Cable management guidelines
When you route and bundle up cables, follow these guidelines:
•
Bind and route the cables neatly inside the rack, and make sure they are not kinked or bent.
Figure 95
Correct and incorrect cable binding
•
The cable bend radius at connectors must be a minimum of 5 times the cable diameter, and must
be a minimum of twice the cable diameter away from the connectors.
•
Route different types of cables (for example, power cords and signal cables) separately. If they are
close to one another, cross them over one another. If you route them in parallel, make sure the space
between a power cord bundle and a signal cable bundle is a minimum of 30 mm (1.18 in).
•
The cable management brackets and cable routing slots, inside or outside the rack, are smooth and
have no sharp edges or tips.
•
When you route cables through sharp sheet metal penetration points or along sharp edges of
mechanical parts, use bushings or take any other action to protect the cables from being cut or
abraded. The sheet metal penetration points must be smooth and fully rounded.
•
Use the correct type of ties to bind the cables. Do not bind cables with joined ties. The following
types of ties are available: 100 × 2.5 mm (3.94 × 0.10 in), 150 × 3.6 mm (5.91 × 0.14 in), 300 ×
3.6 mm (11.81 × 0.14 in), 530 × 9 mm (20.87 × 0.35 in), and 580 × 13 mm (22.83 × 0.51 in).
•
After binding the cables, cut the excess from the ties, leaving no sharp or angular tips. See
.
Figure 96
Cutting cable ties
Содержание S12500-X
Страница 35: ...26 Figure 20 Grounding the switch through the RTN wire of the DC power module...
Страница 80: ...71 Figure 51 Replacing an LPU 1 1 Loosen the captive screw 2 Pull the ejector levers outward...
Страница 138: ...129 Figure 75 CXP fiber cable 1 Connector 2 Pull latch 1 2...
Страница 152: ...143 Figure 91 Cable routing from the left side for an S12510 X AC S12510 X DC switch...