The following settings are recommended:
Forced air systems
4
Radiant systems
6
A lower setting will decrease the tendency to turn off the heating
system before the desired heat setting is reached. If the heating
system response time is slower, as are most radiant heating systems,
a higher number will help maintain an even space temperature.
The default setting is 4.
11 Cooling minimum on/off time (minutes)
This item is used to limit the on and off times of the cooling system.
When the cooling system starts, it must remain on for the minimum
time set by this item. When the cooling system turns off, it must
remain off for a minimum time set by this item.
Setting
Cycles per hour (maximum)
5
6
6
5
7
4
8
3.7
10
3
The recommended setting is 8 minutes. A higher setting may be
appropriate for buildings with low heat loss/gain.
The default setting is 8.
12 Heating minimum on/off time (minutes)
Same as Cooling minimum on/off time, for the heating system.
The default setting is 8.