Motorised changeover switch
125A to 630A
Installation and commissioning
Cabinet /
Back Plate
Installation
Step 1
Connecting the
power section
Step 2
COMMAND /
CONTROL terminal
connections
Step 3
Power SUPPLY
terminal
connections
Step 4
Check
Step 5
Emergency
Manual
Operation
Step 6B
Control by
an external
order (AUTO)
Step 6A
Padlocking
Step 6C
Clip for
storage
of the
emergency
handle
IS 551584A
/ Printing size: A3/
Recto-verso/
Black/
90g/m²/
Final size A4
551584A
Notes
6LE007719Aa
1
Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com
OCOM 140890
Hager 07.21
6LE007719Aa
4
Preliminary operations
Check the following upon delivery and after removal of
the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and fixing clip
- 1 x quick start instruction sheet
Accessories
• Bridging bars and connection kits
• Terminal shrouds
• Terminal shield
This quick start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available
on the hager website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables connected
to the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Risk of electrocution, burns or injury to
persons and / or damage to equipment.
Risk of damaging the device: In case the
product is dropped or damaged in any way
it is recommended to replace the complete
product.
• For 125 - 160A (Uimp = 8 kV). Terminations must
respect a minimum of 8 mm clearance from live parts
to parts intended to be earthed and between poles.
• For 200 - 630A (Uimp = 12 kV). Terminations must
respect a minimum of 14 mm clearance from live parts
to parts intended to be earthed and between poles.
Failure to observe good enginering practises as well as
to follow these safety instructions may expose the user
and others to serious injury or death.