Device Description
·
21 Power Ports individually switchable directly on the device, via HTTP(S) (TLS 1.2 +
1.3), SNMP (v1, v2c and v3), Modbus TCP
·
Command line tool via Telnet, SSH and RS232 serial interface
·
Control and configuration with CGI parameters and JSON messages via HTTP (REST
API)
·
Integrated failure-proof power supply unit (max. 300 W)
·
Power monitoring of 5 V, 12 V and 24 V (Bank A-D)
·
Maximum available DC current per port: max. 4 A
·
Current segmentation per bank: 5 V: max. 8,8 A, 12 V: max. 6 A, 24 V: max. 12,5 A
·
Switching through programmable sensor thresholds
·
Scheduled and event-based switching
·
Self-healing feature: An individual watchdog (ICMP/TCP) for each Power Port automat-
ically reboots in case of lock-up
·
Generation of messages (E-Mail, Syslog and SNMP traps) and relay switching de-
pending on the energy measurement limits, resp. external sensors
·
Dual TCP/IP Stack with IPv4 and IPv6 support
·
AC: Metering of energy, current, power factor, phase angle, frequency, voltage and
active / apparent / reactive power
·
AC: Residual current metering type A
·
A clearly visible LED display for port status, total current,
·
Integrated overvoltage protection (SPD) type 3
·
Each outlet protected by eFuses in case of short circuits
·
2 interfaces for optional sensors for environmental monitoring (temperature, humidity
and air pressure)
·
RJ45 network connection and RS232 interface
·
IPv6, SNMPv3, Telnet, Radius, ModbusTCP
·
HTTP/HTTPS, e-mail (SSL, STARTTLS), DHCP, Syslog
·
Access control via IP Access Control List
·
Low internal power consumption
·
Developed and manufactured in Germany
1.4
Installation
Anzeige pro Bank
1. LED indicators (5V, 12V, 24V, 230V) for bank voltage display
2. LED indicator (flash) for Over Voltage Protection (green - surge protection is active,
red - inactive)
3. 21 plain text displays (on/off) for the state of the outputs (Bank A to Bank E)
4. 2 x 7-segment display for measured values
5. Status LED
Содержание Expert Power Control 8291
Страница 1: ...Manual 2020 GUDE Systems GmbH Manual Ver 1 0 1 from Firmware Ver 1 0 Expert Power Control 8291 ...
Страница 2: ...2 Expert Power Control 8291 2020 GUDESystems GmbH ...
Страница 5: ...Device Description ...
Страница 16: ...Operating ...
Страница 26: ...Configuration ...
Страница 52: ...Specifications ...
Страница 85: ...Support ...