Connecting and mounting the device
q
DANGER!
When connecting the bus/
extensions and mains' voltage wires
in a shared appliance box, the KNX
bus cable may come into contact
with the mains voltage.
The endangers the safety of the
entire KNX installation. People at
remote devices may also receive an
electric shock.
Do not place bus/extensions and
mains voltage terminals in a shared
connection compartment. Use an
appliance box with a fi xed partition
wall (picture 3) or separate boxes.
picture 3
(4) Appliance box
(5) Partition
(6) Potential-free contacts, e.g. for window contact
or installation pushbuttons
picture 4
Minimum spacing between the mains voltage and
bus/extension wires: 4 mm (picture 4).
• Connect the load (picture 5). Use the supplied
sprung screwless terminals. Flexible cable ends
must be tin-plated.
• Connect the device to KNX.
• If necessary, connect potential-free contacts (6)
to inputs (picture 2).
• Install the device in the appliance box.
picture 5
€
i
In the as-delivered state, Inputs 1 and 2 operate
the Venetian blind output. Input 3 has no function.
Function of Inputs 1 and 2 in the as-delivered
state
Input
NO contact
Blind
1
Press briefl y
Adjust slats
Up / Stop
1
Press for a
long time
Move up
2
Press briefl y
Adjust slats
Down / Stop
2
Press for a
long time
Move down
Commissioning
Load the address and the application software
• Switch on the bus voltage
• Assign physical addresses and load application
software into the device.
• Note the physical address on the device label.
Appendix
Technical data
Window interface 1gang fl ush-mounted
Supply
Rated voltage ................................. 230 / 240 V ~
Mains frequency .................................. 50 / 60 Hz
Switching voltage ..................................... 250 V~
Ambient conditions
Ambient temperature ........................ -5 ... +45 °C
Storage/transport temperature ........ -25 ... +70 °C
Venetian blind output
Contact type .......................................................μ
Switching current AC1 .................................... 3 A
Minimum switching current AC ................ 100 mA
Motors 230 V ............................................ 600 VA
Motors 110 V .................................................... —
Heating output
Output type ..................Semi-conductor (Triac),
ε
Switching current ............................... 5 ... 25 mA
Switch-on current ....................max. 600 mA (2 s)
Number of drives per output .....................max. 2
Control cable and inputs
Control cable (preterminated) ................. YY6x0.6
Input type ....................................... Potential-free
Total length of extension
unit cable ................................................max. 5 m
Poll voltage, extension inputs ........... approx. 5 V
Dimension
Ø×H ................................. 53×28 mm
Connection type
..................Terminal (enclosed)
Single-stranded
.......................... 1.0 ... 2.5 mm²
KNX medium
............................................... TP 1
Commissioning mode ............................. S mode
Rated voltage KNX ............DC 21 V ... 32 V SELV
Power consumption KNX .............. max. 240 mW
Own consumption on the KNX Bus:
- typical ................................................ 11,5 mA
- standby ............................................... 6,7 mA
6LE000839A