Table 1-1 Temperature requirements 

Temperature 

Range 

Operating temperature 

0°C to 40°C (32°F to 104°F) 

Storage temperature 

–40°C to +70°C (–40°F to +158°F) 

 

Humidity 

Maintain appropriate humidity in your equipment room, as described i

Table 1-2

. 

 

Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical 
property change of materials, and metal corrosion. 

 

Lasting low relative humidity can cause washer contraction and ESD and cause problems 
including loose mounting screws and circuit failure. 

Table 1-2 Humidity requirements 

Humidity 

Range 

Operating humidity 

5% to 95%, noncondensing 

Storage humidity 

5% to 95%, noncondensing 

 

Cleanliness 

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of 
metal components and contact points.  In the worst case, electrostatic adsorption can cause 
communication failure. 

Table 1-3 Dust concentration limit in the equipment room 

Substance 

Concentration limit (particles/m

3

Dust particles 

≤ 3 x 10

4

 

(No visible dust on desk in three days) 

NOTE: 

Dust particle diameter ≥ 5 µm 

 

The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and 
premature aging of components, as shown in 

Table 1-4

. 

Table 1-4 Harmful gas limits in the equipment room 

Gas 

Max. (mg/m

3

SO

2

 

1.0 

H

2

0.5 

NH

3

 

3.0 

Cl

2

 

0.3 

 

Содержание S12500CR Series

Страница 1: ...y recommendations 1 1 Electricity safety 1 1 Handling safety 1 1 ESD prevention 1 2 Laser safety 1 2 Examining the installation site 1 2 Weight support 1 2 Temperature 1 2 Humidity 1 3 Cleanliness 1 3...

Страница 2: ...hazards such as ungrounded power extension cables missing safety grounds and wet floors Locate the emergency power off switch in the room before installation so you can quickly shut power off when an...

Страница 3: ...nts when the device has power The laser light emitted from the fiber port might hurt your eyes The device is a Class 1 laser product Examining the installation site The device must be used indoors To...

Страница 4: ...ity Range Operating humidity 5 to 95 noncondensing Storage humidity 5 to 95 noncondensing Cleanliness Dust buildup on the chassis might result in electrostatic adsorption which causes poor contact of...

Страница 5: ...evice Power Perform the following tasks to meet the power requirements 1 Calculate the system power consumption The system power consumption varies by module type and density For more information abou...

Страница 6: ...e follow these space requirements Reserve a minimum of 1 2 m 3 94 ft of clearance between the rack and walls or other devices Make sure the rack has enough space to accommodate the device For informat...

Страница 7: ...ed installation accessories Table 1 5 Installation accessories Product code Description Quantity Applicable device models 2150A0GA S12516CR mounting brackets 1 pair S12516CR 2150A0GB S12508CR mounting...

Страница 8: ...S12500CR models 2114A0D3 S12500CR front power tray filler panel 2 All S12500CR models 2114A0D4 S12500CR rear power tray filler panel 2 All S12500CR models 2114A0D1 S12516CR power input area protective...

Страница 9: ...lter 1 S12516CR 0223A1L8 S12508CR air filter 1 S12508CR 26020075 Cage nut S12516CR 28 S12508CR 20 All S12500CR models 26020141 M6 screw S12516CR 24 S12508CR 16 All S12500CR models 0404A0EE Grounding c...

Отзывы: