Tpg_indoor<= 0
last for 2 minutes, and then the outdoor unit will stop, and report
underload malfunction, but don’t send malfunction report to the indoor.
The compressor stops for more than 3 minutes, Tpg_indoor> ice2
, the compressor
recovers.
The frequency limi tation of modification rate
In the field which is controlled by high frequency, if the modification rate is not high enough,
the control-driven chip will enter into weak magnetic control, this will help to relieve the problem
of modification rate. If during the course of weak magnetic control, the modification rate is still not
high enough, enter into the control of decreasing frequency until the alarm of modification rate is
relieved.
Temperature protection of the ou tdoor refrigerating coil
When the defrosting temperature and the sensor’s temperature are higher than 65
, the
frequency of the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to
the lowest frequency. When the temperatures are lower than 65
and higher than 60
, keep
the frequency of the compressor. When the temperatures are lower than 60
, relieve the
defrosting temperature protection.
Malfunction displ ay and malfunction handling
a)
For the complete appliance’s malfunctions
Annex 2
If there’s malfunction with the outdoor unit, the light of the outdoor unit will flash and its frequency
is 1HZ, the number of times is according to the table, when a round of flashing is finished, the
11
//ice5
9
ce3
Increasing slowly
8
//ice2
Keeping the frequency
ice_temp_3
6
6
ice_temp_2
5
Decreasing slowly
ice_temp_1
3
Decreasing rapidly
ice_temp_1
0
Stop
7.1.5.1
7.1.5.2
7.1.5.3
7.1.5.4
Functions and control
Domestic air conditioner
21
Содержание 2U50S2SF1FA
Страница 11: ...Pinping diagrams Domestic air conditioner 4 Pinping diagrams 9 ...
Страница 12: ...Domestic air conditioner 5 Operation range 10 Introduction ...
Страница 16: ...wiring diagram 14 Domestic air conditioner PCB 2 CN4 CN3 CN10 CN6 CN5 CN8 CN11 CN9 CN7 CN1 CN2 ...
Страница 80: ...Domestic air conditioner Removal of procedure 8 s t n i o P e r u d e c o r P p e t S 3 screws and then lift ...
Страница 82: ...Domestic air conditioner Removal of procedure 10 s t n i o P e r u d e c o r P p e t S 1 Remove compressor ...
Страница 83: ...Domestic air conditioner Removal of procedure 11 s t n i o P e r u d e c o r P p e t S 2 ...
Страница 84: ...Domestic air conditioner Removal of procedure 12 s t n i o P e r u d e c o r P p e t S 3 ...
Страница 85: ...Domestic air conditioner Removal of procedure 13 s t n i o P e r u d e c o r P p e t S 4 Remove the ...