- SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible 

ISM0022-6 

D1021S 

INSTRUCTION MANUAL

INSTRUCTION MANUAL

 

 

SIL 2 Powered Isolating Driver with 

Fault Detection Smart-Hart compatible 

DIN-Rail Model D1021S 

Содержание d1031q

Страница 1: ...ered Isolating Driver with Fault Detection Smart Hart compatible ISM0022 6 D1021S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Powered Isolating Driver with Fault Detection Smart Hart compatible DIN Ra...

Страница 2: ...61508 for Tproof 1 3 years 10 20 of total SIF PFDavg 1 year 5 18 E 04 SFF 70 66 Output to Zone 0 Zone 20 Division 1 installation in Zone 2 Division 2 4 20 mA Input Output Signal Wide Band Smart Commun...

Страница 3: ...ce 50 K Fault signalling voltage free NE SPST optocoupled open collector transistor and voltage free NE SPST relay contact each output is de energized in fault condition Open collector rating 100 mA a...

Страница 4: ...ck connections HAZARDOUS AREA SAFE AREA Output Ch 1 for I P Converter Output Ch 1 for I P Converter Not used 13 14 15 16 Input Ch 1 for Source I 1 Input Ch 1 for Source I 2 Power Supply 24 Vdc 3 Power...

Страница 5: ...be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following va...

Страница 6: ...0 Vrms Warning D1021 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T C...

Страница 7: ...nted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detaile...

Страница 8: ...tified either by color coding preferably blue or by marking Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts Turn on power the power on green led must b...

Страница 9: ...is ON Connect the unit as shown below If the power ON Led is off check supply voltage polarity and wiring Set calibrator CAL at 4 000 mA and verify that the output current read by multimeter DMM is co...

Страница 10: ...rs are not running at the maximum current all at the same time the average power consumption of a multitude of isolators can be considered to be only 70 of the value obtained from the section Technica...