background image

 

30302556                                                                                                                                                                    Issue 2.04

 

                                       

 

 

Features 

 

High bright red LEDs are used as light source. 

 

High sound level. 

 

Circuitry and base are twisted together.   

 

Standard: EN 54-3. 

Description 

C-9404(Ex)  Explosion  Proof  Conventional 

Sounder 

and 

C-9403(Ex) 

Explosion 

Proof 

Conventional Sounder Strobe (hereinafter called the 
sounder/sounder strobe) is a kind of audible/audible 
and visual alarm device used to warn people in field 
when fire occurs. It’s applicable to zone 1 and zone 2 
of  areas  with  explosion-proof  requirement  in 
petroleum and chemical industries. It can match with 
I-9333 Interface.

 

Both shallow base with 25.5mm high and deep base 
with 40mm high are available, it employs deep base 
if there is no special statement in this manual. 

 

Connection & Wiring 

Terminals on the base are shown in Fig. 2. 

G

1

K

1

D

D

2

1

2

Z

2

K

S

Z

97.5mm

80mm

55mm

Arch knock off Hole

5mm

  

 

Fig. 1                                                Fig. 2

 

D1+(9),  D2-  (7):  Connected  with  I-9333 

Interface,  polarized.  D1 is  connected  with (3) of the 
safety barrier and D2 to (4). 

 

Recommended Wiring 

Intrinsically  safe  cable  with  cross  section  not  less 
than 1.5mm

2

, subject to local codes.

 

Installation 

 

When  the  sounder/sounder  strobe  is  surface 

mounted,  it  should  be  placed  0.2m  from  the  ceiling 
for normal space height. When conduit is embedded, 
the  base  can  be  mounted  on  the  electrical  box. 
When  conduit  is  surface  mounted,  the  deep  base 
should  be  adopted.  Knock  the  knock-off  hole,  then 
connect  the  conduit  with  it.  The  mounting  hole 
spacing and mounting direction are shown in Fig. 2. 
Mounting  method  is  shown  in  Fig.  3a  and  Fig.  4. 
When 

the 

shallow 

base 

is 

required, 

the 

sounder/sounder 

strobe 

only 

adopts 

conduit 

embedded. Its mounting method is shown in Fig. 3b. 

 

 

Conduit

Knock-off Hole

Electrical Box

sounder/Sounder Strobe

Fig. 3a 

Conduit

Electrical Box

sounder/Sounder Strobe

 

         

Fig. 3b (shallow base) 

Conduit

sounder/Sounder Strobe

 

Fig. 4 

 

The  base  and  the  sounder/sounder  strobe  are 

twisted  together.  When  mounting,  remove  the 
sounder  strobe,  thread  cables  through  the  cable 
entry  in  the  base  and  connect  with  corresponding 
terminals,  then  twist  the  sounder/sounder  strobe 
onto the base. 

 

C-9404(Ex)

 

Explosion Proof Conventional Sounder

   

C-9403(Ex) 

Explosion Proof Conventional Sounder Strobe

 

 

 