6. Programming the product
is to be programmed powered up and after wiring
verification tests. This may either be done through
the front of the ATS Controller using the keypad.
The product is delivered with default setting
values based on most used customer application
requirements. The minimum configuration
parameters that must be programmed are the type
of network and application together with the
voltage and frequency nominal values.
Network parameters
Ensure that the Default Network Setting and
Application match the installation or change
accordingly before using Auto Configuration
7A. Automatic operation
Ensure that the
emergency handle
is not inserted in
the product and
turn the mode
selector to the AUT
position.
LED green = “Power”:
ON
LED Manuel/Default:
OFF
LED green "AUT": ON
7B. Automatic operation:
remote control
Imp. ≥ 60ms
imp.
maintened.
To enable control,
close contact 312 with
317.
For contactor logic
bridge contact 316
with 317.
To operate: close the
contact corresponding
to the desired
position.
To force the product to 0 position “OFF” bridge
contact 313 with 317.
7C. Manual operation
90°
90°
I
II
0
7D. Padlocking mode
(standard: in position O)
Impulse logic
Contactor logic
Order I
Order O
Order II
Position I
Position O
Position II
AUT
IS 551645A
/ Printing size: 630x297
/ Recto-verso
/ Black
/ 90g/m²
/ Final size A4
&
Manual mode LED indication (yellow steady
light when in manual mode).
é
Auto mode LED indication (green steady
light when in auto mode with no timers
running. Green flashing light when in Auto
with timers running in the background.
"
Local/remote control mode LED indication
(yellow steady light when in remote control
mode). Remote control mode is achieved
with the Auto/Manu selector switched to
Auto and terminals 312 closed with terminal
317. Remote control orders are received
through closing 314 to 316 with 317.
'
TEST ON LOAD CONTROL mode LED
indication (yellow steady light when in TON
mode).
(
TEST OFF LOAD CONTROL mode LED
indication (yellow steady light when in TOF
mode).
§
Load supply on LED (green when the load
is supplied).
è
Switch 1 LED position indication (green
when in position 1).
!
Source supply I availability LED indication
(green when supply I voltage is within the
set limits).
ç
Zero position LED indication (yellow when
in position 0).
a
Switch 2 LED position indication (green
when in position 2).
z
Source supply II availability LED indication
(green when supply II voltage is within the
set limits).
e
LCD display screen: (status, measurement,
timers, counters, events, faults,
programming…).
r
Mode key to shift between operation
modes.
t
Navigation keys to browse through the
product menus without software.
y
Fault LED indication (red steady light in
case of an ATS controller internal fault.
Switch the product from Auto to Manual
and back to Auto to reset a fault condition).
u
Ready LED indication (green steady light:
product is powered and in Auto, watchdog
OK, the product is available to changeover).
i
Enter key used to enter Prog Mode (press
and hold for 5 seconds) and to validate the
settings programmed through the keypad.
o
ESC key used to escape from a specific
screen up to the main menu.
p
Lamp test key to check the LED’s and LCD
screen.
q
Green LED Indication: power.
s
Red LED indication: product unavailable/
manual Mode/fault condition.
d
Auto/Manual mode selector switch (key
version available as an option).
f
Padlocking facility (up to 3 padlocks of dia.
4 - 8mm).
g
Emergency manual operation shaft location
(accessible only in manual mode).
h
Switch position indication window:
I (On switch I)
O (Off)
II (On switch II).
Values as listed above are the setting
values by default.
Menus
1
SETUP
2
VOLT. LEVELS
3
FREQ. LEVELS
4
PWR. LEVELS
5
TIMERS VALUE
6
I-O
7
COMM
8
DATE/TIME
NETWORK
4NBL
OV. U
I
115%
OV. F
I
105%
OV.P
I
0000 kVA
1FT
0003 SEC
IN 1
--- NO
DHCP
NO
(9)
YEAR
AUTOCONF
NO
(7)
OV. U HYS
I
110%
OV. F HYS
I
103%
OV.P HYS
I
0000 kVA
1RT
0180 SEC
IN 2
--- NO
IP 1-2
192.168.
(9)
MONTH
NEUTRAL
AUTO
UND. U
I
085%
UND. F
I
095%
OV.P
I I
0000 kVA
2FT
0003 SEC
IN 3
--- NO
IP 3-4
.002.001
DAY
ROT PH.
---
UND. U HYS
I
095%
UND. F HYS
I
097%
OV.P HYS
I I
0000 kVA
2RT
0005 SEC
(2)
IN 4
--- NO
GAT1-2
000.000.
