6LE007621A
21
11.1.2. Reset
Operating fault reset
Open and re-close the AUT/MAN cover
11.2.
Manual mode
To access manual mode, open the Aut/Man cover.
Once manual mode is active (cover open) it is possible:
• To lock the changeover switch.
• To access the DIP switches programmation.
• To manually operate the changeover switch using the handle.
As soon as manual mode is activated, remote orders are inhibited (except the Genset start order in case of a mains loss.
Padlocking
Changeover switching
Manual
DIP switch
programmation
MANUAL MODE
11.3.
Manual switching
Use the handle situated on the front panel under the cover to
manoeuvre the changeover switch. To simplify the operation, it is
advised to also use the handle extension that is delivered with the
product.
Check the changeover switch position on the indicator situated on
the front panel before making any operation.
• From position I, turn anti-clockwise to get to position 0
• From position 0, turn anti-clockwise to get to position II
• From position II, turn clockwise to get to position 0
• From position 0, turn clockwise to get to position I
Do not force the product (Max 8 Nm).
(Max 8 Nm)
Extension