Attaching the cage nuts and slide rails to the rack 

安装浮动螺母及滑道

Mounting the device in a rack 

安装设备

Attaching the mounting brackets and chassis rails to the 
device 

安装挂耳及导轨到设备

Connecting the grounding cable 

连接保护地线

The device has a primary grounding point (above the power module slots) and an auxiliary grounding point.
The primary grounding point has a grounding sign and grounding screw while the auxiliary grounding point does
not. The grounding screw for the primary grounding point is also applicable to the auxiliary grounding point.
To use the auxiliary grounding point, connect the grounding cable to it before mounting the device in a rack.

主接地点(电源模块上方接地点)标有接地标识,并带有接地螺钉,备用接地点无接地标识和接地螺钉。

主接地点上的接地螺钉同样适用于备用接地点。

为了防止机箱安装到机柜后无法安装备用接地线,请您先连接备用接地点。

The device provides multiple chassis rail installation positions on its sides. Determine the chassis rail 

installation position based on the rack depth and make sure the front ends of slide rails reach out the 

chassis rails for the device stability.

The following figure uses installing the mounting brackets near the hard disk side as an example. 

设备侧面板提供了多个滑道导轨安装位,用户可根据机柜的深度,调整滑道导轨的安装位置;为保证设备
安装后的稳定性,当滑道与滑道导轨安装完成后,请确保滑道的头部露出滑道导轨。
本文仅以挂耳安装在靠近硬盘侧的安装位置为例进行介绍,请根据实际安装场景的需要选择合适的
安装位置。

Rack requirements 

推荐机柜尺寸

Auxiliary grounding point

备用接地点

Chassis dimensions

设备尺寸

Rack requirements

对机柜的要求

Height

—88.1 mm (3.47 in)

Width

—440 mm (17.32 in)

Depth

—775.5 mm (30.53 in)

        660 mm (25.98 in) for the chassis

90 mm (3.54 in) for the cable management brackets at the front

        25.5 mm (1.00 in) for the power module handle at the rear

宽度

440 mm

高度

88.1 mm

装配完成后总深度

775.5 mm

机箱本体深度

660 mm

前侧信号线走线架深度

90 mm

后侧电源模块拉手深度

25.5 mm

A minimum of 1000 mm (39.37 in) in depth
(recommended)

A minimum of 100 mm (3.94 in) between the front 

rack posts and the front door

A minimum of 760 mm (29.92 in) between the front 

rack posts and the rear door

518 mm (20.39 in) to 858 mm (33.78 in) between 

   the front and rear rack posts
H3C

推荐您选配

1000mm

及以上深的机柜,并且要求:

前方孔条到前门有不小于

 100 mm

空间

前方孔条到后门有不小于

 760 mm

空间

前后方孔条间距

518mm

858mm

Primary grounding point

主接地点