background image

13

If the temperature is higher than 30  and the humidity is

higher than RH 80 , then thickness of the sealing materials

should be at least 20mm in ouder to avoid condensation

on the surface of the sealing.

Be sure to insulate the liquid and gas-side field piping.

Any exposed piping may cause condensation.

(The highest temperature that the gas-side piping can
reach is around 120 , so be sure to use insulating

material which is very resistant.)

No not touch piping and internal parts.

To avoid the the risk of oil held inside the riser piping flowing

back into the compressor when stopped and causing liquid

compression phenomenon, or cases of deterioration of oil

return, it will be necessary to provide a trap at each difference

in height of 10m in the riser gas piping.

A trap is not necessary when the outdoor unit is installed

at higher position than the indoor unit.

NOTICE

DANGER

7.7.    Cautions for necessity of a trap

When all piping work is complete and the outdoor unit is

connected to the indoor unit, it is necessary to :

check for any leakages in the refrigerant piping

to perform vacuum drying to remove all moisture in the

refrigerant piping.

If there is a possibility of moisture being present in the

refrigerant piping (for example, rainwater may have entered

the piping), first carry out the vacuum drying procedure

below until all moisture has been removed.

All piping inside the unit has been factory tested for leaks.

Use a 2-stage vacuum pump with a non-return valve

which can evacuate to a gauge pressure of-100.7kPa(5

Torr absolute,-755mm Hg).

Connect the vacuum pump to both the service port of

the gas stop valve and the liquid stop valve to increase

efficiency.

8.   Leak test and vacuum

      drying

8.1.    General guidelines

Do not purge the air with refrigerants. Use a vacuum

pump to evacuate the installation. No additional

refrigerant is provided for air purging.

Make sure that the gas stop valve and liquid stop

valve are firmly closed before performing the leak

test or vacuum drying.

NOTICE

The leak test must satisfy specification EN378-2.

1    Vacuum leak test

1.1  Evacuate the system from the liquid and gas piping

        to -100.7 kPa(5 Torr).

1.2  Once reached, turn off the vacuum pump and check

       that the pressure does not rise for at least 1 minute.

1.3  Should the pressure rise, the system may either

       contain moisture (refer to the paragraph " Vacuum

       drying ") or have leaks.

2    Pressure leak test

2.1  Break the vacuum by pressurizing with nitrogen gas

       to a minimum gauge pressure of 0.2 MPa (2 bar).

       Never set the gauge pressure higher than the

        maximum operation pressure of the unit, i.e. 4.0MPa

       (40bar).

2.2  Test for leaks by applying a bubble test solution to

       all piping connections.

8.2.    Leak test

Make sure to use a recommended bubble test solution

from your wholesaler.

Do not use soap water, which may cause cracking of

falre nuts (soap water may contain salt, which absorbs

 moisture that will freeze when the piping gets cold).

and/or lead to corrosion of flared joints (soap water may

contain ammonia which causes a corrosive effect between

the brass flare nut and the copper flare).

NOTICE

To remove all mositure from the system, proceed as follows:

1     Evacuate the system for at least 2 hours to a target

       vacuum of -100.7 kPa(=-1.007 bar).

2     Check that, with the vacuum pump turned off, the target

       vacuum is maintained for at least 1 hour.

3     Should you fail to reach the target vacuum within 2 hours

       or maintain the vacuum for 1 hour, the system may contain

       too much moisture.

4     In that case, break the vacuum by pressurizing with

       nigrogen gas to a gauge pressure of 0.05 MPa (0.5bar)

       and repeat steps 1 to 3 unit all moisture has been removed.

5     The stop valves can now be opened, and/or additional

        refrigerant can be charged .

8.3.    Vacuum drying

Содержание 1UH071N1ERG

Страница 1: ...14 15 15 17 Contents English Definitions Safety considerations Before installation Selecting installation site Precautions on installation Refrigerant pipe size and allowable pipe length Refrigerant piping Leak test andvacuum drying Charging refrigerant Pump down operation Electrical wiring work Test operation This product must only be installed or serviced by qualified personnel Please read this ...

Страница 2: ... product see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging IMPORTANT INFORMATION REGA RDING THE REFRIGERANT USED Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C A B C D kg kg kg R410A WARNING If the supply cord is damaged it must be replac...

Страница 3: ...hat those voltages are 50V DC or less 1 Definitions 2 Safety considerations 1 1 Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of occurrence DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could r...

Страница 4: ...ire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not act on the terminal connections or wires Incomplete connection or fixing may cause a fire When wiring between the indoor and outdoor units and wiring the power supply form the wires so that the fronstside panel can be securely fastened If the frontside panel is not in place overheating of the...

Страница 5: ... mixed into the system Tight Read 9 Precautions on refrigerant piping on page 10 carefully and follow these procedures correctly Since R410Ais a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the refrigerant is in state of gas its composition changes and the system will not work properly The connected indoor units must be indoor units designed exclusiv...

Страница 6: ...t causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this un...

