background image

 

30309767                                                                                                                                                                    Issue 1.04

 

Cautions 

1

  I-9333  Interface  should  be  installed  in  safety 

area,  the  wires  of  "Safety  Area"  should  be 

separated from those of "Hazardous Area", and 

be kept a certain distance (at least 50mm). 

 

2

  The  safety  barrier  should  be  well  grounded. 

The  screws  should  not  be  loose.  Ground 

resistance  should  not  be  over  1Ω.  The 

parameters  assigned  in  the  intrinsically  safe 

loop should not be over the specified value, that 

is, the capacity assigned among cables should 

not  be  over  0.083

μF,  the  inductance  assigned 

not over 4.1mH. 

3

  During  maintenance,  products  passing  the 

explosion-proof test should not be replaced and 

parts  and  structure  affecting  explosion-proof 

functions should not be modified.   

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  from 

defects in design, materials and workmanship during 

the warranty period. This warranty shall not apply to 

any  product  that  is  found  to  have  been  improperly 

installed  or used  in  any  way  not  in  accordance  with 

the  instructions  supplied  with  the  product.  Anybody, 

including  the  agents,  distributors  or  employees,  is 

not  in  the  position  to  amend  the  contents  of  this 

warranty.  Please  contact  your  local  distributor  for 

products not covered by this warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specification 

Power 

Loop 

voltage 

when 

activating 

24VDC

16VDC

28VDC

 

Power 

Loop 

voltage  in  standby 
state 

7VDC

5VDC

8VDC

 

Standby current 

5mA 

Active current 

50mA 

Wiring 

Polarized  two-wire  with  I-9333 
Interface 

Sound Level 

Sound  level:  85dB~115dB  (A 
weighted in 3m front). 

Flashing 
Frequency 

1.4×(1±20

)Hz

DC-9403(IS)

 

Tone  Modification 
Period 

0.7s±20

 

Explosion-proof 
marking 

Exib

CT6 Gb 

Explosion-proof 
Certificate 
Number 

CE17.2192 (DC-9404(IS) ) 

CE17.2190 (DC-9403(IS)) 

Security 

Barrier 

Parameters 
GST-AS-200 

U

0

28V, I

0

93mA 

Ingress  Protection 
Rating 

IP33 

Operating 
Temperature 

-10

℃~

+55

 

Relative Humidity 

95%, non condensing 

Application 

Indoor 

Material and Color 
of Enclosure 

ABS, 

red.

 

10

7

Ω

surface 

resistance

10

9

Ω,  plexiglass  in 

front 

Dimension (D×H) 

ф110mm×95.9mm 

Mounting 

Hole 

Spacing 

55mm

80mm 

Weight 

DC-9404(IS)

About 312.2g 

DC-9403(IS)

About 322.2g 

 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 