ASP-R Quick Start Guide
Approved Document Ref: UI-ASP-R-02 Issue 1.0
6
SETUP & PROGRAMMING
PROGRAMMING SEQUENCE
1
2
Turn on program switch (6) on main PCB
2
1
2
3
Panel Wide Settings
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6 programmable
options are represented by
fi
re zone LEDs 1 - 6, Option 5 being the, ‘set up
internal PCB con
fi
guration’ setting.
Use button 1 to move to option 5
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1
Change / remove keypad access code
2
Set number of repeater panels on system
3
Set output delay time (1 - 10 minutes)
4
Turn off battery monitoring
5
Set up internal PCB con
fi
guration (add extension
zone card or repeater comms PCB)
6
Change repeater comms monitoring
5. Setup Internal PCB Con
fi
guration
With the zone 5
fi
re LED lit, the amber, fault LEDs will show the current con
fi
guration setting. Each of the
3 possible additional internal PCBs are represented by LEDs 1 - 3 as per table below.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Press the ENTER button, zone 1
fi
re LED will pulse to indicate editing of 1st additional PCB as per table
above. Use button 1 to move to pulsing
fi
re LED 3.
Now use button 2 to change the setting (Amber LED ON = PCB included, OFF = not included).
When
fi
nished press the ENTER button again and the zone 5
fi
re LED will return to steady ‘view mode’,
with the amber, fault LEDs showing the new con
fi
guration.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
LED 1 (ON)
LED 2 (ON)
LED 3 (ON)
Extension zone card 1
(zones 5 - 8)
Extension zone card 2
(zones 9 - 12)
Repeater Comms PCB
To change the internal PCB con
fi
guration at the main control panel use: