background image

Expert 

Power

 

Control NET 

8x

Manual

The eight fold socket for TCP/IP networks

Содержание Expert Power Control NET 8x

Страница 1: ...Expert Power Control NET 8x Manual The eight fold socket for TCP IP networks ...

Страница 2: ...Manual Expert Power Control NET 8x 2008 Gude Analog und Digitalsysteme Rev 2 4 ...

Страница 3: ...ation by GBL_Conf exe 5 3 3 Configuration by Webinterface 6 3 4 IP Access Control List 13 3 5 SNMP 13 3 6 Syslog 14 4 Switching 15 4 1 Switching at the device 15 4 2 Switching by Webinterface 15 4 3 Switching via Serial Interface 17 4 4 Temperature sensor 18 5 Features 19 5 1 Bootloader mode 19 5 2 Firmware update 19 5 3 Technical information 20 5 4 Default settings 20 6 Support 21 CE conformity d...

Страница 4: ... 50 or 60 Hz sockets Always plug the device into properly earthed power sockets The device is intended for indoor use only Do NOT install them in an area where excessive moisture or heat is present Because of safety and approval issues it is not allowed to modify the device without our permission Please note the safety advises and manuals of connected de vices too The device is NOT a toy It has to...

Страница 5: ...installation The connection to an elec tric circuit and a TCP IP network and the configuration of the IP settings Afterwards EPC NET 8x can be switched by all PCs of the network 1 Description 2 1 Extend of Delivery Included in delivery are Expert Power Control NET 8x for 19 Installation Power supply cable IEC CD ROM including Software and Manual Short manual 2 Hardware ...

Страница 6: ...loader mode 1 Power Port LEDs 2 TEMP interface 3 Ethernet connector RJ45 4 StatusLED 5 Buttons select and ok 6 RS232 connector 7 Power Socket IEC C20 max 16A 8 8 Power Ports IEC C13 max 10A Figure 1 Front side Figure 2 Rear side 2 2 Installation 1 Connect the power supply cable to the power socket 7 at the rear side of EPC NET 8x and a socket EPC NET 8x now is booting and shortly after ready for u...

Страница 7: ...y settings 192 168 0 2 there is either no DHCP server available in the network or no free IP address could be allocated Enter a free IP address and the according netmask in the entry mask then save these changes by clicking on Program Device gSaveConfig Restart EPC NET 8x by switching it off and on again so that the changes will take effect Now click on Search in order to have the new network conf...

Страница 8: ...ol NET 8x 6 3 3 Configuration by Webinterface Go to the website of EPC NET 8x Enter the IP address of EPC NET 8x into the address line of your internet browser http IP address of EPC NET 8x and press LOGIN Figure 4 LOGIN ...

Страница 9: ...cters can be entered here for each Power Port After power up switch The Power Port s switching state after a power on of EPC NET 8x can be defined here on off re member last state If switching on after power up wait A switching delay of a Power Port can be defined here that is applied after switch on of EPC NET 8x The delay can last up to 8191 seconds Figure 5 Configuration Power Ports ...

Страница 10: ...ou can change the netmask of EPC NET 8x Gateway Here you can change the standard gateway of EPC NET 8x Use DHCP Here you can set if EPC NET 8x shall get its TCP IP settings directly from your DHCP server If DHCP is activated EPC NET 8x proves if a DHCP server is active inside of your LAN Then EPC NET 8x requests TCP IP settings from this server If there is no DHCP server inside of your network we ...

Страница 11: ...Here you can set if EPC NET 8x shell react on pings Enable IP Filter Here you can activate the IP Access Control List IP ACL of EPC NET 8x If IP ACL is active DHCP and SNMP only work if all necessary servers and cli ents are registered in this List Figure 7 Configuration IP ACL ...

Страница 12: ...authorized to switch all ports and to modify the settings of EPC NET 8x and of all ports The username of the admin is admin Users are authorized to switch all ports but are not allowed to modify the settings of neither EPC NET 8x nor the ports The username of the user is user If you have forgotten your password activate the bootloader mode of EPC NET 8x start GBL Conf exe and deactivate the passwo...

Страница 13: ...load the MIBs of EPC NET 8x Configuration SNMP Trap Receiver List Enable Traps Here you can activate SNMP traps if enabled EPC NET 8x will dispatch SNMP traps to all receivers listed Receivers have to be listed as follows IP address and if necessary the HTTP port e g 192 168 0 2 8000 Trap Version Here you can choose between SNMP traps standard 1 and 2c Use SNMP only if your network is fitted for M...

