background image

2

HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

EASIER INSTALLATION

NEW

1.

 

INSTALLATION OF DAMPERS  

AGAINST STRUCTURAL ELEMENTS

 

WITHOUT CAULKING AND REFINISHING

1. Hole dimensions

Damper dim5 mm for sizes 100-315 mm.
Damper dim10 mm for sizes 400-630 mm

4. Sealing

 

Seal between the damper and the wall with a fire-resistant 
sealant.

2. Angle brackets

 

Fix the supplied angle brackets spaced evenly  
around the damper.

Angle bracket

 (supplied)

3. Fix the duct

 

Fix the duct to be installed through the structural element 
against the damper fitting with flat head screws. Check that 
the screws do not hinder damper blade movement. 

Note the installation direction of the damper.

5. Centre in the hole

 

Place the damper casing flush against the structural element, 
centre it in the hole and fix with the angle brackets.

Drawing name:

Содержание INTACT

Страница 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Страница 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Страница 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Страница 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Страница 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Страница 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Страница 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Страница 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Страница 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Страница 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...

Отзывы: