30304411                                                                                                                                                                  Issue 3.03

 

                                       

 

 

Features 

 

A  pair  of  output  contacts,  open  in  normal  state, 
close all the time when alarming. 

 

Built-in  microprocessor  collects  and  processes 
data in real time. 

 

Rate of rise and fixed temperature alarm modes. 

Description 

R6602 Conventional Heat Detector is non-addressable. 

With built-in microprocessor, it's fixed with high reliable 

fire judging program and works stably. 

The  sensor  is  NTC  thermistor;  the  resistance  of  the 

thermistor  reduces  with  the  rise  of  temperature. 

Amplified  output  signal  is  A/D  transformed  by 

microprocessor, 

which 

processes 

the 

rise 

of 

temperature and its volume after calculated by special 

arithmetic.  When  it  overpasses  the  alarm  threshold, 

output control signal  drives  the relay  to  act,  and lights 

the indicator. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 the base.

 

C

D

3 0 - Z

Mounting Hole

 

Fig. 1                                          Fig. 2 

 

There  are  four  conducting  pieces  on  the  base,  each 

carrying  a  terminal  with  number.  Terminal 

“2”  and  “4” 

are  connected  with the  power,  polarity-insensitive. 

“1”, 

“3” connects with relay output. 

Recommended Cabling 

Adopt  1.0mm

2

  or  above  fire  cable,  subject  to  local 

codes. 

 

 

 

 

 

 

 

 

 

 

Installation 

A  fixed  installation  direction is  ensured  by  the  location 

elements  on  the  detector  and  the  base.  Fix  the  base 

with two tapping screws, and then align mark C on the 

detector with A on the base, rotate the detector to align 

mark  C  with  mark  B  (Refer  to  Fig.  1  and  2  for  the 

position of the marks), the detector will be fitted to the 

base.

 

Fig. 3 shows the mounting of the detector.

 

Detector

Conduit

Back Box

Base

 

Fig. 3 

Application 

The  detector  is  applicable  to  hotels,  warehouses.  It 
can work when connected to 12VDC power. 

 

 

 

 

R6602 

  Conventional Heat Detector 

 

 