Parameterization and operation
MODEL CORRECTION FACT.
This factor can be used on order to fine tune the DO concentration
calculated by the model (feed forward part of the N-RTC).
SUBSTIT. DO FOR MODEL
If there is a failure in any of the input signals (NH4-N, TSS, Flow) the
N-RTC will apply the this DO feed forward set point for all further
calculation
[mg/L]
NH4-N SETPOINT
Desired set point of the NH4-N concentration effluent aeration
[mg/L]
P FACT NH4
Note: These settings are only necessary if NH
4
-N measurement in
effluent for feed back control is available!
Proportional factor for the PID closed loop controller for the NH4-N
concentration effluent aeration.
[1/mg/L]
INTEGRAL TIME NH4
Note: These settings are only necessary if NH
4
-N measurement in
effluent for feed back control is available!
Integral time for the PID closed loop controller for the NH4-N
concentration in the thickened sludge.
Note: INTEGRAL TIME NH4 is set to “0” to deactivate the integral
part of the PID controller.
[min]
DERIVATIVE TIME NH4
Note: These settings are only necessary if NH
4
-N measurement in
effluent for feed back control is available!
Derivation time for the PID closed loop controller for the NH
4
-N
concentration effluent aeration
Note: DERIVATIVE TIME NH4 is set to “0” to deactivate the
derivative part of the PID controller.
[min]
LIMITS
MIN DO
If a calculated DO set point is lower than the MIN DO value, the DO
set point is set to that value
[mg/L]
MAX DO
If a calculated DO set point is higher than the MIN DO value, the DO
set point is set to that value
[mg/L]
SMOOTHING
Smoothing on the calculated DO set point
[min]
DO CONTROLL
CHANNEL 1
P GAIN DO
Proportional factor for the PD closed loop controller for the DO
concentrtion in the aeration.
[1/mg/L]
DERIVATIVE TIME
Derivative Time of DO controller
[min]
INT PART
Integral part for DO control
DAMPING
Damping of DO control
[min]
SUBST AERATION
If the DO sensor (e.g. LDO) signals a fault, the set aeration stage is
selected
[Stage]
NO. OF STAGES
Number of controlled aeration stages (maximun 6)
[Stage]
VFD P MIN
Set minimum speed for VFD controlled blowers (stage 1 and 2)
[%]
CHANNEL 2
same as CHANNEL 1
4.5.3
2-Channel RTC103 N-Module VFD (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
Содержание RTC103 N-Module
Страница 2: ......
Страница 6: ...6 Table of Contents ...
Страница 14: ...14 General Information ...
Страница 20: ...20 Installation ...
Страница 54: ...54 Maintenance ...
Страница 56: ...56 Troubleshooting ...
Страница 58: ...58 Replacement parts and accessories ...
Страница 62: ...62 Warranty and liability ...
Страница 64: ...64 MODBUS address setting ...
Страница 66: ...66 Index ...