6H5570-50B
2. Power terminal connections
Use terminal lugs, rigid or flexible busbars.
Orientation
Recommended
OK
OK
NO
1. Installation
Ensure that the product is installed
on a flat rigid surface.
4.
3.
6LE007790Aa
HIC4xxE
Preliminary operations
Check the following upon delivery and after removal
of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and fixing clip
- 1 x quickstart instruction sheet.
Accessories
• Bridging bars and connection kits.
• Terminal shrouds.
• Terminal shield.
• Voltage sensing kit.
• HZI911 interface.
• Current transformers.
• Plug-in optional modules: RS485 MODBUS
communication, 2 inputs/2 outputs, Ethernet
communication, Ethernet communi
RS485 JBUS/MODBUS gateway, Analogue
outputs, Pulse outputs.
This quick start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the hager website.
• This product must always be installed and
commissioned by qualified and approved
personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables
connected to the product when voltage may be,
or may become present on the product, directly
through the mains or indirectly through external
circuits.
• Always use an appropriate voltage detection
device to confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
•
For 800 – 3200A (Uimp = 12kV). Terminations
must respect a minimum of 14 mm clearance
from live parts to parts intended to be earthed
and between poles.
Failure to observe good enginering practises as
well as to follow these safety instructions may
expose the user and others to serious injury or
death.
Installation and commissioning
Risk of electrocution, burns or injury to
persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or
damaged in any way it is recommended
to replace the complete product
.
Step 1
Cabinet/
Back Plate
Installation
Step 2
Connecting the
power section
Step 3
COMMAND/
CONTROL
terminal
connections
Step 4
Power SUPPLY
and controller
terminal
connections
Step 5
Check
Step 6
Programming
Step 7A
AUT Mode
(Automatic
Control)
Step 7B
AUT Mode
(Remote
Control)
Step 7C
Emergency
Manual
Operation
Step 7D
Padlocking
z
Motorised source changeover switch
800A - 3200A
1
Preferred source
2 Alternate source
&
Position 0 order
é
Position 1 order
"
Position 2 order
'
Zero position priority order
(
Remote control enable (priority over auto)
§
Product available output (Motor)
è
Position II aux contact
!
Position I aux contact
ç
Position 0 aux contact
a
O/P to HZI911 remote display
z
Programmable output contact, by default set
to ATS product available - Normally open
e
to
y
programmable inputs 1-4
u
and
i
programmable inputs 5-6
o
Aux. supply (207/210) to be used with
optional I/O modules
p
Contact “Start/Stop Genset”: if S1 is not
available the NC contact (71-72) is closed
q
Contact “Start/Stop Genset”: if S1 is not
available the NO contact (71-74) is open
s
Option module slots 1 to 4
d
Current Transformer incoming cable
connections
f
Voltage sensing inputs
g
Power supply inputs
Example: control wiring for a 400 VAC application having a 3 phase and neutral supply
3. CONTROL/COMMAND terminals
Ensure that the product is in Manual Mode.
f
f
g
g
HZI911
4. Power supply, sensing and control wiring
Use cables with 1,5 to 2,5 mm
2
section.
Screw M3
Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
+=,
%
%
3R
ZHU9a
3R
ZHU9a
ATS Power supply input II
Power supply II - L
Power supply II - N
208-277 VAC ±20% : 50/60 Hz
ATS Voltage sensing input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
575 VAC (ph-ph) maxi
S II - Neutral
332 VAC (ph-n) maxi
Programmable inputs
To option module (-)/Common
Progr. inputs (208-209)
To option module (+)
Genset Start/stop
N
C
Common
NO
ATS Power supply input I
Power supply I - L
Power supply I - N
208-277 VAC ±20% : 50/60 Hz
ATS Voltage sensing input
Source supply I
S I - Phase 1
S I - Phase 2
S I - Phase 3
575 VAC (ph-ph) maxi
S I - Neutral
332 VAC (ph-n) maxi
ATS Module control inputs
(programmable)
ATS Module output control
(programmable)
Remote interface
RJ45 to HZI911
Current transformer incoming
cable connections
Slot for optional modules
5. Check
Whilst in manual mode,
check the wiring
and if ok power up
the product.
LED Green =
“Power” : ON
LED Red =
“Manuel/Defaut”: ON
800 A
1000
A
1250
A
1600 A
2000 A
2500 A
3200 A
Minimum Cu
cable section
at Ith
(mm
2
)
2x185
-
Minimum Cu
busbar section
at Ith
(mm
2
)
2x50x5 2x63x5
2x63x7
2x100x5 3x100x5 2x100x10 3x100x10
Maximum Cu
cable section (mm
2
)
4x185
6x185
-
Maximum Cu
busbar width
(mm)
63
100
Type of screw
M8
M10
M12
Recommended
tightening
torque
(N.m)
8,3
20
40
Maximum
tightening
torque
(N.m)
13
26
45
Dimensions in mm
Door cut-out for front panel
2000A to 3200A
800A to 1600A
33
8.5
8.5
50
33
10
ø 9
ø 15
800A to 1000A
16 x 11
60
28.5
15.75
15.75
28.5
15
1250A
15
5
5
12.5
25
25
30
30
45
45
90
ø12.5
1600A to 3200A
T
250
C
21
28
0
C
21
25
0
M
T
51,5
M
51.5
800A
1000A
1250A
1600A
2000A
2500A
3200A
4P
M
335
467
T
80
120
C
391
523
Clip for
storage
of the
emergency
handle
6LE007790Aa
1
6LE007790Aa
2
6LE007790Aa
3