Table 6-2 Information on labels affixed to the fiber between two devices
Content
Meaning
Example
MN-B-C-D-R/T
MN
—Rack number
•
M
—Row number of the rack in the
equipment room, in the range of A to Z.
•
N
—Column number of the rack in the
equipment room, in the range of 01 to
99.
For example, A01.
B
—Chassis number
Numbered in top-down order with two digits,
for example, 01
C
—Slot number
Numbered in top-down and left-right order
with two digits, for example, 01.
D
—Fiber port number
Numbered in top-down and left-right order
with two digits, for example, 05.
R
—Optical receiving interface
T
—Optical transmitting
interface
N/A
MN-B-C-D-R/T
MN
—Rack number
The meanings are the same as above. If the
local device and the peer device are not in the
same equipment room, MN can be the name
of the equipment room.
B
—Chassis number
C
—Slot number
D
—Fiber port number
R
—Optical receiving interface
T
—Optical transmitting
interface
N/A
Figure 6-10 Example of a label on an optical fiber between two devices
A01-01-05-05-R
—The local end of the optical fiber is connected to Optical Receiving
Interface 05 on Slot 5, Chassis 01 in the rack on Row A, Column 01 in the equipment room.
G01-01-01-01-T
—The peer end of the optical fiber is connected to Optical Transmitting
Interface 01 on Slot 01, Chassis 01 in the rack on Row G, Column 01 in the equipment room
•
Labels for a fiber that connects the device and the optical distribution frame (ODF)
Table 6-3 Information on labels affixed to the fiber between the device and the ODF
Content
Meaning
Example
MN-B-C-D-R/T
MN
—Rack number
•
M
—Row number of the rack in the
equipment room, in the range of A to Z.
•
N
—Column number of the rack in the
equipment room, in the range of 01 to
99.
For example, A01.
TO:
G0
2
01
01
A 0 1
0 1
0 5
0 5
R
01
T