158
the port is still down when the detection timer expires, the port quits the shutdown status and resume its
actual physical status.
Follow these steps to configure the port status detection timer:
To do…
Use the command…
Remarks
Enter system view
system-view
—
Configure the port status detection
timer
shutdown-interval
time
Optional
The detection timer is 30 seconds
by default.
Configuring temperature thresholds for a device
You can set the temperature thresholds to monitor the temperature of a device.
The temperature thresholds include lower temperature threshold, warning temperature threshold, and
alarming temperature threshold.
•
When the device temperature drops below the lower temperature threshold, the device logs the
event and outputs a log message and a trap.
•
When the device temperature reaches the warning threshold, the device logs the event and outputs
a log message and a trap.
•
When the device temperature reaches the alarming threshold, the device logs the event and outputs
a log message and a trap repeatedly.
Follow these steps to configure temperature thresholds for an IRF member device:
To do…
Use the command…
Remarks
Enter system view
system-view
—
Configure temperature
thresholds for an IRF member
device
temperature-limit
slot
slot-number
{
hotspot
|
inflow
}
sensor-number
lowerlimit warninglimit
[
alarmlimit
]
Optional
For the default temperature thresholds,
The warning and alarming thresholds
must be higher than the lower
temperature threshold.
The alarming threshold must be higher
than the warning threshold.
Table 17
Default temperature thresholds
Device Sensor
Lower temperature
threshold
Warning
temperature
threshold
Alarming
temperature
threshold
Inflow 1
0°C (32°F)
67°C (152.6°F)
72°C (161.6°F)
S5500-34C-HI
hotspot 1
0°C (32°F)
77°C (170.6°F)
82°C (179.6°F)
Inflow 1
0°C (32°F)
59°C (138.2°F)
64°C (147.2°F)
S5500-58C-HI
hotspot 1
0°C (32°F)
74°C (165.2°F)
79°C (174.2°F)