30307233                                                                                                                                                                    Issue 1.02

 

                                       

 

Features 

  Electronically  addressed.  The  address  can  be 

modified in field. 

  Built-in  microprocessor,  processing  information 

intelligently. 

  Two working modes (Mode I, II) available.   

  Installed on detector base, easy for installation and 

removal without additional wiring. 

Description 

I-9405  Addressable  Sounder  base  is  a  base  with  an 
integrated  buzzer.  When  there  is  a  confirmed  fire,  it 
will give audible alarm signal to warn people in field. 
With  a  built-in  microprocessor,  the  sounder  base  can 
communicate with fire alarm control panel (FACP). On 
receiving  a  start  command  from  the  FACP,  the 
microprocessor  will  control  the  buzzer  to  generate 
pre-alarm or fire alarm sound according to the pre-set 
working mode.

 

Wiring and Connection 

Terminals of the sounder base are shown in Fig. 1. 

 

Fig. 1 Terminals of Sounder Base 

Z1(1), Z2(3): Signal loop of FACP, polarity-insensitive.   

Recommended Wiring 

1.0mm

2

 or above fire cable, subject to local codes. 

Installation 

Warning:  Before  installing  the  sounder  base, 
disconnect the power from the loop and verify that 
all the bases are securely fixed and that the wiring 
is correct on each base. 

1  Before installation, make sure the enclosure is free 

of scratch or distortion, and labels are complete.   

2  Mounting of the sounder base is shown in Fig. 2.   

3  Secure the sounder base to detector base (Fig. 4) 

with  2  tapping  screws,  and  wire  them  properly. 

Align the orientation mark C on the sounder base 

to mark A of the base, and rotate the sounder base 

clockwise to B. Refer to Fig. 3 and 4. 

4  If the sounder base comes with a cover, align the 

orientation  mark  on  the  cover  to  mark  A    of  the 

sounder  base  (Fig.1),  and  rotate  the  cover 

clockwise  to  B.  If  it's  used  as  detector  base, 

remove the cover and install the detector on it with 

the same method. 

 

Base

Sounder Base

Cover or detector

Electric box

 

Fig. 2 Mounting of Sounder Base 

1

2

3

4

 

Fig. 3 Sounder Base   

DZ

-0

3

 

Fig. 4 Base

 

Application 

The  sounder  base  can  be  used  as  the  base  of 
intelligent  heat  and  smoke  detectors  to  combine 
detection  and  alarm  in  a  single  device.  It  can  be 
connected  to  the  loop  of  FACP  without  additional 
power supply. 

Programming 

The  sounder  base  can  be  programmed  using 
DR-P910B  programmer  in  field.  Connect  the 
programmer  with  Terminal  1  and  3  of  the  sounder 
base.  When  the  sounder  base  occupies  two 
addresses,  only  the  lower  address  (fire  alarm  sound) 
needs  to  be  programmed,  and  the  higher  address 
(pre-alarm)  will  be  automatically  programmed  by 
adding 1 to the lower address. Refer to 

P-9910B Hand 

Held  Programmer  Installation  and  Operation  Manual

 

for details. 

  The Intelligent Solution 

 

    I-9405

 

Addressable Sounder Base

 