background image

 

30307848 

                               

                                                                                                  Issue 1.01

 

                                       

 

 

Features 

 

Electronically addressed. 

 

Built-in microprocessor stores 14 history data. 

 

Drift compensation to suit environment changing 

extensively. 

 

Combined  smoke  and  heat  algorithm  greatly     

improves detector performance. 

 

Self-diagnostic. 

 

Removable innovative sensing chamber, easy for             

maintenance. 

 

Reporting dirt fault for contaminated chamber.

 

 

Remote indicator output available.

 

  Designed  to  comply  with  EN  54-5/EN  54-7 

standards. 

Description 

I-9101  Intelligent  Combination  Heat/Photoelectric 

Smoke Detector integrates photoelectric detection and 

fixed temperature and rate of rise detection technology 

by  combining  smoke  sensor  and  heat  sensor  in 

mechanism and circuitry structure. Just because of the 

combination  of  smoke  detection  and  heat  detection, 

I-9101  detector  not  only  overcomes  the  disadvantage 

that  detectors  using  common  infrared  scattering 

technology  are  insensitive  to  black  smoke  with  small 

particles,  but  also  can  pick  up  fire  with  obvious  rise  of 

temperature  such  as  alcohol  flame,  thus  extending  its 

application range. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 the base. 

100mm

C

25mm

5mm

03mm

45mm~75mm

Mounting 
Hole

Z-0

3

D

 

Fig.1                                          Fig.2 

 

There are four terminals with numbers on the base.   

1&3: Loop connection (non-polarized) 

2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

   

 

 

 

Recommended Cabling 

1.0 mm

or above fire cable for detector loop, laid out 

through  metal  conduit  or  flame-retardant  conduit. 

Subject to local codes. 

Installation 

A fixed installation direction is ensured by the location 

elements  on  the  detector  and  the  base.  Fix  the  base 

with two tapping screws, and then align mark C on the 

detector with A on the base, rotate the detector to align 

mark  C  with  mark  B  (Refer  to  Fig.  1  and  2  for  the 

position of the marks), the detector will be fitted to the 

base. 

Mounting of the detector is shown in Fig. 3. 

 

Conduit

Detector

Base

Back Box

 

Fig.3 

Application 

The  detector  can  be  electronically  addressed  by  a 
programmer.  Please  refer  to 

P-9910B  Hand  Held 

Programmer  Installation  and  Operation  Manual 

for 

details.   
 

The Intelligent Solution 

I-9101 Intelligent Combination     

Heat/Photoelectric Smoke Detector

 

Отзывы: