6. Programming the product

is to be programmed powered up and after wiring 

verification tests. This may either be done through 

the front of the ATS Controller using the keypad.

The product is delivered with default setting 

values based on most used customer application 

requirements. The minimum configuration 

parameters that must be programmed are the type

of network and application together with the 

voltage and frequency nominal values.

Network parameters

Ensure that the Default Network Setting and 

Application match the installation or change

accordingly before using Auto Configuration

7A. Automatic operation

Ensure that the 

emergency handle 

is not inserted in 

the product and 

turn the mode 

selector to the AUT 

position.

LED green = “Power”: 

ON
LED Manuel/Default: 

OFF

LED green "AUT": ON

7B.  Automatic operation: 

remote control

   Imp. ≥ 60ms 

  imp. 

maintened.

To enable control, 

close contact 312 with 

317.

For contactor logic 

bridge contact 316 

with 317.
To operate: close the 

contact corresponding 

to the desired 

position.
To force the product to 0 position “OFF” bridge 

contact 313 with 317.

7C. Manual operation

90°

90°

I

II

0

7D.  Padlocking mode 

(standard: in position O)

Impulse logic 

Contactor logic

Order I

Order O

Order II

Position I

Position O

Position II

AUT

IS 551645A

 / Printing size: 630x297

 / Recto-verso

 / Black

 / 90g/m²

 / Final size A4

&

  Manual mode LED indication (yellow steady 

light when in manual mode). 

é

  Auto mode LED indication (green steady 

light when in auto mode with no timers 

running. Green flashing light when in Auto 

with timers running in the background.

"

  Local/remote control mode LED indication 

(yellow steady light when in remote control 

mode). Remote control mode is achieved 

with the Auto/Manu selector switched to 

Auto and terminals 312 closed with terminal 

317. Remote control orders are received 

through closing 314 to 316 with 317.

'

 

 

TEST ON LOAD CONTROL mode LED 

indication (yellow steady light when in TON 

mode).

(

  TEST OFF LOAD CONTROL mode LED 

indication (yellow steady light when in TOF 

mode).

§

 

 Load supply on LED (green when the load 

is supplied).

è

  Switch 1 LED position indication (green 

when in position 1).

!

  Source supply I availability LED indication 

(green when supply I voltage is within the 

set limits).

ç

  Zero position LED indication (yellow when 

in position 0).

a

  Switch 2 LED position indication (green 

when in position 2). 

z

 

 

Source supply II availability LED indication 

(green when supply II voltage is within the 

set limits).

e

  LCD display screen: (status, measurement, 

timers, counters, events, faults, 

programming…).

r

  Mode key to shift between operation 

modes.

t

  Navigation keys to browse through the 

product menus without software.

y

  Fault LED indication (red steady light in 

case of an ATS controller internal fault. 

Switch the product from Auto to Manual 

and back to Auto to reset a fault condition).

u

  Ready LED indication (green steady light: 

product is powered and in Auto, watchdog 

OK, the product is available to changeover).

i

  Enter key used to enter Prog Mode (press 

and hold for 5 seconds) and to validate the 

settings programmed through the keypad.

o

  ESC key used to escape from a specific 

screen up to the main menu.

p

  Lamp test key to check the LED’s and LCD 

screen.

q

  Green LED Indication: power.

s

  Red LED indication: product unavailable/

manual Mode/fault condition.

d

  Auto/Manual mode selector switch (key 

version available as an option).

f

  Padlocking facility (up to 3 padlocks of dia. 

4 - 8mm).

g

  Emergency manual operation shaft location 

(accessible only in manual mode).

h

  Switch position indication window:

 

I (On switch I)

 

O (Off)

 

II (On switch II).

Values as listed above are the setting 

values by default.

Menus

1

  SETUP

2

  VOLT. LEVELS

3

  FREQ. LEVELS

4

  PWR. LEVELS

5

 TIMERS VALUE

6

 

I-O

7

 

COMM

8

 DATE/TIME

NETWORK

4NBL

OV. U

I

115%

OV. F

I

105%

OV.P

I

0000 kVA

1FT

0003 SEC

IN 1

--- NO

DHCP

NO

(9)

YEAR

AUTOCONF

NO

(7)

OV. U HYS

I

110%

OV. F HYS

I

103%

OV.P HYS

I

0000 kVA

1RT

0180 SEC

IN 2

--- NO

IP 1-2

192.168.

(9)

MONTH

NEUTRAL

AUTO

UND. U

I

085%

UND. F

I

095%

OV.P

I I

0000 kVA

2FT

0003 SEC

IN 3

--- NO

IP 3-4

.002.001

DAY

ROT PH.

---

UND. U HYS

I

095%

UND. F HYS

I

097%

OV.P HYS

I I

0000 kVA

2RT

0005 SEC

(2)

IN 4

--- NO

GAT1-2

000.000.

(9)

HOUR

NOM. VOLT

400 V

UNB. U

I

00%

OV. F

I I

105%

2AT

0005 SEC

(1)

IN 5

--- NO

GAT3-4

.000.000

MINUTE

NOM. FREQ

50 Hz

UNB. U HYS

I

00%

OV. F HYS

I I

103%

2CT

0180 SEC

(1)

IN 6

--- NO

MSK1-2

255.255.

(9)

SECOND

APP

M-G

OV. U

I I

115%

UND. F

I I

095%

2ST

0030 SEC

(1)

IN 7

--- NO

(8)

MSK3-4

.255.000

PRIO TON

NO

(1)

OV. U HYS

I I

110%

UND. F HYS

I I

097%

ODT

0003 SEC

IN 8

--- NO

(8)

ADDRESS

005

PRIO EON

NO

(3)

UND. U

I I

085%

TOT

UNL 

(1)

IN 9

--- NO

(8)

BDRATE

9600

PRIO NET

1

(2)

UND. U HYS

I I

095%

TOT

0010 SEC

(1)

IN10

--- NO

(8)

STOP BIT

1

RETRANS

NO

UNB. U

I I

00%

T3T

0000 SEC 

(1)

IN11

--- NO

(8)

PARITY

NONE

CT PRI

100

UNB. U HYS

I I

00%

TFT

UNL 

(1)

IN12

--- NO

(8)

CT SEC

5

TFT

0600 SEC

(1)

IN13

--- NO

(8)

S1=SW2

NO

E1T

0005 SEC

(3)

IN14

--- NO

(8)

BACKLGHT

INT

E2T

UNL 

(3)

OUT 1

POP NO

CODE P

1000

E2T

0010 SEC

(3)

OUT 2

--- NO

(8)

CODE E

0000

E3T

0005 SEC

(3)

OUT 3

--- NO

(8)

BACKUP

SAVE

E5T

0005 SEC

(4)

OUT 4

--- NO

(8)

E6T

LIM 

(4)

OUT 5

--- NO

(8)

E6T

0600 SEC

(4)

OUT 6

--- NO

(8)

E7T

0005 SEC

(4)

OUT 7

--- NO

(8)

LST

0004 SEC

(5)

OUT 8

--- NO

(8)

EET

0168 H

(6)

OUT 9

--- NO

(8)

EDT

1800 SEC

(6)

Optional modules

Communication between the software and the 

product may be done through the Ethernet/

Modbus TCP or Modbus RTU modules that are 

available as an option. The ETHERNET/MODBUS 

modules are to be installed in one of the slots 

provided in the product ATS control unit.

Note : 

the product may accept a total of

 

4 additional Input/Output modules offering an 

additional 8 programmable inputs and

 

8 programmable outputs. When including a 

MODBUS module the product accepts a total of

 

3 I/O modules and when including the ETHERNET 

module a total of 2 I/O modules.
The Ethernet module includes a built in Web 

Server for Monitoring, Engine Exerciser Control, 

Events...

Setup by Auto Configuration

 (Volts, Hz, Neutral 

pos., Ph rotation).
Press 5s

Go to

1

  SETUP

Scroll to

AUTOCONF

Enter code

1000

Set to

YES

Press 60 ms

LEDs flash

Save: press 5s

(1)  When "APP" is set to"M-G".

(2)  When "APP" is set to"M-M".

(3)  When one of the I/P is set to"EON".

(4)  When one of the I/P is set to "EOF".

(5)  When one of the I/P is set to "LSC".

(6)  When one of the I/P is set to "EES".

(7)  If the product is in manual mode.

(8)  With optional I/O modules.

(9)  With Ethernet module.

Note :

 source I or source II must be

available to set by Auto Configuration.

Programming access

Press and hold for 5 s “Validation” pushbutton 

i

.

 

Access through the keypad is possible in 

automatic or manual mode, when the product is in 

a stable position (I, 0 or II) with at least one supply 

source available.

 

Programming is not accessible whilst any cycle 

sequence is running.

To change the configuration, enter code (factory 

code = 1000) using navigation pushbuttons 

t

.

Programming exit: press and hold for 5 s 

“Validation” pushbutton 

i

.

3 phases/4 wire

3 phases/3 wire

2 phases/3 wire

2 phases/2 wire

1 phase/2wire

1

3

2

N

4NBL
4BL

1

3

2

3NBL
3BL

1

2

3

2NBL

1

3

2BL

1BL

1

N

i

t

SM201: pulsed O/P

SM202: extended I/O 2xIP 2xO/P

SM203: 4-20 mA

SM211:  modbus RS485 

SM213:  ethernet/modbus TCP 

simple

SM214:  gateway

+=,

%

%

3R

ZHU9a

3R

ZHU9a

AUT

6LE007790Aa

4

6LE007790Aa

5

6

Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com

OCOM 141942

Hager 06.21

6LE007790Aa

p

é

j

"

h

'

(

!

r

è
§

&

e

z

a

ç

y

q

s

u

t

i

o

f

d

Отзывы: