59
Expert PDU Energy 8311
© 2022 GUDE Systems GmbH
Specifications
Editing
The following edit functions are available when the terminal supports VT100, and Raw
Mode is deactivated. Entered characters are inserted at the cursor position.
Keys
Function
Left, Right
moves cursor left or right
Pos1, End
moves cursor to the beginning or end of line
Del
deletes character under the cursor
Backspace
deletes character left of cursor
Up, Down
shows input lines history
Tab, Ctrl-Tab
completes the word at cursor
Ctrl-C
clears the line
Sensor Examples
a) External Sensors
>extsensor all show
E=1,L="7106",0="21.3°C",1="35.1%",3="1013hPa",4="5.2°C",5="16.0°C""
E=2,L="7102",0="21.2°C",1="35.4%",4="5.3°C",5="15.9°C""
The command lists one connected external sensor per line, and the individual measured
values are separated by commas after the label name. The digit before the equal sign
corresponds to the Index field in the External Sensor Table.
>extsensor 1 0 value show
Displays temperature of the sensor at Port 1
b) Line Sensors
>linesensor all "0,1,2,3,12" show
L=1,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
L=2,L="Power Port",0="13000Wh",1="0W",2="223V",3="0A",12="996199s"
This command outputs all line sensor values in one line. A list of all fields (according to
the energy sensor table) is transferred as parameter. In this example these are the fields
Absolute Active Energy (0), Power Active (1), Voltage (2), Current (3) and Reset Time
(12).
>linesensor 1
"0,1,2,3,12"
show
>linesensor 1 1 show
These variants give the sensor values of the field list or of a sensor at Line-In 1.
For devices with Overvoltage Protection, the "linesensor all" command also outputs
the state of the protection ("OVP=x"). A "1" means ok, a "0" a failure of the protection.
c) Port Sensors
Содержание 8311-1
Страница 1: ...Expert PDU Energy 8311 Series Manual 2022 GUDE Systems GmbH Manual Ver 1 5 1 from Firmware Ver 1 5...
Страница 2: ...2 Expert PDU Energy 8311 2022 GUDESystems GmbH...
Страница 5: ...Device Description...
Страница 11: ...11 Expert PDU Energy 8311 2022 GUDESystems GmbH Device Description...
Страница 12: ...Operating...
Страница 22: ...Configuration...
Страница 45: ...Specifications...
Страница 80: ...Support...
Страница 85: ...85 Expert PDU Energy 8311 2022 GUDESystems GmbH Index Timer 35 Timer Configuration 35 TLS 54...
Страница 86: ...86 Expert PDU Energy 8311 2022 GUDESystems GmbH Expert PDU Energy 8311 2022 GUDE Systems GmbH 3 16 2022...