background image

4

3

Installing the switch in a 19-inch rack 

安装交换机到19英寸机柜

Before installing cage nuts, mark their installation positions on the rack posts.

安装浮动螺母前,建议用户先使用记号笔在机柜方孔条上标注浮动螺母安装位置。

Connect the grounding cable to a grounding point on the chassis before installing the switch in the rack. 

为了防止机箱安装到机柜后无法安装接地线,请您先将接地线安装到交换机的接地点上。

The switch has three grounding points. The primary grounding point and auxiliary grounding point 1 

are on the side panel. Auxiliary grounding point 2 is on the rear panel. The switch provides a 

grounding sign at the primary grounding point but not at auxiliary grounding points 1 and 2. 

设备提供

3

处接地点,主接地点和备用接地点

1

位于机箱侧面板,备用接地点

2

位于机箱后面板。主接

地点标有接地标识,备用接地点

1

和备用接地点

2

无接地标识。

The grounding cable and grounding screw provided with the switch are applicable only to the 

primary grounding point and auxiliary grounding point 1. 

随机附带的接地线缆和接地螺钉仅适用于主接地点和备用接地点

1

As a best practice, use the primary grounding point or auxiliary grounding point 1 for grounding. To 

use auxiliary grounding point 2, prepare a grounding cable yourself.

建议您优先选用主接地点和备用接地点

1

进行接地。如需使用备用接地点

2

进行接地,请自备接地线缆。

Mounting brackets installed near the port side 

挂耳安装在靠近端口侧

Connect the other end of the grounding 

cable to the grounding point on the rack. 

接地线另一端连接到机柜接地点

2

2

1

Mounting brackets installed near the power 

module side 

挂耳安装在靠近电源侧

Connect the other end of the grounding 

cable to the grounding point on the rack. 

接地线另一端连接到机柜接地点

2

2

1

Mount the switch in the rack (two options)

安装交换机到机柜(二选一)

2

Install cage nuts to the square 
holes on the rack posts

安装浮动螺母到机柜方孔条

Attach slide rails to the rack
posts 

安装滑道到机柜

Install cage nuts and slide rails 

安装浮动螺母与滑道

1

1

2

Connect a grounding cable to auxiliary grounding point 2 

安装接地线缆到备用接地点

2