el

Working Mode Setup

 

In standby state of the programmer, pressing 

Function

 

and  enter  number  4, 

“-”  will  show  on  the  last  digit. 

Input the number of corresponding working mode, and 
pressing 

Program, 

P

”  will  show  on  the  screen, 

meaning the mode has been set. The factory default is 
Mode 1 (102), which can be changed to Mode II (103 
or any number between 1 to 240 except 102) in field. 
Before  installation,  the  sounder  base  should  be 
programmed, and the mode is to be confirmed. 

Application Method 

  The sounder base can be used as a detector base 

to  mount  intelligent  detectors,  so  that  the  detector 
can carry out both fire detection and alarm.

 

  The  sounder  base  can  also  be  directly  connected 

into fire alarm system. In case of a fire alarm, it will 
generate  alarm  sound  according  to  the  cause  and 
effect  setup  of  the  system.  System  connection  is 
shown in Fig. 5. 

 

 

 

 

 

Fig. 5   

Caution 

  Please read this manual before operation.

 

  A  loop  can  have  maximum  40  sounder  bases 

because of their heavy current consumption.   

  Order  the  special  top  cover  if  not  connected 

with fire detector.

 

  Never try to repair it by yourself. Always contact 

your distributor in case of any trouble.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Specifications 

Operating Voltage 

Loop 24V 

Quiescent Current 

1mA 

Alarm Current 

5mA 

Sound Level 

85dB (1m ahead 

horizontally (A weighted)) 

Mode 

Mode I & II.   

Type of Alarm Signal  Pre-alarm: 0.5s on 1s off 

Fire Alarm: 0.4s on, 0.3s off 

Programming 

Electronically programmed 

Code Range 

1~242 when occupying one 
address; 1~241 when 
occupying two addresses. 

Ingress Protection 
Rating 

IP31 

Operating 
Temperature 

-

10

℃~+

50

 

Relative Humidity 

95%, non condensing 

Material of 
Enclosure 

ABS 

Dimension 

Diameter: 151mm 
Height: 35.4mm (without 
cover) 

Weight   

About 136g 

Accessories and Tools

 

Model 

Name 

Remarks 

P-9910B 

Hand Held 
Programmer 

Order separately   

Limited Warranty   

GST

 warrants that the product will be free from defects 

in  design,  materials  and  workmanship  during  the 
warranty  period.  This  warranty  shall  not  apply  to  any 
product that is found to have been improperly installed 
or  used  in  any  way  not  in  accordance  with  the 
instructions  supplied  with  the  product.  Anybody, 
including the agents, distributors or employees, is not 
in the position to amend the contents of this warranty. 
Please  contact  your  local  distributor  for  products  not 
covered by this warranty.

 

 

 

 

 

Mode 

Number of Address 

Type of Alarm 

I

 

Two addresses. The 
lower code occupies an 
address, and the higher 
code shares the 
address of cooperated 
detector.   

Lower address

:   

Fire alarm 

Higher address

Pre-alarm

 

II

 

Occupies one address 

Fire

 

GST China 
Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, 
QETDZ, Qinhuangdao, Hebei,   
P. R. China 066004 
Tel: +86 (0) 335 8502528     
Fax: +86 (0) 335 8508942 

   

[email protected] 
www.gst.com.cn 

GST UK 
Global System Technology PLC 

Lion Court, Staunton Harold Hall,   
Melbourne Road, Ashby de la Zouch,   
Leicestershire, England LE65 1RT 
Tel: +44 1283 225 478 
Fax: +44 1283 220 690 
[email protected]   
www.gst.uk.com 
 

GST Dubai 
Global System Technology PLC 

PO Box 17998 Unit ZA04   
JEBEL ALI Free Zone,   
Dubai, UAE 
Tel: +971 (0) 4 8833050     
Fax: +971 (0) 4 8833053 
[email protected]   
www.gst.uk.com 

This document is subject to change without notice. Please contact GST for more information or questions. 

Отзывы: