Service Diagnosis
Domestic air conditioner
33
1
0
.Service Diagnosis
1
0
.1 Caution for Diagnosis
The operation lamp flashes when any of the following errors is detected.
1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions,
disabling equipment operation.
2.When a signal transmission error occurs between the indoor and outdoor units.In either case, conduct the
diagnostic procedure described in the following pages.
10.1.1 Parameter of primary electronic appliance
NO
Name
Parame
t
e
r
Picture
1
Fan motor
R
ated voltage: DC310V
Rated current:0.05 A
Rated frequency:
90W
-
Rated output:
Compressor
Refrigerant : R410A
Rated voltage: DC310V
Model: TNB220FFEMC
Rate outut: 1300W
2