2-9
Mounting
bracket
installation
position
Chassis dimensions
Distance
between the
front and rear
rack posts
Rack requirements
Mounting
brackets installed
near the power
supply side
•
Width
—440 mm (17.32 in)
•
Height
—88.1 mm (3.47 in)/2
RU
•
Depth
—630 mm (24.80 in)
540 mm (21.26 in) for the
chassis
92 mm (3.62 in) for the
mounting brackets
506 to 778 mm
(19.92 to 30.63 in)
IMPORTANT:
To reserve enough cabling space and close the rack door easily, make sure the rack meets the
depth requirements.
Rack-mounting procedure at a glance
Figure2-6 Rack-mounting procedure
\
NOTE:
If a rack shelf is available, you can put the switch on the rack shelf, slide the switch to an appropriate
location, and attach the switch to the rack using the mounting brackets.
Select an installation position for the
mounting brackets (near the power supply
side or port side)
Attach the mounting brackets to the switch
Attach chassis rails to the switch
Connect the grounding cable
Attach slide rails to the rack
Mount the switch in the rack