background image

 

30307213                                                                                                                                                                    Issue 1.02

 

Specification 

Operating Voltage 

Addressable Mode:   
Loop voltage: 24V 
Ranged: 16V~28V 
Non-addressable Mode: 
Voltage: 24VDC 
Ranged: 20VDC~28VDC 

Operating Current 

Addressable Mode: 
Standby current 

≤ 2mA 

Alarm current 

≤ 3mA 

Non-addressable Mode: 
Standby current 

≤ 13mA 

Alarm current 

≤ 23mA 

Power-up Time 

≤10s 

Indicator 

Red. 

It 

flashes 

when 

polling, 

and 

illuminates 

steadily in alarm. 

Programming Mode      Electronic 

programming. 

Occupying 

one 

loop 

address. 

Address Range 

1

242 

Spectrum Response 
Range   

185nm

260nm 

Detection Angle 

 
 
 
 
 
 
 

Detection 
Distance

 

25m for Level I, 17m for 
Level II and 12m for Level 
III. 

Ingress Protection 

IP66 

Ambient 
Temperature 

20

℃~+

60

 

Relative Humidity 

≤95%RH, non-condensing 

Dimensions 

147mm×106mm×92mm 

Material and Color 

ZL102 aluminum alloy, 
silvery grey. 

Weight 

1.5kg 

Installation Hole 
Spacing 

110mm×72mm 

Explosion-proof 
Mark 

Ex d

CT6 

Test  fire:  The  flame  generated  by  2000g  of  alcohol 

in  a  container  with  bottom  area  33cm×33cm  and 
height 5cm. 

 

 

 

 

 

 

 

 

 

 

Accessories and Tools 

Name and Model 

Qty.  Remarks 

P-9910B Hand Held 
Programmer

 

Order separately   

Expansion Bolt M6×60 

 

Screws M3×16 

 

Maintenance 

(1) The detector shall be cleaned at lease once a year 

to ensure normal operation of the system. 

(2) Before  cleaning,  notify  the  proper  authorities  that 

the  system  is  undergoing  maintenance  and  will 
temporarily be out of service. Disable the zone or 
system 

undergoing 

maintenance 

to 

avoid 

unwanted alarms. 

(3) The  detector  shall  be  tested  after  being  cleaned 

and  re-installed.  After  testing,  notify  the  proper 
authorities the system is back in operation. 

Caution 

(1) The  detector  should  be  handled  with  care  during 

storage,  transportation,  installation,  commission 
and  maintenance  to  avoid  damage  from  falling, 
impact, outside force and friction . 

(2) Installation and maintenance should strictly comply 

with  relative  codes  for  explosive  and  hazardous 
areas. 

(3) Never open the cover for maintenance in field. 
(4) The enclosure must be earthed. 
(5) The  following  places  are  not  suitable  for  the 

detector: 

 Where flameless fire is to be expected. 

 Where intensive smoke spreads before flames. 

 Where  the  "view"  of  the  detector  is  opt  to  be 

obscured. 

 Where the sun can directly shine the detection 

window. 

 Where  there  is  strong  UV  light  source  in  field, 

like a tungsten halogen lamp.   

 Where open fire, welding, X rays, arc or sparks 

may exist in normal condition.   

Limited Warranty   

GST warrants that the product will be free from defects 
in  design,  materials  and  workmanship  during  the 
warranty  period.  This  warranty  shall  not apply to any 
product that is found to have been improperly installed 
or  used  in  any  way  not  in  accordance  with  the 
instructions  supplied  with  the  product.    Anybody, 
including the agents, distributors or employees, is not 
in the position to amend the contents of this warranty. 
Please  contact  your  local  distributor  for  products  not 
covered by this warranty. 

 

 

 

 

 

 

 

 

 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 

Отзывы: