HAI 54A00-1 Скачать руководство пользователя страница 4

 

Page 4 

Create the following programs: 
 

WHEN ARM AWAY: Armed Flag ON 
WHEN OFF: Armed Flag OFF 

 

WHEN RECEIVE 1234 &IF Armed Flag OFF: PROGRAM ARM AWAY 
WHEN RECEIVE 1234 &IF Armed Flag ON: PROGRAM DISARM 

 
Every time “1 2 3 4  #” is entered at the 54A00-1, the system will toggle between Away (armed in away mode) and Off (disarmed) 
and the red and green will toggle accordingly. 
 

Example 2: 

 
Additional codes and programs can be entered for other functionality.  For example, a code of ‘12341’ can be to activate an electric 
door strike that is connected to Output 2.  In this example the green LED is illuminated when the door strike is engaged (locked) and 
the red LED will illuminate when the door strike is disengaged (unlocked). 
 
a)

 

Enter the digits for each message under “Setup, Names, Messages”.  Each code can be up to 10 digits long:  Message 2 = 12341 

 
b)

 

Configure the voltage output to control the LEDs, under “Setup, Installer, Control”.  If the green wire is connected to Output 1, 
configure “Output 1” to “General Purpose”.  The red LED will illuminate when the output is turned on and the green LED will 
illuminate when the output is turned off. 

 
c)

 

Configure the voltage output to control the door strike, under “Setup, Installer, Control”.  If the door strike is connected to Output 
2, configure “Output 2” to “General Purpose”.   

 
d)

 

Configure the serial port and baud rate, under “Setup, Installer, Expansion, Serial Function”.  If the 54A00-1 is connected to 
Serial Port 1, configure “Serial 1 Function” to “Pro-Link” and configure “Serial 1 Rate” to “9600” baud. 

 
e)

 

In the example, Output 1 is named “Red LED” and Output 2 is named “Door Strike”. 

 
 

Create the following programs: 

 

WHEN RECEIVE 12341: Door Strike ON FOR 5 SECONDS 
WHEN Door Strike ON:  Red LED ON 
WHEN Door Strike OFF: Red LED OFF 

 
Every time “1 2 3 4  1 #” is entered at the 54A00-1, the output will turn on to disengage the electric door strike for the specified 
amount of time (i.e. 5 seconds).  The red LED will illuminate whenever the door strike is disengaged (unlocked) and the green LED 
will illuminate whenever the door strike is engaged (locked). 
 

 
 
 
SPECIFICATIONS

 

 
Dimensions: 

 

3-3/8W x 5-1/8H x 7/16D 

 
Nominal Voltage:  

10 – 13.7 VDC 

 
Current Consumption: 

25mA maximum 

 
Operating Ranges: 

-40°C to +70°C (-40°F to +160°F), 100% Relative Humidity 

 
 

 