Страница 7: ...g pitch1 B leg pitch2 C Front grill air outlet side D Drain hole E Bottom frame F Knock out hole for piping line C D E F 349 174 A 600 174 80 27 37 99 276 367 70 90 450 B 405 410 2 1 5 4 2 6 Fix the outdoor unit to the foundation bolts using nuts with resin washers 1 as shown in the figure Height of barriers is below that of outdoor unit Back and side Above 150 Above 300 Above 200 Front and back A...

Страница 8: ...ndard Make sure the drain works properly In regions where buildups of snow can be expected the accumulation and freezing of snow in the space between the heat exchanger and external plate may lower operating efficiency After punching the knock out hole the application of repair type paint on the surface around the edge sections is recommended to prevent rust 5 3 Drain pipe disposal Piping an other...

Страница 9: ... ones for HFC type refrigerant may be used Vacuum Pump Vacuum drying May be used if a reverse flow check adaptor is attached Refrigerant Recovery Equipment Recovery of refrigerant May be used if designed for use with R410A Flare Tool Flare machining of piping Chages have been made in the flare machining dimension Refer to the next page Tools Materials Use Notes Vacuum Pump with a Check Valve Vacuu...

Страница 10: ...tightness If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusion is useful Size mm Radial Thickness mm Size inch Type Type O pipes Type 1 2H or Hpipes 6 2 Piping Materials Types of Copper Pipes Reference Using this table as a reference choose pipes that me...

Страница 11: ...sting pipes must be cleaned or replaced after removing the air conditioning units to be replaced 3 Prepare the flare connections for higher pressure See paragraph 6 2 The stem cap is sealed where indicated by the arrow Take care not to damage it After handling the stop valve make sure tighten the stem cap securely For the tightening torque refer to the table below Check for refrigerant leaks after...

Страница 12: ...sing a 6mm drill 4x After knocking out the knock out hole it is recommended to apply repair paint to the edge and the surrounding end surfaces to prevent rusting When passing electrical wiring through the knock out holes remove any burrs from the know out holes and wrap the wiring with protective tape to prevent damage If there is any possibility that small animals enter the system through the kno...

Страница 13: ...rants Use a vacuum pump to evacuate the installation No additional refrigerant is provided for air purging Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying NOTICE The leak test must satisfy specification EN378 2 1 Vacuum leak test 1 1 Evacuate the system from the liquid and gas piping to 100 7 kPa 5 Torr 1 2 Once reached tur...

Страница 14: ...ts indicated on the figures below opened The location is depending on mode type Fill using a cylinder with a siphon attached Charge the liquid refrigerant with the cylinder in up side down position Fill using a cylinder with a siphon attached Charge the liquid refrigerant with the cylinder in upright position This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not v...

Страница 15: ... 2 Push the BS4 pumping down operation button on the PC board of the outdoor unit 8 seconds Never leave the outdoor unit unattended with oopened front panel when power supply is on In case the stop valve on the liquid side is not securely closed during compressor operation during compressor operation pumping down operation cannot be executed Compressor and outdoor fan will start operation automati...

Страница 16: ...e side Secure the electrical wiring with cable ties as shown in the figure in 11 2 for single split or 12 3 for maxi split Make sure no external pressure is applied to the terminal connectors When installing the earth leakage circuit breaker make sure that it is compatible with the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage circuit break...

Страница 17: ... units connected in series correct Are any of the wiring attachment screws loose Is the insulation resistance at leaset 1 Use a 500V mege tester when measuring insulation Do not use a mega tester for low voltage circuits Extra refrigerant Is the size of the piping appropriate Is the insulation material for the piping attached securely Are both the liquid and gas pipes insulated Are the stop valves...

Страница 18: ...l block Outdoor unit S R N T N L 1 2 3 1 2 3 1 2 3 1 2 3 Note 1 The master is the indoor unit which connect to a wired controller others are slaves please purchase wired controller separately for MAXI system 2 For one MAXI split system there is only one master 3 For the MAXI system with 2 to 3 indoor units the wiring method is the same with the diagram on the left except for the indor units quanti...

Страница 19: ...20 45 P 30 L 20 45 P 30 L 20 45 P 30 L 20 45 P 30 L 20 45 P 30 L P 20 30 L P 20 30 Charge g P m P 0 P L1 L2 P L1 L2 L3 P L1 L2 L3 L4 __ L P 20 45 L P 20 45 __ L P 20 30 L P 20 30 P 20 30 L L P 20 45 Single Split Twin Triple Quadruple 1UH105 1UH125 1UH140 Example 2 1UH125 Remark a L is the main pipe length of liquid pipe P is the sum length of branch liquid pipes b The piping length L P means the s...

Страница 20: ...20 60 80 80 60 80 80 80 80 When installing MAXI SPLIT Series 1UH105N1ERG 1UH125P1ERG 1UH125P1ERK 1UH140P1ERG 1UH140P1ERK Please refer to the table below concerning the pipe lengths heights and sizes ...

Страница 21: ...draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage the furnishings Do not spray water on the air conditioners or immerse the air conditioners in water Water on the unit presents a risk of electric shock Periodically check the platform on which is placed for...

Страница 22: ...22 12 6 Failure diagnosis ...

Страница 23: ......

Страница 24: ...Address Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C Contacts TEL 86 532 88936943 FAX 86 532 8893 6999 Website www haier com ...

Отзывы: