T is the temperature difference between the upper limiting 

temperature of the installed equipment and the ambient air 
temperature of the distribution board.

Reference

Admissible thermal dissipation loss for wall mounted 
distribution boards at temperarture rise 

T*

10K

15K

20K

25K

30K

VS112..

4,3

7,1

10,1

13,3

16,7

VS212..

5,6

9,2

13,2

17,4

21,8

VS312..

6,9

11,4

16,3

21,5

27,0

VS412..

8,5

14,0

20,0

26,4

33,1

VS118..

5,8

9,5

13,7

18,0

22,6

VS218..

7,4

12,3

17,6

23,2

29,1

VS318..

9,1

15,0

21,5

28,3

35,6

VS418..

10,1

16,8

23,7

33,1

40,9

Attention!

It is critical that any enclosure is sized and selected to accomodate 
and dissipate heat rise generated from all installed devices.
The table (right) provides maximum permissible heat dissipation for 
each golf enclosure size. Please ensure that you calculate internal 
heat generated from your installation and select the correct 
enclosure accordingly.