  When  the  detector  is  connected  with  conventional  FACP  or 

addressable zone monitor unit, if a 4.7k

Ω

end of line resistor is 

connected to the end of output loop, DB-01 base is used. The 
system composition is shown in Fig. 6.   

 

Fig. 6

 

  When  multiple  detectors  are  connected  with  a  remote 

indicator, a diode 1N5819 should be connected to Terminal 4 
of the orientation base in series before going to the positive of 
the remote indicator. System composition is shown in Fig. 7.   

   

Fig. 7 

Maximum  15 detectors can  be connected to  the output of  zone 
monitor unit. In case of broken circuit or removal of any detector, 
the unit will transmit a fault message to the FACP. If and AEOL is 
connected, normal operation of other device in the system will not 
be affected. 

Testing 

Note:  Before  testing,  make  sure  the  detector  is  properly 
installed and powered up.    Testing can only begin after the 
detector is powered up for 10 seconds.   

The  detector  must  be  tested 
after  installation  and  regular 
maintenance.  The  methods  are 
as follows: 
(1) Reed switch testing 
The testing area of the detector 
is shown in Fig. 8.   
Approach the commission tool to 
the  testing  area  of  the  detector 
and  hold  for  several  seconds 
until the detector alarms. 
(2) Temperature test 
Approach a heater (such as a hair drier) to the thermistor of the 
detector until it alarms. 
After  testing,  disconnect  power  to  the  detector  for  over  10 
seconds to reset it. Notify the proper authorities that the system is 
back to normal operation. 
If a detector fails in testing, clean it by the steps in “Maintenance”, 
and retest it. If it still fails, return it for repair. 

Maintenance 

  The detector should be installed just before commission and 

kept well  before  installation,  taken corresponding  measures 
for dust-proof, damp-proof and corrosion-proof. 

  The dust cover cannot be removed until the project has been 

plunged into usage.   

  Clean  the  detector  at  least  once  a  year  to  ensure  normal 

operation of the system. 

  Before cleaning, notify the proper authorities that the system 

is  undergoing  maintenance  and  will  temporarily  be  out  of 
service. Disable the zone or system undergoing maintenance 
to avoid unwanted alarms. 

  The  detector  should  be  tested  again  after  cleaning  and 

re-installing. 

 

  Protect the metal component on the PCB against damp and 

improper distortion. 

 

  Do fire simulation test at least once every 6 months.

 

Specification 

Operating Voltage 

24VDC(16VDC~28VDC) 

Standby Current 

60μA 

Alarm Current 

55mA 

Fire LED 

Red, periodically flash once in 
polling when the status is set to 
“ON”; don’t illuminate when the 
status is set to “OFF”. Periodically 
flash twice in fault; illuminate in 
alarming.   

Remote Indication 
Output

 

Polarity-sensitive, directly 
connecting with remote indicator 
(built in 10k resistor in series, 
maximum output current is 2.0mA);   
The remote indicator does not 
illuminate in normal and flashes in 
alarm.   

Class and Setup   

Classes 

A1R, 

A2S, 

BS 

programmable. 

Maximum Ripple 
Voltage 

2V ( peak-to-peak) 

Alarm Reset 

Instantaneous cut-out (10s Min, 
1.0VDCMax.) 

Wiring 

Polarized two wire   

Ingress Protection 
Rating 

IP2X 

Ambient Temperature 

Class A1: -10

~+50

 

Class A2: -10

~+50

 

Class B: -10

~+65

 

Typical Fixed 
Temperature 

Class A1:    58

 

Class A2:    62

 

Class B:      77

 

Relative Humidity 

≤95%, non-condensing 

Material   

ABS 

Dimensions 

Diameter: 100mm 
Height: 53.3mm (with base) 

Mounting Hole Spacing 

45mm~75mm 

Weight 

About 110g (with base) 

Accessories and Tools 

Module 

Name 

Remarks 

P-9910B 

Handheld Programmer 

Order separately 

DB-01 

Base 

Order separately 

DB-01D 

Base 

Order separately 

DP-9907   

Active End of Line Unit   

Order separately 

T-MT 

Commission Tool 

Order separately 

WEEE Information 

2012/19/EU  (WEEE  directive):  Products  marked  with  this 
symbol cannot be disposed of as unsorted municipal waste 
in  the  European  Union.  For  proper  recycling,  return  this 
product  to  your  local  supplier  upon  the  purchase  of 
equivalent  new  equipment,  or  dispose  of  it  at  designated 
collection points. 

Limited Warranty

 

GST

 warrants that the product will be free from defects in design, 

materials  and  workmanship  during  the  warranty  period.  This 
warranty shall not apply to any product that is found to have been 
improperly  installed  or  used  in  any  way  not  in  accordance  with 
the instructions supplied with the product. Anybody, including the 
agents, distributors or employees, is not in the position to amend 
the contents of this warranty. Please contact your local distributor 
for products not covered by this warranty. 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532        [email protected]   www.gst.com.cn 

 

Отзывы: