Functions and control
Domestic air conditioner
During the starting process of the compressor, if the AC current is greater than 7A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
7.1.4.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 12A for 3 seconds,
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20
minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only
after the the power is off.
During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 7A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there’s compensation for AC current protection.
(1) When the outdoor environment temperature is higher than 40
ć
, AC current protection value
decreases by 1A.
(2) When the outdoor environment temperature is higher than 50
ć
, AC current protection value
decreases by 2.5A.
7.1.4.5 Anti-freezing protection of the indoor heat exchanger
When cooling/heating, prevent freezing.
Tpg_indoor is the minimum value of the effective indoor unit (start it and it is in accord with the running
state).
11
ć
//ice5
ice3 9
ć
Increasing slowly
8
ć
//ice2
Keeping the frequency
ice_temp_3 7
ć
7
ć
ice_temp_2 5
ć
Decreasing slowly
ice_temp_1 3
ć
Decreasing rapidly ice_temp_1
0
ć
Stop
When Tpg_indoor
LJ
ice_temp_1
ć
, the frequency of the compressor decreases at the speed of
1HZ/1second.
When Tpg_indoor
LJ
ice_temp_2
ć
, the frequency of the compressor decreases at the speed of
1HZ/10seconds.
When Tpg_indoor begins to rise again, and ice_temp_2
İ
Tpg_indoor
İ
ice_temp_3
ć
, the frequency
of the compressor doesn’t change.
20
Содержание 1U12BS3ERA
Страница 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Страница 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Страница 16: ... CN1 CN2 CN3 CN4 CN5 CN6 6 CN7 PCB 2 Dom Wirin mestic air co ng diagrams onditioner CN1 CN1 s 11 10 14 ...
Страница 32: ... Dimensinal drawings Domestic air conditioner 8 Dimensional drawings 9 Center of gravity 30 ...