Features 

 

Twin LED for 360° view. 

 

Electronically addressed in field. 

 

Built-in microprocessor stores 14 history data. 

 

Drift compensation to suit environment changing 
extensively. 

 

Self-diagnostic. 

 

Remote indicator output available. 

 

Complies with EN 54-7 standard. 

Description 

I-9102  Intelligent  Photoelectric  Smoke  Detector  is  an 
addressable  fire  alarm  device  cooperating  with  GST 
intelligent  fire  alarm  control  panels  to  build  a  fire 
detection  system.  It  shows  fire  alarm  by  LED 
indicators  and  transmits  the  fire  signal  to  the  control 
panel. Using infrared scattering technology, the smoke 
density  can  be  detected.  The  detector  receives  very 
weak infrared light under normal smokeless condition. 
If smoke particles enter the chamber, the received light 
signal will increase by scattering. When smoke density 
reaches a pre-set level, the detector will alarm out. In 
order to reduce interference and power  consumption, 
the emitting circuit works in pulse mode to prolong the 
life of IR LED. 

Connection and Cabling 

Fig.1 shows the detector bottom and Fig. 2

 

the base.   

100mm

C

25mm

5mm

03mm

45mm~75mm

Mounting 
Hole

Z-0

3

D

       

Fig. 1                                              Fig. 2

 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 

2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

Recommended Cabling 

1.0mm

2

  or  above  fire  cable  is  recommended  but 

subject to local codes.   

Installation 

A fixed installation direction is ensured by the location 
elements  on the  detector  and  the  base.  Fix  the  base 
with two tapping screws, and then align mark C on the 
detector with A on the base, rotate the detector to align 
mark  C  with  mark  B  (Refer  to  Fig.  1  and  2  for  the 
position of the marks), the detector will be fitted to the 
base. 

Note: The detector shall be horizontally installed. If 
it  has  to  be  installed  on  an  inclined  plane,  the 
inclination angle shall not be over 45

º

.   

 

Fig. 3 shows the installation of the detector. 

Conduit

Detector

 Base

Back Box

 

Fig. 3 

Application 

The  detector  is  suitable  for restaurants,  hotels,  office 
buildings,  school  buildings,  banks,  warehouses, 
libraries, computer rooms, power plants, etc. 

The  detector  can  be  addressed  in  field  by  using 
P-9910B programmer.  Please refer to 

P-9910B Hand 

Held  Programmer  Installation  and  Operation  Manual

 

for details. 

Maintenance 

The  detector  should  be  installed  just  before 
commission  and  kept  well  before  installation, 
taken  corresponding  measures  for  dust-proof, 
damp-proof and corrosion-proof. 

The dust-proof cover should not be removed until 
the project plunged into usage. Otherwise it may 
not report alarm properly.

 

Clean the detectors regularly, at least once a year 
to ensure normal operation of the system.

 

Maintenance should be carried out for false alarm 
detectors,  either  clean  or replace  the  chamber  if 
necessary.    Before  cleaning,  notify  the  proper 
authorities that the system is under maintenance 
and will temporarily be out of service. Disable the 
automatic controls relating to the  zone or system 
under maintenance to avoid unwanted actions. 

Steps for chamber cleaning: 

a) 

Open the top cover of detector. 

b) 

Draw  out  the  chamber  slightly  shaking  by 
hand. 

c) 

Clean  the  internal  of  the  chamber  by 
alcohol  cotton  or  other  clean  liquid  swab 
with  tweezers.  Make sure not to leave any 

I-9102 

  Intelligent Photoelectric Smoke Detector 

 