Страница 14: ...If syslog is active enter here the IP address of you Syslog server Syslog Port If syslog is active enter here the port number that your Syslog server uses to receive syslog information More information about Syslog you can find in chapter 3 6 on http www gude info wiki or ask our support team Figure 11 Configuration Syslog ...

Страница 15: ...e used SNMP communicates via UDP port 161 with EPC NET 8x You can use SNMP to switch the power ports as well Supported SNMP commands SNMPGET request status information SNMPGETNEXT request the next status information SNMPSET EPC NET 8x request change of status You will need a Network Management System e g HP Open View OpenNMS Nagios etc or the command line tools of NET SNMP to request information o...

Страница 16: ... called Managed Objects are descripted in Management Information Bases MIBs There are three MIBs which can be requested from EPC NET 8x system interface and powerports system and interface are standardised MIBs MIB II powerports GUDEADS EPC MIB gadsEPC was created especially for EPC NET 8x At least there are so called Object Identifiers OID subordina ted to those three structures An OID describes ...

Страница 17: ...ort is selected If you want to change the switching state of the selected Power Port push the ok button for two seconds You can check the status of the Power Ports by the color of the Power Port status LED green enabled red disabled 4 2 Switching by Webinterface Go to the website of EPC NET 8x Enter the IP address of EPC NET 8x into the address line of your internet browser http IP address of EPC ...

Страница 18: ...of EPC NET 8x can be switched on or switched off for a selectable delay 1 30 sec or 1 30 min After the chosen delay the selected port will be switched off or switched on again auto matically Optionally the device can be accessed by using the pearl script EPC_Control pl through the command line e g for automatic or time triggered switching For more information please refer to our website www gude i...

Страница 19: ...e into a outlet Now you can turn on EPC NET 8x The boot process lasts a few seconds longer than by Ethernet You can access EPC NET 8x through the terminal program as soon as the status LED shines green Choose the COM port that is connected to EPC NET 8x and enter the following values for the serial interface If you do not use HyperTerminal please make sure that the terminal program supports VT100 ...

Страница 20: ... 4 Temperature sensor Connect the temperature sensor with the TEMP connector at the front of the device If it is connected exactly the recent tem perature is displayed in the login window Figure 4 and 13 in the switching window Figure 14 and can be requested via SNMP The temperature sensor can be ordered as additional supplies More information can be found at www gude info or requested at mail gud...

Страница 21: ...m window of GBL_Conf exe and by the alternately red and green blinking status led During bootloader mode an alteration of the switching state of a port is not possible 5 2 Firmware update In order to update the firmware the program GBL_Conf exe and the latest firmware are needed Start EPC NET 8x in boot mode see 4 1 and run the program GBL_Conf exe On the left side of the program window all EPC NE...

Страница 22: ...ll be loaded when EPC NET 8x is restarted the next time 5 3 Technical information Connections 1 x Ethernet RJ45 1 x Serial Interface D SUB RS232 8 x Power Ports IEC C13 max 10A 1 x Power supply inlet IEC C20 max 16A Network connection 10 MBit 10baseT Ethernet Protocols TCP IP HTTP SNMP Syslog Voltage 230 V Operating temperatur 0 C 50 C Dimensions 19 1 rack unit Weight 2 3 kg Default settings EPC N...

Страница 23: ... information current drivers and software can be found on http www gude info In case of further questions about installation or operation of EPC NET 8x please have look at www gude info wiki or do not hesitate to contact our support mail gude info ...

Страница 24: ...oltage Electrical Equipment 93 68 EWG 93 68 EEC CE Kennzeichnung CE marking und dass die nachstehenden Europäischen Normen zur Anwendung gelangt sind and comply with the following european standards Norm Titel Standard Title EN 55022 2006 A1 A2 Einrichtungen der Informationstechnik Funkstöreigenschaften Grenzwerte und Messverfahren EN 55022 2006 A1 A2 Information technology equipment Radio disturb...

Страница 25: ...23 Expert Power Control NET 8x ...

Страница 26: ...Expert Power Control NET 8x 24 Gude Analog und Digitalsysteme GmbH Eintrachtstrasse 113 50668 Koeln Tel 49 221 912 90 97 Fax 49 221 912 90 98 E Mail mail Gude info Web www Gude info CONTACT ...