30301837   

         

                                                                                             

                     

  Issue 1.05

 

                                       

 

 

Features 

 

Built-in  microprocessor  samples  and  collects 
data in real time.   

 

Rate of rise and fixed temperature alarm mode. 

 

Standard: UL 521. 

Description 

C-9103(UL)  Conventional  Rate  of  Rise  and  Fixed 
Temperature 

Heat 

Detector  (the 

detector) 

is 

non-addressable.  With  built-in  microprocessor,  it  is 
fixed  with  highly  reliable  fire  judging  program  and 
works stably.   

When the detector checks fire signal, it can change its 
own  current to transmit fire  signal to  control  panel  or 
interface module.  The  detector  keeps  illuminating  fire 
LED  to  indicate  fire  status  until  resetting.  Used 
together with P-9907 Active End of Line Unit (AEOL), 
it can connect with compatible fire alarm control panel 
to conduct the processing of detector signals. 

Connections and Wiring 

The orientation base is shown in Fig. 2. 

       

C

 

Record Label

0

Mounting Hole

3

B

-Z

D

A

 

Fig. 1                              Fig. 2

 

The  bottom  and  orientation  base  of  the  detector  are 
shown  in  Fig.1  and 2.    There  are four  terminals  with 
numbers on the base, “1” connects with the anode of 
the output end of compatible controller,    “2” connects 
with  the  power  anode  of  the  next  detector  as  output 
(terminal  No.  “1”),    “3”  connects  with  the  power 
cathode of the next detector (terminal No. “3”) and the 
cathode of the output end of compatible controller, “4” 
doesn’t  connect  to  any  wires  but  is  used  to  fix  the 
detector accessorily.

 

Recommended Wiring: 

1.0mm

or  above  fire  cable  for  all  terminals,  laid 

through metal conduit  or  flame-proof  conduit,  subject 
to local codes.   

Installation 

There  are  location  elements  on  the  detector  and  the 
orientation base to ensure there is only one installing 
position.    There are two marks on point A and B of the 
orientation  base,  and  a  mark  on  point  C  of  the  side 
face  of  bottom  of  the  detector.    When  installing, 
aligning  the  mark  C  of  the  detector  to  point  A  of  the 
orientation base, rotate the detector clockwise to point 
B, then the detector is installed.     

 
 

 

 

Mounting of the detector is shown in Fig. 3. 

Detector

Orientation Base

Wiring Tube

Embedded Box

 

Fig. 3 

Application 

Warning:  The  detector  should  be  connected  with 
fire  alarm  control  panel  or  other  devices  with 
current limit function. Otherwise the detector may 
be destroyed by too heavy alarm current. 

4.7k/1w    terminal  resistor  can  be  connected 

between terminal “2” and “3” of the last base in a loop.   
System connection is shown in Fig. 4. 

Output-

Compatible 
Controller

DZ-03 Base

4.7k
Terminal 
Resistor

DZ-03 Base

CAUTION: 

DO NOT USE LOOPED WIRE UNDER TERMINAL 3. BREAK WIRE 

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

Fig. 4 

Maintenance 

1.  Before installation, the detector should be kept well 
and  adopted  the  corresponding  measures  for 
dust-proof, damp-proof and corrosion-proof.   
2.  The dust cover cannot be removed until the project 
has been plunged into usage. 
3.  The detector should be cleaned at least once each 
year. 
4.  Before  cleaning,  notify  relative  departments  that 
the system is undergoing maintenance and will be out 

C-9103(UL) 

Conventional Rate of Rise 

and Fixed Temperature Heat Detector

 