1
6E 6360.c
6E 6360.c
§
2 channel programmer
annual and weekly cycle
User instructions
Navigation &
value setting
Validation
Enter in PROGRAMME mode &
return to previous step
Selection of days of the week
1 = Monday, 2 = Tuesday
... 7 = Sunday
Canal B command
Canal A command
Keyboard locked by PIN code
menu
+
ok
At any time, pressing the button menu allows you
to return to the previous choice level.
Programming
To do the yearly programming of the clock, you
have the following 4 types of programme :
-
Basic weekly programme
This is a non-priority weekly programme.
-
Sub-programmes 1 to 10
These are weekly sub-programmes which are
activated for a defined date-to-date period. As
the sub-programme number increases, so does
the priority.
-
DATE/TIME
This is a programme step composed of a time
and a date which will run in addition to the usual
programme. If there is conflict between this
programme step and another programme step
(SP or weekly), this step has priority.
-
Holidays
This programme allows you to define a
permanent ON or OFF from date-to-date.
This programme has the highest priority.
Product Presentation
Connection diagram
A
B
1 3 5
2 4 6 8 10 12 14 16
11 13 15
7 9
L
N
EG293B
Menu
Press the button
menu
to access the programming/
setting mode.
All of the programming and adjustments are
based on the following principle :
- the 1st line and/or 2nd line of the display
indicate the requested setting,
- the buttons
+
/
-
allow navigation through the
menus and settings,
- the button
ok
allows validation.
Pressing the button menu allows you to access
the following settings :
PROGRAM
SETTINGS
FUNCTIONS
DATE-TIME
S/W TIME
LANGUAGE
FACTORY
SETTINGS
BACK AUTO
PROGRAM
CREATE
PROGRAM
READ
PROGRAM
MODIFY
PROGRAM
DELETE
PROGRAM
COPY
BACK AUTO
COUNTER
CYCLE
PIN CODE
INPUT
BACK AUTO
menu
Electrical characteristics
⦁
Supply voltage :
230 V
+
10/-15%
⦁
Frequency : 50/60
Hz
⦁
Power consumption :
< 2 VA
⦁
Output :
2 changeover contacts
⦁
Maximum load :
AC1 μ 10A 250 V
~
Incandescent lighting :
1500 W
Halogen lighting :
230 V 1500 W
Compensated fluorescent tubes // :
(max. 45 μF) 400 W
Non compensated fluorescent tubes,
compensated in series :
1000 W
Compact fluorescent lamps :
400 W
⦁
Minimum load
AC1 100 mA 250 V
~
⦁
Galvanic insulation between power supply and
output
< 4 kV
Technical specifications
Functional characteristics
⦁
Programming capacity :
300 steps
⦁
Minimum time between 2 steps :
1 minute
⦁
Running accuracy :
± 0,2 sec/ 24h
⦁
Operating reserve : lithium battery, total of 5
years autonomy (unlimited programme backup)
⦁
The product is set into standby state (display
switched-off) after 1 minute with power off.
It switches back into automatic mode as soon
as power is back on or when pressing any key.
⦁
Protection degree :
IP 20 / IK 04
Environment
⦁
Operating temperature :
-10 °C to
+
50 °C
⦁
Storage temperature :
-20 °C to
+
70 °C
Connection by quick-connect terminals
⦁
Flexible :
0,75 to 2,5 mm
2
⦁
Rigid :
0,75 to 2,5 mm
2
Presentation
⦁
Product delivered with current time and date set.
⦁
Automatic change of summer/winter time.
⦁
Programming key
-
For permanent overrides
-
For program copy or save
⦁
300 programme steps ; ON, OFF, pulses
or
.
⦁
Permanent overrides On or Off (
permanent
light on).
⦁
Temporary overrides On or Off (
flashing).
⦁
Overrides (temporary, permanent or time delayed)
remote activation possible.
⦁
Simulation of presence
.
⦁
Keyboard lock function
by PIN number.
⦁
Counter of operating time on every output.
⦁
Programmable with power off.
⦁
Display with backlight.
When using for the first time, the following
settings must be done :
- select the language
- select the year, month, day
- select the hour and the minutes
- select the automatic change summer/winter.
Press the buttons
+
/
–
to set the display.
Press
OK
to validate.
When the settings are finished, the clock goes to
automatic mode.
First commissioning
*
*
Input for external override
Pressing simultaneously the
menu
,
–
,
+
,
ok
keys
allows you to réinitialize the product.
The program is kept in memory.
Reinitializing
Creating a holiday programme
The Holiday programme allows you to define one
or several periods during which the output
contact is on ON or OFF.
This programme has the highest priority.
To define your Holiday programme :
To visualise a programme
To check the steps of the recorded programme
without risk of modifying or deleting.
Creating a specific programme step (day-time) :
A specific programme step is a programme step
composed of a switching time and a date.
This happens in addition to the weekly programme
type or the sub-programme. If there is conflict, this
has priority.
PROGRAMME READ
HOLIDAYS
DAY/TIME
SP1 - SP10
WEEKLY
HOLIDAYS
DATE/TIME
SP1 - SP10
WEEKLY
BACK
AUTO
DELETE
MODIFY
HOLIDAYS
OFF
NOT
REPEATED
VARIABLE
DATE
HOLIDAYS
ON
FIX
DATE
14.07 - 03.08
HOLIDAYS
CONTINUE
PROGRAM
START
MONTH
01.
07
START
DAY
14
.07
END
MONTH
01.
08
END
DAY
03
.08
DATE/TIME
CYCLE
DATE/TIME
IMPULSE
DATE/TIME
OFF
NOT
REPEATED
KEEP
DAYWEEK
BACK
AUTO
DELETE
MODIFY
DATE/TIME
ON
FIX DATE
07:00
CONTINUE
PROGRAM
EX 03.03
ON
07:00
SET
HOUR
00:
00
SET
MINUTES
00:
00
SET
MONTH
00:
00
SET
DAY
00:
00
Select :
- fixed dates : if the programme must be
repeated every year at the same dates.
- KEEP DAY WEEK : if the dates must be
recalculated every year in order to occur on
the same day of the week.
- NOT REPEATED : if the programme is to be
activated once only.
Validate by
ok
.
Select :
- FIX DATE : if the programme must be repeated
every year at the same dates.
- VARIABLE DATE (
) if the dates must be
recalculated every year according to the dates
of Easter.
- NOT REPEATED : if the programme is to be
activated once only.
Validate by
ok
.
1. Define the weekly programme
Creating a sub-programme (SP1-10) :
Two phases are necessary to create a sub-
programme :
Define the weekly programme.
Define the period when the programme will be active.
Creating the basic weekly programme
:
CYCLE
FUNCTIONS
SETTINGS
CHANNEL B
HOLIDAYS
DAY/TIME
SP1 - SP10
IMPULSE
OFF
NO
MONDAY
BACK
AUTO
DELETE
MODIFY
PROGRAM
COPY
PROGRAM
DELETE
PROGRAM
MODIFY
PROGRAM
READ
PROGRAM
CREATE
CHANNEL A
WEEKLY
PROGRAM
ON
YES
MONDAY
SUNDAY
SET
MINUTE
00:
00
ON
07:00
CONTINUE
PROGRAM
SET
HOUR
00
:00
menu
HOLIDAYS
DAY/TIME
SP1 - SP10
SP
ACTIVATE
WEEKLY
SP
PROGRAM
BACK
AUTO
DELETE
MODIFY
SUNDAY
SET
MINUTE
00:
00
SP01
ON
07:00
CONTINUE
PROGRAM
SET
HOUR
00
:00
PROGRAM CREATE
PROGRAM
FUNCTIONS
SETTINGS
PROGRAM
menu
*
*
The cycle
programme is only
possible if one or
several cycles have
been defined in the
FUNCTION/CYCLE
menu.
SP
ACTIVATE
SP01
IMPULS
SP01
OFF
NO
MONDAY
SP
NUMBER
10
SP
NUMBER
...
SP
NUMBER
02
SP
PROGRAM
SP
NUMBER
01
SP01
ON
YES
MONDAY
SUNDAY
Select :
- fixed dates : if the programme must be repeated
every year at the same dates.
- variable date (
) if the dates must be recalculated
every year according to the dates of Easter.
- NOT REPEATED : if the programme is to be activated
once only.
Validate by
ok
.
2. Activate the sub-programme.
To define the start and end of activation dates of the
sub-programme :
SP
ACTIVATE
BACK
AUTO
DELETE
MODIFY
SP
NUMBER
10
SP
NUMBER
...
SP
NUMBER
02
NOT
REPEATED
VARIABLE
DATE
SP
PROGRAM
SP
NUMBER
01
FIX
DATE
28.01 - 14.02
SP1
CONTINUE
PROGRAM
START
MONTH
01.
01
START
DAY
28
.01
END
MONTH
01.
02
END
DAY
14
.02
HOLIDAYS
DAY/TIME
SP1 - SP10
WEEKLY
A sub-programme can be attributed to several different
periods.
When the start date and the end date are identical, the
sub-programme is only valid for that day. If several
programmes are activated in the same time, at the
same date, the programme with the highest number
(eg. Pg 10) is the one that will be activated.
The other sub-progammes will be cancelled.
EG293B
http://waterheatertimer.org/Hagar-timers-and-manuals.html
_________________________________________________________________________