background image

1

6E 6131.c

6E 6131.c

7

6

on

off

5

4

3

2

1

ON

OFF

enter

reset

prog
auto
manu

EG171

§

1 impulse channel time switch -
weekly cycle

User instruction

NC

D

ATÉ

du 15/02/2010

EG171

3 4 5 6

2

1

L
N

Technical specifications :

Electrical characteristics :

- supply voltage : 230V +10/-15%   50Hz
- output : 1 changeover contact

μ 16A - 250V AC1.
μ 3A - 250V cos 

φ

= 0.6

1000 W incandescent lighting

- power consumption : 1 VA
- protection degree : IP20
- insulation class : II

Functional characteristics :

- accuracy : ± 1sec. / day at 20 °C
- operating reserve : lithium battery, 

total of three years.

Environment :

Operating temperature : -10 to +50 °C
Storage temperature :

-10 to +50 °C

Connection tunnel terminals : 

flexible : 0,5 to 2.5 mm

2

rigid : 0,5 to 4 mm

2

Dimensions : 3 modules (3x17,5mm)

Electrical connections :

1. Move mode selector to “

manu

”.

2. Select the state of the output with key 

on/off

”.

3. Input with key “

+

” and “

-

” the override duration :

from 1 to 23 hours by steps of 1 hour,
then from 1 to 27 days by steps of 1 day. 

4. Move mode selector to “

auto

”.

The state indication is flashing. This means a  
timed override. Return to the initial program  
after the duration.

To reset the time switch :

Press “

reset

“ to clear the program.

1. Move mode selector to “

manu

”.

2. Press key “

-

” or “

+

” until display -h. 

3. Move mode selector to “

auto

” to switch  

back to automatic mode.

Timed override :

enter

reset

on

off

prog
auto

manu

ON

enter

reset

on

off

prog
auto

manu

ON

A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). The warranty
is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry at
the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.

Warranty

GB

Working principle :

The EG 171 is a time switch especially des-
igned to control any timed delayed application
(school bells, fans, etc...).
It is fully programmable with a maximum of 20
program steps. Each program step can be
applied to one or several days, maximising the
use of each memory location.
The front cover is sealable preventing 
unauthorised access after completion of 
programming.

Warning :

at the beginning of use, please  

reset the device in order to clear the memory
before programming. 
This is achieved by using a pen to push the
reset button.

Presentation :

Display :

time

circuit status (ON or OFF)

day of the week 
(1 = Monday, 2 = Tuesday ....)

Buttons :

Mode selector : to select one of the  
following modes :

time setting

prog

programming

auto

running mode

manu

manual override

1

” to “

7

” : selection of the days

on/off

” : chooses whether the circuit 

is on or off

+

” and “

-

” : changes settings

enter

” : to confirm

reset

” 

Time and day setting : 

1. Move mode selector to 
2. Select with key “

1

” to “

7

” , the actual day 

(1 = Monday, 2 = Tuesday.)

3. Input time with buttons “

+

” and “

-

”.

Important :

The clock starts when exiting the time setting mode.

Programming :

1. Move mode selector to “

prog

”.

2. Input the impulse duration with keys “

+

” and “

-

” 

from 1 to 59 seconds (in 1 sec. increment),
then from 1 to 99 minutes (in 1 min. increment).
- seconds are shown as e.g. 10” 
- minutes are shown as e.g. 2’ 

3. Select with keys “

1

” to “

7

” the day(s) assigned  

to this program step. An arrow appears  
above each day concerned.

4. Input switching time with buttons “

+

” and “

-

”.

5. Enter this program step with button “

enter

”.

Program additional time settings by repeating  
steps 3 to 5.

To modify the impulse duration while programming,
press “

on/off

” key.

To switch back to programmation, press “

on/off

”.

Important :

To activate the program, move mode selector to

auto

”.

Running Auto mode

This mode is the current displaying mode. 
It does not allow any modification.

Move mode selector to “

auto

”.

Display of the time, the day and the state of the
channel.

To check your program :

1. Move mode selector to “

prog

”.

2. Press the “

enter

” key repeatedly to display  

the different program steps (switching  
time and days assigned).

To override the output :

Permanent override :

1. Move mode selector to “

manu

”.

2. Select the state of the output with key 

on/off

”.

To switch back to automatic mode, move  
mode selector to “

auto

”.

4

5

1

6

7

8

9

3

2

enter

reset

on

off

prog
auto

manu

OFF

enter

reset

on

off

prog
auto

manu

To modify or delete a program step :

1. Move mode selector to “

prog

”.

2. If necessary modify the impulse duration 

and confirm with “

enter

”.

3. Press “

enter

” repeatedly and select the 

program step to modify or to delete.

4. Modify :

- switching time with keys “

+

” or “

-

” 

- days assigned with keys “

1

” to “

7

(an arrow flashes above all days assigned, 
press once to add a day, press twice to 
cancel).

- impulse duration by pressing key “

on/off

and then with “

+

” and “

-

To delete a program step, press keys “

1

” to 

7

” in order to cancel all days assigned.

5. Confirm with the “

enter

” key.

enter

reset

on

off

prog
auto

manu

ON

ON

enter

reset

on

off

prog
auto

manu

ON

enter

reset

on

off

prog
auto

manu

ON

To cancel the timed override : 

 

http://waterheatertimer.org/Hagar-timers-and-manuals.html

_________________________________________________________________________

Отзывы: