background image

APPLICATION
& ENGINEERING DATA

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with 
BS5514, ISO3046 and DIN6271).  (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

60 kW

GENERATOR SPECIFICATIONS

TYPE ...........................................................................................................Synchronous
ROTOR INSULATION ..........................................................................................Class H
STATOR INSULATION .........................................................................................Class H
TOTAL HARMONIC DISTORTION ........................................................................... <5%
TELEPHONE INTERFERENCE FACTOR (TIF) ........................................................<50
ALTERNATOR OUTPUT LEADS 3 PHASE ...........................................................4 wire
BEARINGS .................................................................................................... Sealed Ball
COUPLING .................................................................................................. Flexible Disc
LOAD CAPACITY (STANDBY RATING) ................................................................ 60 kW
EXCITATION SYSTEM ........................................................................................... Direct

NOTE:    Generator  rating  and  performance  in  accordance  with 
ISO8528-5,  BS5514,  SAE  J1349,  ISO3046,  and  DIN6271  standards.

GENERATOR FEATURES

 

Revolving field heavy duty generator

 

Directly connected to the engine

 

Operating temperature rise 120 °C above a 40 °C ambient

 

Insulation is Class H rated at 150 °C rise

 

All models are fully prototyped tested

VOLTAGE REGULATOR

TYPE ................................................................................................................Electronic
SENSING ................................................................................................... Single Phase
REGULATION .......................................................................................................... ± 1%
FEATURES ............................................................................................... V/F Adjustable
 

Adjustable Voltage and Gain

LED Indicators

CONTROL PANEL FEATURES

 

SEVEN LED INDICATOR LIGHTS    

ADDITIONAL FUNCTIONS

    • System ready 

• Utility sensing

    • Low fuel pressure 

• Delay on utility failure for engine start

    • Low battery 

• Engine warm-up before transfer

    • Low oil pressure 

• Delay to retransfer to utility

    • High coolant temp/low coolant temp 

• Engine cooldown timer

    • Overspeed 

• Exerciser not set

    • Overcrank 

• Hour meter

 

INTERNAL FUNCTIONS:

    • 3 position switch (auto, off and manual)
    • 2 wire start for any transfer switch
    • Communicates with the Generac RTS transfer switch
    • Built-in 7 day exerciser
    • Selectable engine speed at exercise
    • Governor controller is built into the master control board
    • Temperature range -40 °

C to 70 °C

ENGINE SPECIFICATIONS

MAKE ................................................................................................................ Generac
MODEL ................................................................................................................2.4 Liter
CYLINDERS .........................................................................................................Inline 4
DISPLACEMENT .................................................................................................2.4 Liter
BORE ........................................................................................................................3.41
STROKE ....................................................................................................................3.94
COMPRESSION RATIO ...........................................................................................8.5:1
INTAKE AIR SYSTEM .............................................................Turbocharged/Aftercooled
VALVE SEATS ..................................................................................................Hardened
LIFTER TYPE ....................................................................................................Hydraulic

GOVERNOR SPECIFICATIONS

TYPE ................................................................................................................Electronic
FREQUENCY REGULATION ....................................................................± Isochronous
STEADY STATE REGULATION .......................................................................... ± 0.25%
ADJUSTMENTS FOR:
 

Speed .....................................................................................................Yes

 

Droop ......................................................................................................Yes

ENGINE LUBRICATION SYSTEM

OIL PUMP ................................................................................................................Gear
OIL FILTER ............................................................................. Full flow spin-on cartridge
CRANKCASE CAPACITY ...................................................................................4 Quarts

ENGINE COOLING SYSTEM

TYPE .....................................................................................................................Closed
WATER PUMP .................................................................................................Belt driven
FAN SPEED .............................................................................................................2100
FAN DIAMETER ............................................................................................... 22 inches
FAN MODE ..............................................................................................................Puller           

FUEL SYSTEM

FUEL TYPE ..........................................................................Natural gas, propane vapor
CARBURETOR...............................................................................................Down Draft
SECONDARY FUEL REGULATOR ................................................................... Standard
FUEL SHUT OFF SOLENOID .......................................................................... Standard
OPERATING FUEL PRESSURE ..................................................................5” - 14” H2O

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR .............................................................12V 30 Amp
STATIC BATTERY CHARGER .............................................................................. 2 Amp
RECOMMENDED BATTERY .......................................................... Group 24F, 525CCA
SYSTEM VOLTAGE .............................................................................................12 Volts

Содержание 05649

Страница 1: ...tor Sets Standby Power Rating 60 kW 60 Hz Turbocharged Aftercooled Gaseous Fueled Innovative design and fully prototype tested UL2200 Listed Solid state frequency compensated voltage regulator Dynamic and static battery charger Sound attenuated acoustically designed enclosure Quiet test for low noise level exercise Acoustically designed engine cooling system High flow low noise factory engineered ...

Страница 2: ... on utility failure for engine start Low battery Engine warm up before transfer Low oil pressure Delay to retransfer to utility High coolant temp low coolant temp Engine cooldown timer Overspeed Exerciser not set Overcrank Hour meter INTERNAL FUNCTIONS 3 position switch auto off and manual 2 wire start for any transfer switch Communicates with the Generac RTS transfer switch Built in 7 day exercis...

Страница 3: ... power 60 Hz cfm 180 SOUND EMISSIONS IN DBA Exercising at 7 meters 65 Normal operation at 7 meters 72 EXHAUST Exhaust flow at rated output 60 Hz cfm 494 Exhaust temp at muffler outlet F 1 050 ENGINE PARAMETERS Rated synchronous RPM 60 Hz 3600 HP at rated KW 60 Hz 94 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3 for every 10 C above C 25 1 65 for every 10 F above F 77 Altitude Dera...

Страница 4: ... INSTALLATION LAYOUT Installation Drawing Ref No 0F9577 Generac Power Systems Inc P O Box 8 Waukesha WI 53187 generac com 2008 Generac Power Systems Inc All rights reserved All specifications are subject to change without notice Bulletin 0178490SBY Printed in U S A 06 08 rev 10 08 WEIGHT 1650 lbs ...