background image

 

30309581

           

                                                                                   

       

                                          Issue 1.08

 

                                       

 

Features 

 

Reed switch testing.   

 

Remote indicator output available.   

 

2  levels  smoke  sensitivities  programmable,  complies  with     
UL268. Heat part is fixed temperature, complies with UL521. 

Description 

DC-M9101  Conventional  Combination  Heat  Photoelectric  Smoke 
Detector  integrates  photoelectric  detection  and  fixed  temperature 
detection 

technology 

by 

combining 

smoke 

sensor 

and 

semi-conductor  heat  sensor  in  mechanism  and  circuitry  structure. 
Just  because  of  the  combination  of  smoke  detection  and  heat 
detection,  it  not  only  overcomes  the  disadvantage  that  detectors 
using  common  infrared  scattering  technology  are  insensitive  to 
black  smoke  with  small  particles,  but  also  can  pick  up  fire  with 
obvious  rise  of  temperature  such  as  alcohol  flame,  thus  extending 
its application range. 

On detecting  a fire signal, it can change its own current to transmit 
the  signal  to  fire  alarm  control  panel  (FACP)  or  addressable  zone 
monitor unit. The detector keeps illuminating fire LED until it is reset 
by power-down. 

Connection and Cabling 

The  detector  connects  with  UL-certified  products  such  as  I-M9300 
module and intelligent control panels. The detector bottom is shown 
in Fig. 1 and the base in Fig. 2. 

5

45

75

Cable Entry

Mounting

Hole

 

Fig. 1                              Fig. 2 

Please install the base according to following steps: 
1) 

Locate  mounting  holes  on  the  rubber  layer  of  the  base 
according to the holes on the back box, and punch the holes 
with a screwdriver. 

2) 

Count  the  number  of  cables  needed  and  punch  correct 
quantity  of  holes  with  a  screwdriver  on  the  rubber  layer. 
Thread the cables through the cable entry holes.   

3) 

Install the base onto the back box with screws. 

Warning:  Do  not  punch  mounting  holes  and  cable  entry  holes 
bigger than needed. Do not punch more holes than needed.

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 
2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator

   

It connects a 4.7k/1w resistor between number 2 and 3 at the end 
of the base. The system connection is shown in Fig. 3.   

Remote Indicator

O

-

O

+

I-M9300

Conventional Detector

4.7

k
Ω

 

Res

istor

Remote Indicator

Conventional Detector

 

Fig. 3 

Recommended Cabling 

1.0mm

2

 or  above  fire cable is  recommended, laid through metal  or 

flame-retardant  conduit,  but  subject  to  local  codes.  Different  color 
cables for remote indicator are used to avoid wiring mistake. 
I-M9300 modules connect with 15 conventional devices at most.     

Note:  It

’s  recommended  to  use  cables  of  different  colors  to 

avoid incorrect wiring.

 

 

Installation 

Refer  to 

D  Series  Detector  Application  Bulletin 

for  additional 

installation instructions. 
A fixed installation direction is  ensured by the  location  elements  on 
the  detector  and  the  base.  Fix  the  base  with  two  tapping  screws, 
and then align mark A on the detector with B on the base, rotate the 
detector to  align mark A with mark  C (Refer to Fig. 1  and  2 for the 
position of the marks), the detector will be fitted to the base. 

Fig. 4 shows the installation of the detector. 

54.5mm

Electrical Box

Conduit

Base

Detector

 

 

Fig. 4 

Application 

Warning: The alarm current depends on the  current 
limit  of  the  control  panel.  24VDC  cannot  power  the 
detector  directly.  Otherwise  the  detector  will  be 
blown up for lack of current limit resistor. 

Fixed  temperature  and  level  2  are  default.  Sensitivity  level  of  the 
detector  can  be  set,  read  or  written  in  field  by  using  P-9910B 
programmer. 

In  power-on  state,  input  unlocking  password  and  press 

Clear

  to 

unlock. Press 

Function

, then press “3”, the screen shows “_” at the 

last digit.   

Input corresponding sensitivity or parameter and press 

Program

, the 

screen will show a “P”, the corresponding sensitivity or parameter is 
programmed.  Press 

Clear

  to  clear  the  "P".  Input  locking  password 

and press 

Clear

 to return. 

Parameters set using programmer 

Input  Parameter 
of a Detector 

Smoke 
Sensitivity 

Heat Part 

Fixed   

Fixed 

Read Sensitivity Level: in power-on state, pressing 

Test, the

 screen 

displays  address  of  the  detector.  Pressing 

Up”,

  display  sensitivity 

level, device type and initial sensitivity in turns.   

Testing 

Before  testing,  please  ensure  that  the  detector  has  been 
installed  correctly  and  powered  up.  After  10  seconds,  testing 
begins. 

Before testing, notify the proper authorities that the system is under 
maintenance  and  will  temporarily  be  out  of  service.  Disable  the 
automatic  controls  relating  to  the  zone  or  system  under 
maintenance to avoid unwanted actions. 

All  detectors  must  be  tested  after  installation  and  periodically 
thereafter.  Testing  methods  must  satisfy  the  Authority  Having 
Jurisdiction  (AHJ).  Detectors  offer  maximum  performance  when 
tested  and  maintained  in  compliance  with  NFPA  72.  The  detector 
can be tested in the following way: 