Working Mode Setup
In standby state of the programmer, pressing
Function
and enter number 4,
“-” will show on the last digit.
Input the number of corresponding working mode, and
pressing
Program,
“
P
” will show on the screen,
meaning the mode has been set. The factory default is
Mode 1 (102), which can be changed to Mode II (103
or any number between 1 to 240 except 102) in field.
Before installation, the sounder base should be
programmed, and the mode is to be confirmed.
Application Method
The sounder base can be used as a detector base
to mount intelligent detectors, so that the detector
can carry out both fire detection and alarm.
The sounder base can also be directly connected
into fire alarm system. In case of a fire alarm, it will
generate alarm sound according to the cause and
effect setup of the system. System connection is
shown in Fig. 5.
Fig. 5
Caution
Please read this manual before operation.
A loop can have maximum 40 sounder bases
because of their heavy current consumption.
Order the special top cover if not connected
with fire detector.
Never try to repair it by yourself. Always contact
your distributor in case of any trouble.
Specifications
Operating Voltage
Loop 24V
Quiescent Current
≤
1mA
Alarm Current
≤
5mA
Sound Level
≥
85dB (1m ahead
horizontally (A weighted))
Mode
Mode I & II.
Type of Alarm Signal Pre-alarm: 0.5s on 1s off
Fire Alarm: 0.4s on, 0.3s off
Programming
Electronically programmed
Code Range
1~242 when occupying one
address; 1~241 when
occupying two addresses.
Ingress Protection
Rating
IP31
Operating
Temperature
-
10
℃~+
50
℃
Relative Humidity
≤
95%, non condensing
Material of
Enclosure
ABS
Dimension
Diameter: 151mm
Height: 35.4mm (without
cover)
Weight
About 136g
Accessories and Tools
Model
Name
Remarks
P-9910B
Hand Held
Programmer
Order separately
Limited Warranty
GST
warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.
Mode
Number of Address
Type of Alarm
I
Two addresses. The
lower code occupies an
address, and the higher
code shares the
address of cooperated
detector.
Lower address
:
Fire alarm
Higher address
:
Pre-alarm
II
Occupies one address
Fire
GST China
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
Fax: +86 (0) 335 8508942
[email protected]
www.gst.com.cn
GST UK
Global System Technology PLC
Lion Court, Staunton Harold Hall,
Melbourne Road, Ashby de la Zouch,
Leicestershire, England LE65 1RT
Tel: +44 1283 225 478
Fax: +44 1283 220 690
[email protected]
www.gst.uk.com
GST Dubai
Global System Technology PLC
PO Box 17998 Unit ZA04
JEBEL ALI Free Zone,
Dubai, UAE
Tel: +971 (0) 4 8833050
Fax: +971 (0) 4 8833053
[email protected]
www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.