(9)
HOUR
NOM. VOLT
400 V
UNB. U
I
00%
OV. F
I I
105%
2AT
0005 SEC
(1)
IN 5
--- NO
GAT3-4
.000.000
MINUTE
NOM. FREQ
50 Hz
UNB. U HYS
I
00%
OV. F HYS
I I
103%
2CT
0180 SEC
(1)
IN 6
--- NO
MSK1-2
255.255.
(9)
SECOND
APP
M-G
OV. U
I I
115%
UND. F
I I
095%
2ST
0030 SEC
(1)
IN 7
--- NO
(8)
MSK3-4
.255.000
PRIO TON
NO
(1)
OV. U HYS
I I
110%
UND. F HYS
I I
097%
ODT
0003 SEC
IN 8
--- NO
(8)
ADDRESS
005
PRIO EON
NO
(3)
UND. U
I I
085%
TOT
UNL
(1)
IN 9
--- NO
(8)
BDRATE
9600
PRIO NET
1
(2)
UND. U HYS
I I
095%
TOT
0010 SEC
(1)
IN10
--- NO
(8)
STOP BIT
1
RETRANS
NO
UNB. U
I I
00%
T3T
0000 SEC
(1)
IN11
--- NO
(8)
PARITY
NONE
CT PRI
100
UNB. U HYS
I I
00%
TFT
UNL
(1)
IN12
--- NO
(8)
CT SEC
5
TFT
0600 SEC
(1)
IN13
--- NO
(8)
S1=SW2
NO
E1T
0005 SEC
(3)
IN14
--- NO
(8)
BACKLGHT
INT
E2T
UNL
(3)
OUT 1
POP NO
CODE P
1000
E2T
0010 SEC
(3)
OUT 2
--- NO
(8)
CODE E
0000
E3T
0005 SEC
(3)
OUT 3
--- NO
(8)
BACKUP
SAVE
E5T
0005 SEC
(4)
OUT 4
--- NO
(8)
E6T
LIM
(4)
OUT 5
--- NO
(8)
E6T
0600 SEC
(4)
OUT 6
--- NO
(8)
E7T
0005 SEC
(4)
OUT 7
--- NO
(8)
LST
0004 SEC
(5)
OUT 8
--- NO
(8)
EET
0168 H
(6)
OUT 9
--- NO
(8)
EDT
1800 SEC
(6)
Optional modules
Communication between the software and the
product may be done through the Ethernet/
Modbus TCP or Modbus RTU modules that are
available as an option. The ETHERNET/MODBUS
modules are to be installed in one of the slots
provided in the product ATS control unit.
Note :
the product may accept a total of
4 additional Input/Output modules offering an
additional 8 programmable inputs and
8 programmable outputs. When including a
MODBUS module the product accepts a total of
3 I/O modules and when including the ETHERNET
module a total of 2 I/O modules.
The Ethernet module includes a built in Web
Server for Monitoring, Engine Exerciser Control,
Events...
Setup by Auto Configuration
(Volts, Hz, Neutral
pos., Ph rotation).
Press 5s
Go to
1
SETUP
Scroll to
AUTOCONF
Enter code
1000
Set to
YES
Press 60 ms
LEDs flash
Save: press 5s
(1) When "APP" is set to"M-G".
(2) When "APP" is set to"M-M".
(3) When one of the I/P is set to"EON".
(4) When one of the I/P is set to "EOF".
(5) When one of the I/P is set to "LSC".
(6) When one of the I/P is set to "EES".
(7) If the product is in manual mode.
(8) With optional I/O modules.
(9) With Ethernet module.
Note :
source I or source II must be
available to set by Auto Configuration.
Programming access
Press and hold for 5 s “Validation” pushbutton
i
.
Access through the keypad is possible in
automatic or manual mode, when the product is in
a stable position (I, 0 or II) with at least one supply
source available.
Programming is not accessible whilst any cycle
sequence is running.
To change the configuration, enter code (factory
code = 1000) using navigation pushbuttons
t
.
Programming exit: press and hold for 5 s
“Validation” pushbutton
i
.
3 phases/4 wire
3 phases/3 wire
2 phases/3 wire
2 phases/2 wire
1 phase/2wire
1
3
2
N
4NBL
4BL
1
3
2
3NBL
3BL
1
2
3
2NBL
1
3
2BL
1BL
1
N
i
t
SM201: pulsed O/P
SM202: extended I/O 2xIP 2xO/P
SM203: 4-20 mA
SM211: modbus RS485
SM213: ethernet/modbus TCP
simple
SM214: gateway
+=,
%
%
3R
ZHU9a
3R
ZHU9a
AUT
6LE007790Aa
4
6LE007790Aa
5
6